This notification introduces the Delhi Fire Service (Amendment) Rules, 2026, to amend the Delhi Fire Service Rules, 2010, by exercising powers under Section 63 of the Delhi Fire Service Act, 2007.

Detailed Summary

The Lieutenant Governor of the National Capital Territory of Delhi, through the Home Department (Delhi Fire Service), issued a notification on August 28, 2026, introducing the Delhi Fire Service (Amendment) Rules, 2026. These rules amend the Delhi Fire Service Rules, 2010, under Section 63 of the Delhi Fire Service Act, 2007 (Delhi Act 2 of 2009). The amendments come into force upon the notification of the amended UBBL-2016 under sub-section (1) of Section 57 of the Delhi Development Act, 1957, by the Delhi Development Authority; however, pending applications will be processed under prior provisions. Key changes include the omission of rule 2(viii) and "National Building Code of India" from rule 2(xiii) of the Delhi Fire Service (Amendment) Rules, 2025, along with renumbering rules 2(ix) as 2(viii) and 2(xiii) as 2(xii) in the 2025 rules. In the Principal Rules (Delhi Fire Service Rules, 2010), rules 2(x) to 2(xii) are renumbered as 2(ix) to 2(xi). Furthermore, "National Building Code of India" in rule 29 of the 2025 rules is replaced with "Building Bye – Laws", and rule 33 of the 2025 rules is entirely substituted. The new Rule 33 defines comprehensive minimum standards for fire prevention and fire safety for buildings, referencing the Building Bye-Laws for matters like 06-meter fire engine access, exit protection, fire extinguishers, automatic detection systems, hydrants, emergency power, and refuge areas. It also grants the Director power to mandate international standards for uncovered occupancies and allows the Government to relax or modify requirements for specific buildings or areas for recorded reasons. Additionally, Form 'J' of the Seventh Schedule, an 'INSPECTION REPORT BY FIRE SAFETY AUDITOR UNDER RULE-35 OF DFS RULES-2010', is substituted to detail 18 categories of fire safety compliance checks.

Full Text

REGD. No. D. L.-33002/99 GOVERNMENT OF INDIA Delhi Gazette SG-DL-E-28082026-275847 EXTRAORDINARY PUBLISHED BY AUTHORITY No. 251] DELHI, MONDAY, FRIDAY 28, 2026/BHADRA 6, 1948 [N. C. T. D. No. 187 PART IV GOVERNMENT OF THE NATIONAL CAPITAL TERRITORY OF DELHI HOME DEPARTMENT (Delhi Fire Service) NOTIFICATION Delhi, the 28th August, 2026 F. No. DFS/HQ/Misc./2026/01(E-331845)/501.—In exercise of the powers conferred by Section 63 of the Delhi Fire Service Act, 2007 (Delhi Act 2 of 2009), the Lieutenant Governor of the National Capital Territory of Delhi hereby makes the following amendments in the Delhi Fire Service Rules, 2010, namely: 1. Short title and commencement- (1) These Rules may be called the Delhi Fire Service (Amendment) Rules, 2026. (2) They shall come into force on the date as and when the amended UBBL-2016 is notified under sub-section (1) of Section 57 of Delhi Development Act, 1957 by the Delhi Development Authority. Provided that all applications pending on date of commencement shall be processed under the provisions in force on the date of application. 2. In the Delhi Fire Service (Amendment) Rules, 2025, rule 2(viii) shall be omitted. 3. In the Delhi Fire Service (Amendment) Rules, 2025, "National Building Code of India" shall be omitted from rule 2(xiii). 4. In the Delhi Fire Service (Amendment) Rules, 2025, rule 2(ix) shall be renumbered as rule 2(viii) and rule2 (xiii) shall be renumbered as rule 2(xii). 5. In the Delhi Fire Service Rules, 2010 (hereinafter referred to as the Principal Rules), rule 2(x) to rule 2(xii) shall be renumbered as rule 2(ix)to rule 2(xi) in sequence. 6. In the Delhi Fire Service (Amendment) Rules, 2025, “National Building Code of India" shall be substituted with "Building Bye – Laws" in rule 29. 7. In the Delhi Fire Service (Amendment) Rules, 2025, the rule 33 shall be substituted namely, 33. Minimum standards for fire prevention and fire safety for buildings 1. The Minimum standards for fire prevention and fire safety for the buildings as may be applicable with reference to the height of the building and class of occupancy for the purpose of Section 32 and Section 35 of the Act shall be as are provided in the Building Bye-Laws as amended time to time relating to the following matters: (1) Minimum 06 meters right of way for fire engines upto the premises. (2) Protection of Exits from fire products by means of Fire Check Door (s) and or pressurization. (3) Fire and Smoke Barrier, Fire Stop and Smoke Management System. (4) Fire Extinguishers. (5) First-Aid Hose Reels. (6) Automatic fire detection and alarming system. (7) MOEFA. (8) Public Address System and or Voice Evacuation System. (9) Automatic Sprinkler and Fire Suppression System. (10) Internal Hydrants (Wet Riser and or Down Comer) and Yard Hydrants (Ring Main). (11) Fire Pump House with Pumping Arrangements and protected access for fireman upto pump house. (12) Captive Water Storage for firefighting purposes. (13) Exit Signage, Floor Numbering & Reflective Tape marking in corridors leading to Exits. (14) Provision of Fire Tower and Fire Lifts. (15) Emergency power for the following system and equipment where provided: - a) Fire pumps b) Pressurization and smoke venting; including its ancillary systems such as dampers and actuators. c) Fireman's lifts (including all lifts). d) Exit signage lighting e) Emergency lighting f) Fire alarm system g) Public address (PA) system (relating to emergency voice vacuation and annunciation) h) Magnetic door holds open devices i) Lighting in fire command centre. (16) Fire Check Floor and Refuge Area. (17) Fire Control room with Automated Continuous Monitoring System. (18) Special Fire Protection Systems for Protection of Special Risks: Provided that classes of occupancies or buildings or premises for which fire prevention and fire safety measures are not provided in the Building Bye-Laws, the Director may require owner or occupier of such occupancies or buildings or premises to provide fire prevention and fire safety measures in accordance with international standards as may be provided by the fire prevention wing: Provided further that where the Government is of the opinion that it is necessary or expedient so to do, it may, by order, for reasons to be recorded in writing, relax or modify or annul any requirement concerning fire prevention and fire safety measures under these rules with respect to any class of occupancy in any building or premises in special areas or in respect of any building or premises in any area that was constructed or which was under construction prior to the date of enforcement of these rules. (2) Where the Director is of the opinion that it is necessary or expedient so to do, it may, for reason to be recorded in writing, require the owner or occupier of the buildings or premises to provide additional fire prevention and fire safety measures." 6. In the Delhi Fire Service (Amendment) Rules, 2026, the Form 'J' of the Seventh Schedule shall be substituted namely, FORM 'J' [See rule 35] INSPECTION REPORT BY FIRE SAFETY AUDITOR UNDER RULE-35 OFDFS RULES-2010 1. UID No. 2. Name and address of the building: 3. Details of below and above ground Levels along with each level Occupancy As observed during inspection: 4. Details of Previous FSC: 5. Date of inspection: 6. Name and designation of the representative Of the owner/occupier present during inspection: +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | S. | Minimum Standards on fire prevention and | Requirement under | Status at | Remarks | | No. | fire safety | Rule | site | MR/NMR* | | | Under Rule 33 | 35 | | | +=====+===================================================+=======================+=================+=================+ | 1. | Access to building | | | | | | • Width of access road | | | | | | • Gate width | | | | | | • Width of internal access | | | | | | Road all around the building | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 2. | Protection of Exits from fire products | | | | | | a. Fire Check Doors | | | | | | • Upper Floors | | | | | | • Basements | | | | | | b. Pressurization | | | | | | • Staircase | | | | | | • Lift well | | | | | | Lift Lobby | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 3. | a. Fire and smoke Barrier, Fire Stop and Smoke Management. | | | | | | • Fire check door | | | | | | • Sealing of electrical shafts | | | | | | • Fire/Smoke/Water Curtain | | | | | | • Fire Dampers | | | | | | b. Smoke Management System | | | | | | • Basements | | | | | | • Ground and Upper floors | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 4. | Fire Extinguishers | | | | | | • Total numbers | | | | | | • Types | | | | | | • IS marking | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 5. | First-Aid Hose Reels | | | | | | • Total numbers on each | | | | | | floor | | | | | | • Length of hose reel hose | | | | | | • Nozzle diameter | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 6. | Automatic fire detection and alarming system | | | | | | • Type of detectors | | | | | | • Location of Main Panel | | | | | | • Location of Repeater Panel | | | | | | • Hooters' Location | | | | | | • Alternate source of power | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 7. | MOEFA | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 8. | Public Address System and or | | | | | | Voice Evacuation System | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 9. | Automatic Sprinkler and Fire Suppression System | | | | | | • Basements | | | | | | • Ground and Upper floors | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 10. | (a)Internal Hydrants | | | | | | • Size of riser/down-comer | | | | | | • Number of hydrants per | | | | | | floor | | | | | | • Hose Box | | | | | | (b) Yard Hydrants | | | | | | • Total number of hydrants | | | | | | • Hose Box | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 11. | Pumping Arrangements | | | | | | a. Ground/Basement Level | | | | | | • Discharge of main Pump | | | | | | • Head of Main pump | | | | | | • Number of main pumps | | | | | | • Jockey Pump output | | | | | | • Jockey pump head | | | | | | • Standby Pump output | | | | | | • Standby Pump Head | | | | | | • Auto Starting/Manual | | | | | | Stopping | | | | | | • Pump House protected | | | | | | Access for fireman | | | | | | b. Terrace level | | | | | | • Discharge of pump | | | | | | • Head of the pump | | | | | | • Power Supply | | | | | | • Auto Starting of pump | | | | | | Access to terrace tank | | | | | | /pump | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 12. | Captive Water Storage for firefighting | | | | | | a. Underground tank capacity | | | | | | • Draw-off connection | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | | • Fire service inlet | | | | | | • Access to tank | | | | | | b. Overhead Tank capacity | | | | | | • Access to tank | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 13. | • Exit Signage | | | | | | • Floor Numbering | | | | | | • Reflective Tape marking in | | | | | | Corridors leading to Exits | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 14. | Provision of Fire Tower and Fire Lifts. | | | | | | • Protection of Fire Tower | | | | | | • Protection of lobby | | | | | | • Communication In lift Car | | | | | | • Fireman's Grounding | | | | | | Switch | | | | | | • Lift Signage | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 15. | Emergency power supply | | | | | | • Fire pumps | | | | | | • Pressurization and smoke venting; | | | | | | including its ancillary systems such | | | | | | as | | | | | | Dampers and actuators. | | | | | | • Fireman's lifts (including all | | | | | | lifts). | | | | | | • Exit signage lighting | | | | | | • Emergency lighting | | | | | | • Fire alarm system | | | | | | • Public address (PA) system (relating to | | | | | | emergency voice evacuation and | | | | | | annunciation) | | | | | | • Magnetic door holds open | | | | | | devices. | | | | | | • Lighting in fire command | | | | | | centre | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 16. | Fire Check Floor and Refuge Area. | | | | | | • Fire Check Floor | | | | | | • Refuge Area | | | | | | • Total Area | | | | | | • Location | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 17. | Fire Control room with Automated Continuous Monitoring System. | | | | | | • Detector System Panel | | | | | | • Flow Switch Panel | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | | • PA System Panel | | | | | | • Battery backup | | | | | | • Building Floor Plans | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ | 18. | Special Fire Protection System | | | | | | For Protection of special Risks, if any: | | | | +-----+---------------------------------------------------+-----------------------+-----------------+-----------------+ *MR/NMR: Meeting the requirement/Not Meeting the requirement Notes (if any): Signature. Name of the Fire Safety Auditor. Email ID. Telephone No. Mobile No.. Fire Safety Auditor Level........... Registration No......... Stamp. By Order and in the Name of the Lt. Governor of the National Capital Territory of Delhi, AJAY KUMAR SHARMA, Dy. Secy. (Home) Uploaded by Dte. of Printing at Government of India Press, Ring Road, Mayapuri, New Delhi-110064 and Published by the Controller of Publications, Delhi-110054. RAVINDER KUMAR Digitally signed by RAVINDER KUMAR Date: 2026.08.28 16:21:50+05'30'

Never miss important gazettes

Create a free account to save gazettes, add notes, and get email alerts for keywords you care about.

Sign Up Free