Full Text
6001 GI/202 4 (1)
EXTRAORDINARY
PART II —Section 3 —Sub-section ( ii)
PUBLISHED BY AUTHORITY
No. 3668 ] NEW DELHI, THURSDAY , SEPTEMBER 19, 2024 /BHADRA 28 , 194 6
CG-DL-E-23092024-257378
MINISTRY OF POWER
NOTIFICATION
New Delhi, the 18th September , 2024
S.O. 4007(E).—In exercise of the powers conferred by sub -para 3.2 of Para 3 of the Guidelines circulated
under Section 63 of the Electricity Act, 2003 (No. 36 of 2003), the Central Government, on the recommendations of
23rd meeting of National Committee on Transmission, hereby notifies the following transmission scheme under TBCB
mode, with details of respective Bid -Process Coordinator (BPC): -
Name & Scope of the Transmission Scheme
Name: Transmission System for Integration of Kurnool -IV REZ - Phase -I (for 4.5 GW)
Tentative implementation timeframe: 24 months
BPC: REC Power Development and Consultancy Limited
Scope:
Sl. No. Scope of the Transmission Scheme Capacity/(Km)
1. Establishment of 4x1500 MVA, 765/400 kV &
4x500 MVA, 400/220 kV Kurnool -IV Pooling
Station near Kurnool, Andhra Pradesh along with
2x330 MVAr (765 kV) bus reactors at Kurnool -IV
PS with provision of two (2) sections of 4500
MVA each at 400 kV level
Future Provisions: Space for
➢ 765/400 kV, 1500 MVA, ICTs – 2 Nos.
➢ 765 kV ICT bays – 2 Nos.
➢ 400 kV ICT bays – 2 Nos.
➢ 400/220 kV, 500 MVA, ICTs – 14 Nos.
➢ 400 kV ICT bays – 14 Nos.
➢ 220 kV ICT bays – 14 Nos.
➢ 765 kV line bays – 8 Nos. (with provision
for SLR)
➢ 400 kV line bays – 12 Nos. (with provision
for SLR)
➢ 220 kV line bays – 20 Nos.
➢ 220 kV Bus Sectionalizer : 2 sets • 765/400 kV, 1500 MVA, ICTs – 4 Nos. (13x500
MVA incl. 1 spare unit)
• 765 kV ICT bays – 4 Nos.
• 400 kV ICT bays – 4 Nos.
• 400/220 kV, 500 MVA, ICTs – 4 Nos.
• 400 kV ICT bays – 4 Nos.
• 220 kV ICT bays – 4 Nos.
• 765 kV line bays – 4 Nos. (at Kurnool -IV PS for
termination of Kurnool -IV – Bidar and Kurnool -
IV – Kurnool -III 765 kV D/c lines)
• 765 kV, 330 MVAr Bus Reactor – 2 Nos.
• 765 kV Bus Reactor bays – 2 Nos.
• 220 kV line bays – 6 Nos.
• 220 kV Bus Sectionalizer : 1 set
• 220 kV Bus Coupler (BC) Bay – 2 Nos.
• 220 kV Transfer Bus Coupler (TBC) Bay – 2 Nos.
➢ 220 kV Bus Coupler (BC) Bay – 2 Nos.
➢ 220 kV Transfer Bus Coupler (TBC) Bay –
2 Nos.
➢ 400 kV Bus Sectionalizer : 1 set
2. Kurnool -IV – Bidar 765 kV D/c line (about 330
kms) with 330 MVAR SLR (convertible) at both
ends on both circuits ~ 330 km
• 765 kV line bays – 2 Nos. (at Bidar PS)
• 765 kV, 330 MVAr SLR at Kurnool -IV PS – 2
Nos. (7x110 MVAr incl. 1 switchable spare unit
for both bus reactor and line reactor)
• 765 kV, 330 MVAr SLR at Bidar PS – 2 Nos.
(7x110 MVAr incl. 1 switchable spare unit)
3. Kurnool -IV – Kurnool -III PS 765 kV D/c line
(about 150 kms) with 240 MVAR SLR
(convertible) at Kurnool -IV end on both circuits ~ 150 km
• 765 kV line bays – 2 Nos. (at Kurnool -III PS)
• 765 kV, 240 MVAr SLR at Kurnool -IV PS – 2
Nos. (7x80 MVAr incl. 1 switchable spare unit)
4. + 300 MVAR STATCOM at Kurnool -IV PS
along with 2x125 MVAr MSR • 400 kV bay – 1 No.
5. Augmentation of 1x1500 MVA, 765/400 kV ICT
(3rd) at C’Peta • 765/400 kV, 1500 MVA, ICT – 1 No.
• 765 kV ICT bays – 1 No.
• 400 kV ICT bays – 1 No.
6. LILO of Vijayawada -Nellore 400 kV D/c line at
C’Peta (about 20 kms) ~ 20 km
• 400 kV line bays – 4 Nos. (at C’Peta for
termination of LILO of Vijayawada -Nellore 400
kV D/c line at C’Peta)
Note:
a) POWERGRID shall provide space for 2 nos. of 765 kV line bays at Kurnool -III for termination
of Kurnool -IV – Kurnool -III PS 765 kV D/c line
b) Developer of Bidar PS shall provide space for 2 nos. of 765 kV line bays at Bidar PS for
termination of Kurnool -IV – Bidar 765 kV D/c line
c) As both the circuits of Kurnool -IV – Bidar 765 kV D/c line are proposed to be LILOed at
Shadnagar, Telangana under Phase -II, the line should be routed via Shadnagar area for
optimisation of establishment of 765/400 kV Shadnagar Station under Phase -II.
2. The appointment of the Bid Process Coordinator is subject to the conditions laid down in the Guidelines issued
by Ministry of Power in this regard, amended from time to time.
[F. No. 15/3/2018 -Trans -Part(4) ]
NAOREM INDRAKUMAR SINGH , Under Secy . (Transmission)
Uploaded by Dte. of Printing at Government of India Press, Ring R oad, Mayapuri, New Delhi -110064