CG-DL-E-04072026-274074
MINISTRY OF DEFENCE
NOTIFICATION
New Delhi, the 3rd July 2026
S.R.O. 13(E).—The following draft of the Barrackpore Cantonment Building bye-laws,
2026, which the Cantonment Board proposes to issue, in exercise of the powers conferred by
section 251 of the Cantonments Act, 2006 and in supersession of notification number 492, dated
22.04.1939, except as respects things done or omitted to be done before such supersession, the
draft Barrackpore Cantonment Building Bye-Laws, 2026 is hereby published for the information of
the public likely to be affected thereby; and notice is hereby given that the said draft Bye-laws shall
be taken into consideration on or after the expiry of a period of thirty days from the date on which
copies of the Gazette of India containing this Bye-laws are made available to the Public; and the
said draft Bye-Laws is also available at the office of the Cantonment Board, Barrackpore and on
the website http://barrackpore.cantt.gov.in
Any person interested in making any objections or suggestions on the proposals contained
in the draft Bye-laws may forward the same in writing, for consideration of the Cantonment Board
within the period so specified to the Cantonment Board, Barrackpore or at e-mail address :
[email protected]
[F. No. B/I/5/I]
SAPAN KUMAR, IDES, Chief Executive Officer
The Draft of the Barrackpore Cantonment Board Building Bye-Laws, 2026
CHAPTER I
GENERAL
1. SHORT TITLE AND COMMENCEMENT AND EXTENT :- (1) These Bye-Laws shall be called the
Barrackpore Cantonment Building Bye-Laws,2026.
(2) These shall come into force on the date of final publication in the Official Gazette by the Central
Government.
(3) These Bye-Laws shall apply within the limits of Barrackpore Cantonment.
2. DEFINITIONS :- In these Bye-laws, unless the context otherwise requires:
(1) “Act” means the Cantonments Act, 2006 as amended from time to time;
(2) “Application” means an application made in such a form as may be specified by the
authority from time to time;
(3) “Applicant” means a person who has legally valid occupancy rights on leased or old grant
or private land and intends to erect / re-erect a building or to make any addition / alternation
in the building;
(4) “Approved” means approval granted by the Competent Authority as prescribed under the
Act;
(5) “Architect” means any person who holds a valid registration with the Council of
Architecture, India as per the provisions of the Architects Act 1972;
(6) "Addition to abuilding" means addition to the cubic contents of a building;
(7) “Alteration of a building" means,-
i. The sub-division of any room in such building so as to convert the same into two
or more separate rooms, or
ii. The change in two or more rooms in such building which increases or diminishes
the cubic content of any room or rooms.
iii. The conversion of any passage or space in such building into a room or rooms;
(8) “Air-Conditioning” means the process of treating air so as to control simultaneously its
temperature, humidity, cleanliness and distribution to meet the requirement of conditioned
space;
(9) “Access” means a clear approach to a plot or a building;
(10) “Apartment” means whether called block, chamber, dwelling unit, flat, office, showroom,
shop, godown, premises, suit, tenement, unit or by any other name, means separate and
self-contained part of any immovable property, including one or more rooms or enclosed
spaces, located on one or more floors or any part thereof, in a building or on a plot of land,
used or intended to be used for any residential or commercial use such as residence,
office, shop, showroom or godown or for carrying on nay business, occupation, profession
or trade, or for any other type of use ancillary to purpose specified;
(11) “Accessory Building" means a building separate from the main building on a plot and
containing one or more rooms for accessory use such as servant quarters, garage,
storerooms etc.;
(12) “Appendix” means an appendix to these Bye-Laws;
(13) “Balcony” means a horizontal projection including a handrail, balustrade or a parapet to
serve as a sitting out place;
(14) “Barrier free” means a barrier free environment which enables people with disabilities to
move safely and freely and to use the facilities within the built environment;
(15) “Basement” means the lowest storey of a building below or partly below ground level or
adjoining ground level;
(16) “Board” shall mean a Cantonment Board constituted under the Cantonments Act, 2006;
(17) “Building” means a house, outhouse, stable, latrine, shed, hut or other roofed structure
whether of masonry, brick, wood, mud, metal or other material, and any part thereof, and
includes a well and a wall other than a boundary wall but does not include a tent or other
portable and temporary shelter;
(18) "Building Height" means the vertical distance measured in the case of flat roof from the
average level of the centre line of the adjoining street to the highest points of the building
adjacent to the street wall; in the case of pitched roofs up to the point where the external
surface of the outer wall intersects the finished surface of the sloping roof; and in the case
of gable facing the road, the midpoint between the caves level and the ridge. Architectural
features serving, chimneys, water tanks, and other ornamental features which are not
intended for human habitation and serving no other function except that of decoration shall
be excluded for the purpose of taking heights, and if the building does not about on a street
the height shall be measured above the average level of the ground around and
contiguous to the building;
(19) “Building Line” means the line upto which the plinth of a building adjoining on a street or
on an extension of a street or on a future street may lawfully extent and includes the line
prescribed, if any, in any scheme;
(20) “Building Envelop” means the horizontal spatial limits upto which a building may be
permitted to be constructed on a plot which shall not exceed the clear setbacks as
prescribed in the Bye-Laws;
(21) “Bungalow area” means area outside notified civil area with old grant/lease hold
bungalows excluding privately held properties;
(22) "Built up Area" means the area covered by a building on all floors including cantilevered
portion, mezzanine floors, if any, but excluding the areas specifically exempted from
computation of Floor Space Index (F.S.I) under these Regulations;
(23) "Butchery” means a slaughter house where animals (sheep and goats) are slaughtered
under the supervision of competent Authority;
(24) "Cabin" means a non-residential enclosure constructed of non-load bearing, non-masonry
partitions;
(25) "Chajja" means a sloping or horizontal structural overhang usually provided over openings
on external walls to provide protection from sun and rain and for purpose of architectural
appearance;
(26) “Canopy” means an overhead roof or else a structure over which a fabric or metal
covering is attached, able to provide shade or shelter from weather conditions such as sun,
hail, snow and rain. A canopy can also be a tent, generally without a floor;
(27) “Competent Authority” means the authority to sanction the building plan as prescribed
under Chapter 10 of the Cantonments Act, 2006;
(28) "Commercial Building" means a building used or constructed or adapted to be used the
whole or a substantial part of building for commercial purposes;
(29) "Ceiling Height" means vertical distance between the finished floor and the ceiling;
(30) "Central Government" for the purposes of these Bye-Laws means the Government of the
Union in the Ministry of Defence;
(31) "Chimney" means an upright shaft containing and encasing one or more flues;
(32) “Civil Area” means an area declared to be a civil area by the central Government under
Sub-Section (1) of Section 46 of the Act;
(33) "Civil Engineer" means any person who is a graduate of civil engineering from a
recognized Indian or foreign university duly approved by Govt. of India or is a member of
Civil Engineering Division of the Institution of Engineers (India) and is competent to carry
out supervision of building works as per approved drawings and design;
(34) "Corner Plot or Site" means a plot or site at the junction of and fronting on two or more
intersecting streets;
(35) "Combustible Material" means any material if it burns or adds heat to a fire when tested
for combustibility in accordance with good practice;
(36) "Courtyard" means a space open to the sky enclosed or partially enclosed, by walls or by
railing and shall be at ground floor level;
(37) "Cup-board" means a space used for storage of household goods/dress having
shelves/partitions not more than 2.5 meters apart;
(38) "Covered Area" means ground area covered by the building immediately above plinth
level, but does not include the space covered by the following:
i. Garden, rockery, well and well structure, plant nursery, water pool, swimming pool
(if uncovered), platform around a tree, water tank, fountain, bench, with open to
pandunen closed sites and the like;
ii. Drainage, culvert, conduit, catch pit, gully pit, chamber, gutter, septic tank, soakage
pit and the like;
iii. Compound wall, gate, canopy, uncovered staircases, areas covered by chajja and
the like;
iv. Maximum Area of 4.2 sq meter for one toilet cum bathroom unit in each floor.
(39) "Damp Proof Course" A course consisting of appropriate water proofing material provided
to prevent penetration of dampness or moisture from any part of the ground to the structure
or from one part of the structure to any other part of it;
(40) "Drain" means a line of pipes including all fittings and equipment such as manholes,
inspection chambers, traps, gully traps and floor traps, used for the drainage of a building,
or a number of buildings, or yards appurtenant to buildings, within the same cartilage. Drain
shall also include open channels used for conveying surface water;
(41) "Drainage" means the removal of any liquid by a system constructed for this purpose;
(42) "Dwelling Unit/Tenement" An independent housing unit with separate facilities for living,
cooking and sanitation needs;
(43) “Demolished” meaning total dismantling of an existing building;
(44) “Equivalent Car Space (ECS)” means the space occupied by the vehicle as well as the
minimum space needed to move it into and out of the space and one equivalent car space
is as defined in National Building Code, as amended from time to time;
(45) "Existing Building or Use" means a building, structure or its use as sanctioned or
deemed to have been sanctioned by the Competent Authority, existing before the
commencement of the Bye-laws;
(46) “Exit” means a passage, or means of egress from any buildings, storey or floor area to a
street or any other open space of safety;
a. Vertical exit: It is a means of exit used for ascending or descending between two or
more levels including stairways, ramps and fire escapes;
b. Horizontal exit: It is a protected opening through or around a fire-resistant wall or
bridge connecting two buildings;
c. Outside exit: It is an exit from the building to a public way or to an open area
leading to a public way or an enclosed fire resistant passage leading to a public
way;
(47) “Enclosed Staircase” means a staircase separated by fire resistant walls and doors from
the rest of the buildings;
(48) "External Wall" means outer wall of a building not being a partition wall, even though
adjoining to a wall of another building and also means, a wall abutting on an interior open
space of any building; all external walls shall be a minimum of 230 mm brickwork in suitable
mortar or of suitable thickness as per structural design in case of reinforced concrete;
(49) “Floor” means the lower surface in a storey on which one normally walks in a building. The
general term, floor, unless otherwise specifically mentioned, shall not refer to a mezzanine
floor. Sequential numbering of floor shall be determined by its relation to the determining
entrance level. For floors at or wholly above ground level the lowest floor in the building
with direct entrance from the road/street to be termed as Ground floor. Other floors above
ground floor shall be numbered in sequence as Floor 1, Floor 2, with numbers increasing
upwards;
(50) "Floor Area Ratio" or "FAR" means the quotient obtained by dividing the multiple of the
total of the covered area on all floors and hundred by the area of the plot i.e.
(51) "Floor Space Index" or "FSI" means the quotient obtained by dividing the multiple of the
total of the covered area on all floors by the area of the plot i.e.
FSI= Total covered area of all floors
Plot Area
(52) “Flue” means a confined space provided for the conveyance to the outer air of any product
of combustion resulting from the operation of any heat producing appliance or equipment
employing solid, liquid or gaseous fuel;
(53) “Footing” means offset portions at the base of a foundation to provide a greater bearing
area;
(54) “Foundation” means that part of the structure which is below the lower most floor and
which provides support for the superstructure and which transmits loads of the super
structure to the ground;
(55) “Frontage” means the measurement of the side of any site abutting the road;
(56) “Front Open Space / Margin / Setback” means the distance between the boundary line of
plot abutting the means of access/road/street and the building line. In case of plots facing
two or more means of access, roads / streets, the plot shall be deemed to front on all such
means of accesses/roads/streets;
(57) “Ground Coverage” means the quotient obtained in terms of percentage by dividing the
plinth areas of Ground floor by plot area i.e.
Ground Coverage=Plinth area of ground floor x 100
Plot Area
(58) “Gallery” means an intermediate floor or platform projecting from a wall of an auditorium or
hall providing extra floor, additional seating accommodation etc.;
(59) “Garage Private” means a building designed or used for the parking of a motor car or
other vehicles;
(60) “Ground Level” Means the finishing surface after formation cutting of the site from where
erection of the building starts;
(61) “Group Housing” means housing of more than one dwelling unit, where land is owned
jointly as in the case of cooperative society or public agencies such as local authorities or
housing boards or property developers etc. and the construction is under taken by one
agency but shall not include properties which are co-owned by the family members;
(62) “Habitable Room” means a room occupied or designed for occupancy by one or more
persons for study, living, sleeping, eating, kitchen if it is part of living room but does not
includes bathroom, water closet compartments, laundries, serving and storage pantries,
corridors, cellars, attics and other spaces that are not used frequently or during extended
period;
(63) “Height of a Room” means the vertical distance measured from the finished floor surface
to the finished ceiling/slab surface;
(64) “Internal Wall” means all partition walls in the interior of a building excluding walls which
abut exterior or interior open spaces; internal walls When made of bricks shall be a
minimum of 115 mm brickwork in suitable mortar; other non load bearing partitions shall be
of suitable thickness;
(65) “Loft” means an intermediate floor in between two main floors but not more than 1.5 meters
in height which may be adopted or constructed for storage purpose;
(66) “Masonry” means the form of construction composed of brick, stone, tile, concrete blocks,
gypsum or other similar building material units or combination of these material units laid
up, bonded together and set in mortar;
(67) “Mezzanine Floor” means an intermediate floor between two floor levels above ground
floor and at least one side of it should form an integral part of space/floor below;
(68) “Mumti” means a structure with a covering roof over a staircase and its landing built to
enclose only the stairs for the purpose of providing protection from weather and not meant
for human habitation;
(69) “Materials Alteration” means a change of use in building materials in any existing
building;
(70) “Marginal Distance / Side and Rear Marginal Open Space” means a minimum distance
required to be left open to sky between the boundary of the building plot and the building
line on respective sides.
(71) "Non Combustible” means a material which does not burn or add heat to a fire
when tested for combustibility in accordance with good practice;
(72) “Occupancy” means the function or use of the building;
(73) "Public Building" means a building used or intended to be used either ordinarily or
occasionally, as a church, temple, mosque or any other place of public worship,
dharamshala, college/school, hostel, theatre, cinema, public concert room, lecture room,
library, orphanage, or rescue home or any other place of public assembly ;
(74) “Parapet” means a low wall built along the edge of a roof or a floor not more than 0.90
meters height;
(75) "Parking Space" means an area enclosed or unenclosed sufficient in size to park vehicle
together with a drive-way connecting the parking space with a street or alley and provided
for ingress and egress of the vehicles;
(76) "Partition” means an interior non-load bearing wall, one storey or part storey in height;
(77) “Pavilion” means a flexible architectural open space that invites people to come in and
spend time in it. It could be temporary or permanent and might even change its form and
function. A pavilion might be used as a shelter, seating, meeting point, café, theatre, of for
lectures, event, exhibitions, sports, play, relaxation, and work etc.,
(78) “Pillar” means a wood, stone, brick, RCC or a metal pillar and includes all columns or
upright post or support, stanchions (steel structures) and an assemblage of columns of
stanchions properly riveted or welded or bolted together;
(79) "Plinth" means the portion of a structure between the surface of the surrounding ground and
surface of the floor, immediately above the ground;
(80) “Porch or Portico” means covered surface supported on pillars or otherwise for the purpose of
pedestrian or vehicular approach to a building;
(81) “Public Garage” means a building or portion thereof designed other than a private garage,
operated for gains, designed or used for repairing, servicing, hiring, selling or storing motor
driven or other vehicles;
(82) “Residential building” means a building used or constructed or adapted to be used wholly
for human habitation;
(83) “Residential cum Commercial Building” means a building where part of the building is used
or constructed or intended to be used for human habitation with remaining part used or
constructed or intended to be used for commercial purpose;
(84) “Repairs” means and includes the following activities, which do not otherwise violate any
provisions regarding general building requirements, structural stability and fire safety
requirements of these Bye-laws;
a) Erection, Re-erection, Addition to, or Alternation of
i. a internal partition wall which does not involve sub-division of property, or.
ii. a parapet wall or a cornice or chhajja within the boundaries of the permissible
setback & ground coverage area of the site. Provide that the total height of the
parapet wall shall not be more than 1.5 meter and width of the cornice or chajja
shall not be more than 75cm.
b) plastering and patch repairs;
c) white washing or painting;
d) re-flooring of the surface of an existing floor;
e) minor repairs and recasting of an existing damaged roof without changing the character
and dimension of such roof;
f) erection of a false ceiling in any floor for air-conditioning, lighting or decorative
purposes;
g) plastering and patch work
h) providing or closing an internal door or window or a ventilation not opening directly
opposite a door or a window of another building
i) replacing of fallen bricks or stones;
j) Repairing or renewing existing plumbing, sanitary and other utility services
k) Repairing of boundary wall
l) Installation of air conditioner/ water tank /solar plants / solar water heater… etc.,
m) Construction or reconstruction of sunshades not more than 0.75 meters in width
within one’s own land and not overhanging on public street;
n) Construction or reconstruction of a parapet wall not exceeding .90 meter in height
and pardah walls up-to a maximum height of 1.50 meters on any floor or floors;
(85) “Storey” means the portion of a building included between the surface of any floor and the
surface of the floor next above it, or if there be no floor above it, then the space between
any floor and the ceiling next above it;
(86) “Street” includes any way, road, lane, square, court, alley or passage in a cantonment,
whether a thorough fare or not and whether built upon or not, over which the public have a
right of way and also the road-way or foot-way over any bridge or cause way;
(87) "Set Back Line" means a line usually parallel with the centre line of the road or street and
laid down in each case by the Board beyond which nothing can be constructed towards the
road or street;
(88) “Site or Plot” means a parcel/piece of land enclosed by definite boundaries;
(89) “Smoke Pipe” means a flue approximately horizontal, made of metal or other material in
which smoke or the products of combustion are conducted from a furnace to a chimney;
(90) “Store or Shop” shall mean any store or shop in which it is not intended that any person
shall reside;
(91) “Structural Engineer” means a person who is a graduate of civil engineering from a
recognized India or foreign university or is a member of Civil Engineering Division of the
Institution of Engineers (India) with experience in structural engineering practice which
includes structural design and field work;
(92) “Sanctioned Plan” means the set of plans and specification submitted under section 235
of the Cantonments Act, 2006 under the Bye – Laws and regulations in connection with a
building and duly sanctioned by the Authority under section 234/237/238 of the
Cantonments Act, 2006;
(93) “Sun Shade” means a sloping or horizontal structural overhang usually provided over
openings on an external wall to provide protection from sun and rain;
(94) "Swimming Pool" means a wading pool, paddling pool or simply a pool in container filled
with water intended for swimming or water based recreation The pool can be built either
above or in the ground and from materials such as concrete, metal plastic or fiber glass;
(95) “To Abut" means to be positioned juxtaposed to a road, lane, open space, building etc.;
(96) “To erect or re-erect” means;
(a) To erect a new building on any site whether previously built upon or not;
(b) To re-erect any building of which portion have been pull down, brunt or destroyed,
damaged by storm, rains, fire, earthquake or any other natural calamity to the some
extent, similarly specifications existing prior to damage;
(c) Conversion from one occupancy to another;
(d) To carry out alterations and;
(e) To add to a storey/ storeys;
(97) “Total floor area” means the area of all floors of building including habitable, basement
and mezzanine floor;
(98) “Travel distance” Means the distance an occupant has to travel to reach the exit;
(99) “Verandah” A covered area with at least one side open to the outside;
(100) "Water Closet" means a privy with arrangements for flushing the pan with water but does
not include bathroom;
(101) "Window" means an opening to the outside other than a door which provides all or part of
the required natural light, ventilation or both to an interior space and not used as a means
of ingress/egress;
(102) "Workshop" means a room or a group of rooms or buildings in which goods are
manufactured or repaired;
(103) “Warehouse” means a building, the whole or a substantial part of which is used or
intended to be used for the storage of goods whether for keeping or for sale or for any
similar purpose, but does not include a storeroom attached to and use for proper
functioning of a shop;
(104) “Washing Platform” means an authorized platform for washing and also for servicing of
scooters/cars etc.;
(105) Words and expressions used and not define in these Bye laws but defined in the Act shall
have the same meanings as assigned to them in the Act.
CHAPTER II
PROCEDURE FOR SANCTION OF BUILDING PLANS AND RELATED DOCUMENTATION
3. BUILDING SANCTION REQUIRED :-No person shall carry out any erection, re-erection,
addition or alteration to any building or cause the same to be done without obtaining a
sanction for such work from the Competent Authority.
4. PROCEDURE FOR OBTAINING BUILDING SANCTION :- (1) Anapplicant who intends to
erect or re-erect a building or to make addition or alteration in any building shall register
himself/herself in the e-Chhawani portal and apply through online, duly enclosing all the
requisite documents and plans, in e-Chhawani portal through Cantonment Board registered
architect / architects:
Provided that due to any reasons, if it is not feasible for an applicant to apply in the e-
Chhawani portal the Board may prescribe a procedure for submission of application:
Provided further that the Central Government or Director General may issue guidelines
from time to time to the Board regarding the manner of submitting applications for the said
purpose.
The drawings shall be printed on white paper, using black lines on one side of the white paper.
Normally three sets of documents shall be submitted with the notice out of which one set shall be
on plasticized paper.
(2) Only persons who have legally valid occupancy rights on leased or old grant or private land,
are eligible for applying for sanctions of building plan. In cases wherein breach of lease
conditions on leased land or breach of old grant terms in old grant land involved, the Boards shall
have the right to refuse or reject application for erections, re-erection or addition/ alteration till the
breach of lease or old grant condition is regularized or condoned.
(3) On scrutiny of the documents and plans submitted, the applicant receives the development
charges communication (or the charges levied by the Board by whatever name these are known)
for payment to the Barrackpore Cantonment Board.
(4) On deposition of development charges(or the charges levied by the Board by whatever name
these are known), the sanction is conveyed within the prescribed timelines.
(5) Recommended Notation for Colouring of Plans:(1)The site and building plans shall be
coloured as specified in the table given below. Where items of work are not identified, the
colouring notation used shall be indexed:
Table 1.0: Colouring Notations
+-----+-------------------------------+----------------+----------------+
| S. | Item | Site plan | Building plan |
| No. | | | |
+=====+===============================+================+================+
| 1 | Plot lines | Thick green | Thick green |
+-----+-------------------------------+----------------+----------------+
| 2 | Existing street | Green | Not applicable |
+-----+-------------------------------+----------------+----------------+
| 3 | Permissible building line | Thick dotted green| Not applicable |
+-----+-------------------------------+----------------+----------------+
| 4 | Existing work (outline) | Green | Green |
+-----+-------------------------------+----------------+----------------+
| 5 | Work proposed to be demolished| Yellow hatch | Yellow hatch |
+-----+-------------------------------+----------------+----------------+
| 6 | Proposed addition/alteration | Red | Red |
+-----+-------------------------------+----------------+----------------+
| 7 | Proposed new work | Not to be colored| Not to be colored|
+-----+-------------------------------+----------------+----------------+
| 8 | Drainage | Red dotted | Red dotted |
+-----+-------------------------------+----------------+----------------+
| 9 | Water supply | Thin dotted green| Thin dotted green|
+-----+-------------------------------+----------------+----------------+
Dimensions: All dimensions shall be indicated in metric units. All linear dimensions shall
be in mm.
The size of drawing sheets shall only by as specified below:
Table 2.0: Size of Drawing Sheets
+-----+---------------+-----------------------+
| S. No.| Drawing type | Trimmed size (in mm) |
+=====+===============+=======================+
| 1 | A-0 | 841X1189 |
+-----+---------------+-----------------------+
| 2 | A-1 | 594X841 |
+-----+---------------+-----------------------+
| 3 | A-2 | 420X594 |
+-----+---------------+-----------------------+
| 4 | A-3 | 297X420 |
+-----+---------------+-----------------------+
| 5 | A-4 | 210X297 |
+-----+---------------+-----------------------+
(2) Key Plan (Location Plan):- A key plan drawn to a scale of not less than 1:10000 shall be
submitted along with the application for a building sanction showing the boundary locations of the
site with respect of neighborhood landmarks.
(3) Site Plan:-The site plan sent with the application for sanction shall be drawn to a scale of
1:500 and shall show:
i. The boundaries of the site;
ii. The direction of the North point relative to the plan of the buildings;
iii. All existing building or structures on, over or under the site or projecting beyond it;
iv. All surrounding buildings in outline within a distance of 12 metres from the
boundaries of the site;
v. The name of the street in which the building is proposed to be situated, if any.
vi. The position of access from the street to the building and the width of the street
(if any) in front and of the street (if any) at the side or rear of the building.
vii. Any existing physical feature, such as wells, drains, trees etc;
viii. Parking plans indicating the parking spaces for all buildings.
ix. Scheme of tree planting proposed.
x. The Rainwater harvesting scheme complete with all details of drainage scheme and
rainwater harvesting pits.
xi. Holding number or plot no. of the property on which the building is intended
tobe erected is to be indicated on the drawing.
xii. Such other particulars as may be prescribed from time to time by the
Competent Authority;
(6) Architectural drawings of the building –(1)All drawings of the building viz. plans, elevations
and sections accompanying the notice shall be drawn to a scale of 1:50 for plots measuring up to
250 square metres; for plots over 250 square metres they shall be drawn at 1:100.
The drawings shall include:-
i. Floor plans of all floors together with the covered area on each floor.
ii. Sizes of rooms, thickness of walls, size of columns and the position and width ofstair
cases, ramps and other exit ways, lift wells, lift machine room and lift pit details;
iii. Exact location of essential services, e.g. water closet, urinals, sink, baths, bath-tubs,
showers and the like;
iv. Sections showing clearly, the sizes of footings, thickness of basement walls and all
intermediate floor and roof slabs, wall thicknesses, sizes and spacing of framing
members, ceiling heights and parapet-heights along with details of their materials. The
section should indicate the drainage and the slope of the roof and at least one section
should be taken through the staircase and toilet respectively;
v. All street/side elevations;
vi. Dimensions of the projects like chajjas, cupboards, balconies and canopies;
vii. Terrace plan indicating the drainage and slope of roof; details indicating the drainage
system and collection of rain water for ground water recharge;
viii. Indication of the 'North point’;
ix. Plans and sections of water supply and sewerage disposal system, if any;
x. Set back line;
xi. Labelling of individual spaces in the plans and sections to show the use or occupancy
of all parts of the buildings.
xii. Landscape plan including details of parking spaces provided and scheme of rain
harvesting scheme;
xiii. Give indication of sizes of all doors, windows, ventilators and other openings including
their sill and lintel levels in a proper schedule form; and
xiv. Such other particulars as may be required to explain the proposal clearly and as pre
scribed by the Authority.
(2) Service Drawings:-Plan, elevations and sections of water supply, sewerage disposal
system and details of building services, where required by the Competent Authority shall be
made available on a scale of 1:100.
(3) Structural Drawings and Design:-Detailed documentation of structural design in keeping
with Bye-law No. 38 including structure plans, framing plans, structural details including
reinforcement and calculations duly verified by Competent Structural Engineer.
(4) The requirement at 3 above shall be applicable for plots of 500 square metres and above
only. For plots of less than 500 square metres submission of Form C shall be considered
sufficient.
5. BUILDING APPLICATION FEES AND APPLICABLE CHARGES:-(1) Building Application Fees -
The Building plan application shall be deemed valid only if the applicant has paid the requisite
building application fee as determined by theBoard.
(2) Development Charges -The development charges, labourcess and other fees, as
determined by the Board, are to be paid by the applicant through online before issuance of
the sanction of the building application by the competent authority.
(3) Incentive in development charges if Rooftop Solar Installation and Rain Water Harvesting is
proposed and implemented - For construction of residential or commercial or any building
less than 50 sqmeter, if the applicant opts for Rooftop Solar Installation and/or Rain Water
Harvesting, he/she shall be eligible for refunding of development charges after the
completion of said Rooftop solar installation and/or Rain Water Harvesting facility and
submission of photographs to this effect. The quantum of incentive for different categories
of buildings shall be decided by the Board by resolution. Rain water Harvesting is
mandatory for the large sized plots (Please refer Bye-Laws No.45).
(4) Stacking of building material on street or other public land shall not take place without the
permission of the Chief Executive Officer on a case to case basis and on payment of
charges as fixed by the Chief Executive Officer in terms of section 257 of the Act.
6. DOCUMENTS AT THE TIME OF APPLICATION :-The following documents shall besubmitted
through online on e-Chhawani portal at the time of submitting application for building sanction:
i. Proof of ownership/ HOR/Lessee / Successor / legal rights document;
ii. Affidavit and Indemnity Bond as specified by the competent authority;
iii. Proof of identity;
iv. Any other documents as approved by the competent authority (Cantonment specific
documents)
v. Along with all drawings mentioned herein above, the following documents shall be
submitted at the time of application for building sanction:-
a. Certificate Regarding Safety from Natural Hazard and Structural Safety as per Form A, set
forth in the Appendix, signed by Structural Engineer and the Applicant.
b. Form B for Supervision signed by Architect / Civil Engineer / Structural Engineer.
c. Indemnity Bond as per Form C, set forth in the Appendix, in case of proposal for the
construction of a basement;
d. Form D as per Notice for Commencement of Work;
e. From E, Notice on Completion of Buildingsigned byArchitect / Civil Engineer / Structural
Engineer;
f. Certificate for Completion-Cum-Occupancy of Building as per Form F.
g. Clearance Certificate for Tax Arrears issued by the Tax / Revenue Department of the
Board.
h. In case of requirement of statutory clearance for certain occupancies requiring clearance
from the authorities like, Civil Aviation, Railways, Directorate of Industries, State Govt.,
Pollution Control Board, Directorate of Boiler and smoke nuisance etc., the relevant
clearance from the authority shall also accompany the Building application
7. SANCTION/REFUSAL OF PLANS, VALIDITY PERIOD AND REVALIDATION
PROCEDURE:-(1)In case of old grant land, the proposed building plan shall be in conformity with
the old grant terms and the land policies of Ministry of Defence.
(2) In case of leased land, the proposed building plan shall be in conformity with the lease hold
rights/terms and the land policies of Ministry of Defence.
(3) The Competent Authority shall sanction the plan unless such building would contravene
any of the following, namely:-
(i) That the building or the use of the site for the building or any of the particulars comprised in
the site plan, ground plan, elevation, section or specification contravenes the provisions of
this Act or the Bye-Laws made thereunder;
(ii) That the notice for sanction does not contain the particulars or is not prepared in the
manner required under the provisions of these Bye-Laws;
(iii) That any information or documents required by the Board under these Bye-Laws made has
or have not been duly furnished;
(iv) That the building plan is not in accordance with the bye laws framed by the Board under
section 260 or those framed under clauses (19) and (20) of section 348 of the Act;
(v) That the building would be an encroachment on Government land or land vested in the
Cantonment Board;
(vi) That the site of the building does not abut on a street or projected street and that there is
no access to such building from any such street by a passage or path-way appertaining to
such site; or
(vii) That the erection or re-erection of the building is not in conformity with any general scheme
sanctioned under section 240 of the Act.
(viii) When the land on which it is proposed to erect or re-erect the building is entrusted to the
management of the Board by the Government if the erection or re-erection constitutes a
breach of terms of the entrustment of management or contravenes any of the instructions
issued by the Government regarding the management of the land by the Board;
(ix) When the land on which it is proposed to erect or re-erect the building is not held on a
lease from the Government, if the right to build on such land is in dispute between the
person applying for sanction and the Govt;
(x) That the minimum size of the plot for residential purpose is not less than 50 sqmt, provided
that the existing authorized buildings having a plot size of less than 50 sqm, the said
restriction shall not apply; or
(xi) That it is mandatory to provide Rooftop Solar Installation and Rain Water Harvesting if the
size of the plot exceeds 500sqmt.
(4) The sanction once granted shall be valid for a period as provided in the Act from the date of issue
of sanction.
(5) The Building Sanction can be revalidated beyond the date of the expiry of the original Sanction of
building plans on payment of the required revalidation fees as decided by the Board under
provisions of the Act. Application for such revalidation shall be submitted on plain paper along
with the following documents:-
(a) Original sanctioned plan.
(b) Revalidation fees chargeable based on the decision and guidelines issued by Competent
Authority from time to time.
(c) Documents in support of construction, if any, having been done within valid period of
sanction.
(d) Certificate of supervision from Architect/Engineer/Supervising Engineer and the Applicant
that the construction will be carried out under his supervision according to the plans
sanctioned by the Competent Authority.
8. SCRUTINY OF PLANS:-Once the plans have been scrutinized and objections, if any, have been
communicated through online, the applicant may modify the plan, comply with the objections raised
and resubmit through online, for consideration of the competent authority.
9. REVOCATION OF SANCTIONED BUILDING PLANS AND LIABILITY OF THE APPLICANT TO
CONFORM TO BYE-LAWS:- (1)The Competent Authority may revoke any building sanction issued
under the provisions of these byelaws, whenever there has been any false statement, or any
misrepresentation of material fact, or concealment of facts in the application on which the building
sanction was based, and the whole work executed on the basis of such sanction shall be treated as
unauthorized. Further, any or all executed works in cases of deviation from the sanctioned plan shall be
treated as unauthorized construction and would lead to revocation of accorded sanction.
(2) In the case of revocation of sanction during course of construction under the above Bye- law, no
compensation /damages shall be payable by the Competent Authority.
(3) No such order of revocation shall be passed by the Competent Authority without giving a
reasonable opportunity to the applicant of being heard.
10. NOTICE OF COMMENCEMENT AND COMPLETION OF WORK:-(1)Onissue of building
sanction the applicant shall commence the work for which the building sanction has been issued. The
Applicant shall give notice to the Chief Executive Officer of his intention to start work on the building
site by submitting Form D, set forth in the Appendix.
(2) Oncompletion of work the Applicant shall submit a Notice of Completion of the building as per
Form E, set forth in the Appendix through the Architect/Engineer who has supervised the construction
within a period of thirty days from the date of completion of work.
11. COMPLETION-CUM-OCCUPANCY CERTIFICATE:- The Chief Executive Officer on receipt of
the notice of completion shall inspect the work and issue a certificate of occupancy within the
period stipulated in the Act, as per Form F, set forth in the Appendix, if the building has been
constructed in conformity with sanction issued.
12. COMPOSITION OF UNAUTHORIZED CONSTRUCTION:-(1)The Barrackpore Cantonment
Board may by resolution decide formula to calculate quantum of penalty/fees for regularization of
unauthorized construction.
(2) Such composition of unauthorized construction shall be subject to the provisions of the
Cantonments Act, 2006, the rules subsisting there under and other restrictions mentioned in these
Bye-Laws including but not limited to FSI, Set-backs, and Ground Coverage.
(3) In so for as constructions which are present and existing on the date of notifying of these Byelaws
wherein such constructions are without sanction or in violation of approved plan including deviation, the
applicants may apply to Barrackpore Cantonment Board for Compounding, which at the discretion of
the Barrackpore Cantonment board or GoC-in-Chief, as applicable, may be allowed subject to payment
of compounding fees as determined by Barrackpore Cantonment Board or GoC-in-Chief, as applicable.
This exercise shall be undertaken subject to the Bye-Laws framed hereunder after approval of Central
Government.
CHAPTER III
ZONING
13. ZONING:- (1) The Cantonment should be divided into two broad zones, namely:-
(a) Zone I :-this would include notified civil areas including freehold properties within the limit of
notified civil area. These are generally high density areas.
(b) Zone II :- All other land not included in Zone - I but inclusive of all OGBs and leases situated
outside notified civil area. This will be generally low density zone.
(2) ZONE-I– This Zone comprises all lands as depicted in zonal Plan passed by the Board by
resolution in this regard.
(a) REQUIREMENT OF SITE:– (i) No piece of land shall be used .as a site for the construction
of a building if the Competent Authority considers that the site is insanitary or is not drained
properly or isincapable of being well drained.
(ii) The minimum size of a plot, for the purpose of erection of a residential building, shall not
be less than 50 square meter. Provided that, for those plots of residential units whose area
recorded in the GLR is 50 sq.mt or below shall be exempted from this clause.
(b) PERMISSIBLE FAR :-The permissible FAR, depending on the plot size, shall be as per table
below:
Table 3.0 – Permissible FAR depending on the Plot Size for Zone I
+-----+-----------------------------------+-----------------------------+----------------+
| S.No.| Area of plot in square meters | Maximum ground coverage as %| F A R |
+=====+===================================+=============================+================+
| 1 | Up to 100 | 70 | 125 |
+-----+-----------------------------------+-----------------------------+----------------+
| 2 | Above 100 to 500 | 70 | 125 |
+-----+-----------------------------------+-----------------------------+----------------+
| 3 | Above 500 to 1000 | 70 | 100 |
+-----+-----------------------------------+-----------------------------+----------------+
| 4 | Above 1000 to 1500 | 60 | 100 |
+-----+-----------------------------------+-----------------------------+----------------+
| 5 | Above 1500 to 2000 | 50 | 75 |
+-----+-----------------------------------+-----------------------------+----------------+
| 7 | Above 2000 | 50 | 50 |
+-----+-----------------------------------+-----------------------------+----------------+
The total coverage and FAR permissible in any plot in a category, shall not be less than that
permissible and available to the largest plot in the next lower category.
(i) Mezzanine, if constructed, shall be included in FAR.
(ii) Basement shall not be counted in FAR, if used for purpose permissible as per Bye-law
No.29 Basement area shall not extend beyond the coverage on the ground floor as per
permissible and sanctioned built up area, but may extend to the area below the internal
courtyard and shaft.
(iii) The following shall not be included in covered area and FAR calculation:
(a) A basement under a building used as parking space and for air conditioning plant room,
other building services and storage as defined at Bye laws No. 29.Holdings in Zone –I
which already have a built up area more than 70% shall be exempted from this
clause.
(b) Area under stilts at the ground floor used as parking space.
(c) Electrical cabin or a substation, watchman's booth width of maximum size of 1.5 metre
with minimum width or diameter of 1.2 metres, pump house, garbage shaft, and space
required for location of fire hydrants, electrical fittings and water tank.
(d) Projections as specifically exempted under the byelaws.
(e) Staircase, mumty, chimneys and area under water-tanks of dimensions as permissible
under these Bye-Laws.
(f) The lift machine room. The lift shaft provided shall be included only once for FAR and
ground coverage calculations.
(iv) Rockery, plant nursery, water pool, swimming pool (if uncovered) platform round a tree,
water tank, septic tank, soakage pit, fountain, bench, pavilion with open top and
unenclosed side by walls, ramps, compound wall, gate, slide swing, overhead water tank
on top of buildings;
(v) Existing structure/ building which is already sanctioned on the previously existing
Building Bye-Laws of Barrackpore Cantonment and which exceeds the ground coverage
or FAR mentioned herein this Building Bye-Laws will remain permitted.
(c) TENEMENT DENSITY:-
Table 4.0 – Dwelling unit depending on the Plot Size for Zone I
+-----+-----------------------------------+--------------------------+
| S.No.| Area of plot in square meters | Dwelling units per plot |
+=====+===================================+==========================+
| 1 | Up to 100 | Not more than 02 |
+-----+-----------------------------------+--------------------------+
| 2 | Above 100 to 500 | @not more than 1 unit for 100 sq meters|
+-----+-----------------------------------+--------------------------+
| 3 | Above 500 to 1000 | -do |
+-----+-----------------------------------+--------------------------+
| 4 | Above 1000 to 1500 | -do |
+-----+-----------------------------------+--------------------------+
| 5 | Above 1500 to 2000 | -do |
+-----+-----------------------------------+--------------------------+
| 6 | Above 2000 | -do- |
+-----+-----------------------------------+--------------------------+
*No independent dwelling unit of less than 50 sqm can be constructed, provided that for existing
authorized buildings having a plot size of less than 50 sqmt, the said restriction shall not apply.
(d) BUILDING HEIGHT:-Maximum building height in all plot categories shall be 15
metres.(Note: These recommendations are as per the West Bengal Municipal (Building) Rules,
2007.)
The following appurtenant structures shall not be included in the height:
(a) Parapet wall;
(b) Roof water tanks and their supports;
(c) Ventilation and air-conditioning structures;
(d) Lift rooms and similar service equipment;
(e) Mumty of staircase;
(f) Chimneys;
(g) Architectural features not exceeding 1 metre in height;
(h) The Basement should be used only for parking, storage and housing services only. In
no case be used for residential or commercial purpose.
(e) MAXIMUM NUMBER OF STOREY PERMISSIBLE:-The maximum number of storey
permissible in all categories plot shall be G+2, apart from Stilt and Basement.
(3) ZONE – II- This Zone comprises all lands as depicted in zonal Plan passed by the Board
by resolution in this regard.
(a) REQUIREMENT OF SITES :-No piece of land shall be used .as a site for the
construction of a building if the Competent Authority considers that the site is insanitary or is
not drained properly or isincapable of being well drained.
(b) PERMISSIBLE FAR
Table 5.0
Permissible FAR depending on the Maximum ground Coverage for Zone II
+-----+-----------------------------------+----------------+
| S.No | Maximum ground coverage as % | F A R |
+=====+===================================+================+
| 1 | 50 | 50 |
+-----+-----------------------------------+----------------+
(c) TENEMENT DENSITY
Table 6.0
Dwelling units depending on the Maximum ground Coverage for Zone II
+-----+-----------------------------------+--------------------------+
| S.No | Maximum ground coverage as % | Dwelling units per plot |
+=====+===================================+==========================+
| 1 | 50 | @not more than 1 unit for 100 sqm|
+-----+-----------------------------------+--------------------------+
(d) BUILDING HEIGHT:-Maximum building height in all plot categories shall be 15 meters.
(Note: These recommendations are as per the West Bengal Municipal (Building) Rules, 2007.)
The following appurtenant structures shall not be included in the height:
(a) Parapet wall;
(b) Roof water tanks and their supports;
(c) Ventilation and air-conditioning structures;
(d) Lift rooms and similar service equipment;
(e) Mumty of staircase;
(f) Chimneys;
(g) Architectural features not exceeding 1 metre in height
(e) MAXIMUM NUMBER OF STOREY PERMISSIBLE:-The maximum number of storey
permissible in all categories plot shall be G+2, apart from Stilt and Basement.
CHAPTER IV
SPECIFICITIES WITH RESPECT TO BUILDING CONSTRUCTION
14. OPEN SPACES/SET BACKS:-The building envelop shall be governed by the following
minimum clear open space and setback:-
(1) FRONT SETBACK
(a) Every building abutting a street / footpath shall have a front setback from the front
property line to the front building envelop or building front main wall.
(b) External staircases in the front elevation of the building shall not be considered in
front setback calculation.
(c) Sunshades and balconies shall be within the front property line or shall be
constructed within the front set back or within the boundary wall of the plot.
(d) In the case of school buildings, the front boundary wall shall be recessed by 6 meters
to accommodate visitor parking within setback area.
(2) SIDE AND REAR BACK
(a) Every building shall have a minimum clear side and rear setback as prescribed in
these Bye-Laws. No use is permitted in this open space except steps, staircase, rain
water harvesting pits, septic tank and soak pit or in case this space is less than 6 m &
more than 9 m wherein parking of vehicle is allowed.
(b) External staircases in the sides and rear of the building shall not be considered in
setback calculation and shall be as per the following table and shall be constructed
within the boundary wall of the plot.
(c) Sunshades and balconies shall be within the boundary wall of the plot.
The provisions for open spaces at the front side and rear of the building shall be as per
Table 7.0
Table 7.0: Minimum Building Setback
+-----+-----------------------------------+-------+-------+---------+---------+
| S. No.| Plot size | Minimum setback (in metres) |
| | (in square metres) | Front | Rear | Side (1)| Side (2)|
+=====+===================================+=======+=======+=========+=========+
| 1 | Up to 100 | 0.90 | 0.90 | 0.90 | 0.90 |
+-----+-----------------------------------+-------+-------+---------+---------+
| 2 | Above 100 up to 200 | 3 | 0.90 | 0.90 | 0.90 |
+-----+-----------------------------------+-------+-------+---------+---------+
| 3 | Above 200 up to 500 | 3 | 3 | 3 | 0 |
+-----+-----------------------------------+-------+-------+---------+---------+
| 4 | Above 500 up to 2000 | 6 | 3 | 3 | 3 |
+-----+-----------------------------------+-------+-------+---------+---------+
| 5 | Above 2000 up to 10000 | 9 | 6 | 6 | 6 |
+-----+-----------------------------------+-----------------------------------+
| 6 | Above 10000 | 15 | 9 | 9 | 9 |
+-----+-----------------------------------+-------+-------+---------+---------+
Note: For Corner Plot at the corner of two streets : -
(a) In case both the adjoining roads are below 3.5m in width and area of land is within 200
sq.m., the such corner of plot shall be splayed by 1.20mx1.20m.
(b) In case both the adjoining roads are 3.5m or above, in such corner of plot shall be splayed
by 2.50mx2.50m.
(3) INTERIOR OPEN SPACE – VENTILATION SHAFT- For ventilating the spaces for bathroom
and water closet, if not opening on to front, side, rear or interior (courtyard) open spaces, these
shall open on the ventilation shaft, the size of which shall not be below values indicated in
Table 8.0.
Table 8.0: Minimum Size of Ventilation Shaft
+-----+--------------------------+------------------------------+--------------------------+
| S. | Building height inmetres.| Size of shaft in square metres.| Minimum one dimension in metres.|
| No. | | | |
+=====+==========================+==============================+==========================+
| 1 | Up to 10 | 1.2 | 0.9 |
+-----+--------------------------+------------------------------+--------------------------+
| 2 | 12 | 2.8 | 1.2 |
+-----+--------------------------+------------------------------+--------------------------+
| 3 | Above 12 | 4.0 | 1.5 |
+-----+--------------------------+------------------------------+--------------------------+
(4) INTERIOR OPEN SPACES–COURTYARD:- The whole of every room excepting bath,
water closet and store room and not abutting on either the front, rear or sides open spaces shall
abut on an interior open spaces (courtyard), whose minimum width shall be 3 meters. Further the
courtyard shall have an area at all levels of courtyard of not less than the square of the 1/5th the
height of the wall abutting the courtyard; Provided that when any room excluding a bathroom or
water closet is dependent for its light and ventilation on an inner courtyard, the dimension shall
be such as is required for each wing of the building.
15. LAND SITUATED IN ARCHAEOLOGICAL ZONE:-For plots falling in Archaeological Zone,
NOC from Department of Archaeological Survey of India shall be submitted.
16. RESTRICTIONS TO HEIGHT IN THE VICINITY OF AERODROMES:-For building in the vicinity of
aerodromes, the maximum height of such building shall be decided in consultation with the Civil
Aviation Authorities and in such cases, applicant shall obtain ‘no-objection’ from the Civil Aviation
Authorities.
17. PARKING SPACE:-(1)Parking provision for different types of buildings shall be as per norms laid
out in Table 9.0. The standards given are in Equivalent Car Space (ECS) as laid out by the
National Building Code of India and it includes parking of all vehicles like cars, scooter, cycles and
light and heavy commercial vehicle.
Table 9.0: Parking Standards in ECS
+-----+-------------------------------------------------------+-----------------------------------+
| S. | User/Use Premises | Per 100 square metre of floor area|
| No. | | |
+=====+=======================================================+===================================+
| 1 | Residential: In plots of 250 square metres and above | 1.00 ECS |
+-----+-------------------------------------------------------+-----------------------------------+
| 2 | Residential Group housing | 2.00 ECS |
+-----+-------------------------------------------------------+-----------------------------------+
| 3 | Offices and Courts | 1.80 ECS |
+-----+-------------------------------------------------------+-----------------------------------+
| 4 | Sub-city commercial area, Hotel & service apartment | 3.00 ECS |
+-----+-------------------------------------------------------+-----------------------------------+
| 5 | Local and convenience shopping centre | 2.00 ECS |
+-----+-------------------------------------------------------+-----------------------------------+
| 6 | Primary, Middle and Secondary School | 1.33 ECS |
+-----+-------------------------------------------------------+-----------------------------------+
| 7 | Senior Secondary School | 2.00 ECS |
+-----+-------------------------------------------------------+-----------------------------------+
| 8 | Hospital, Nursing Home, Maternity Home, Diagnostic | 2.00 ECS |
| | Center & Medical College | |
+-----+-------------------------------------------------------+-----------------------------------+
| 9 | College, Vocational Training Institute & Professional | 1.33 ECS |
| | College | |
+-----+-------------------------------------------------------+-----------------------------------+
| 10 | Post Office, telephone exchange and fire station | 1.33 ECS |
+-----+-------------------------------------------------------+-----------------------------------+
| 11 | Old age home, orphanage, working persons | 1.80 ECS |
+-----+-------------------------------------------------------+-----------------------------------+
| | hostels | |
+-----+-------------------------------------------------------+-----------------------------------+
| 12 | Multipurpose community hall and Banquet hall | 3.00 ECS |
+-----+-------------------------------------------------------+-----------------------------------+
| 13 | Club, Auditorium and Religious building | 2.00 ECS |
+-----+-------------------------------------------------------+-----------------------------------+
| 14 | Exhibition hall and conference facility | 2.00 ECS |
+-----+-------------------------------------------------------+-----------------------------------+
| | * 2 ECS shall be provided per plot in residential plots less than 250 square metres.|
+-----+---------------------------------------------------------------------------------------+
(2) These parking norms shall be applicable for all new applications for building plan sanctions.
(3) This parking can be provided in any manner i.e. covered, under stilts or open. In providing
the parking, care has to be taken that 50% of the open space in plots which are above
1000 square metres is leftfor hard and soft landscapingand not accounted in parking
calculations.
(4) For Assembly, Institutional, Industrial, Health facilities, Commercial Centers parking floor
may provide on upper floors provided that the plot area is not less than 4000 sq.meter, and
shall be in accordance with the latest revision of the National Building Code of India.
(5) The area of each ECS shall be as follows:
i Basement: 32 square meter.
ii Stilts: 28 square metre.
iii Open: 23 square metre.
iv Multi-level with ramps: 30 square metre.
v Automated multilevel with lifts: 16 square metre.
18. PLINTH OF MAIN BUILDING:- The plinth of any part of a building shall be so located with respect
to surrounding ground level that adequate drainage of the site is assured but not at a height of less
than 0.45 metres.
19. PLINTH OF INTERIOR COURTYARDS:-Every interior courtyard shall be raised at least 0.15
metres above the surrounding ground level and shall be satisfactorily drained.
20. SIZE OF HABITABLE ROOMS:–
(1) No habitable room shall have an area of less than 9.5 square metres.
(2) In case of hostels of educational institutionsthe minimum size of a habitable room for the residency
of a single person shall be 7.5 square metres.
(3) The minimum width of a habitable room shall be 2.4 metres.
(4) In a two rooms tenement one shall be not less than 9.5 square metres and other 7.5 square
metres.
21. HEIGHT OF HABITABLE ROOM:–
(1) The height of all rooms for human habitation, Assembly, institutional, Educational, Industrial,
Hazardous and Storage Occupanciesshall not be less than 2.75 metres and not more than 5.0
metres measured from the surface of the floor to the lowest point of the ceiling i.e. bottom of slab.
(2) In case of centrally air-conditioned building, the height of the habitable room shall not be less than
2.4 meters measured from the surface of the slab or to the underside of the false ceiling.
(3) The minimum clear head room under beam shall be 2.4 metres. In the case of pitched roof, the
average height of rooms shall not be less than 2.75 metres and the minimum height under
theeaves level shall not be less than 2.1 metres.
22. BATHROOMS AND WATER CLOSETS (COMBINED):-
(1) Size: The minimum size of a bathroom shall be 1.8 square metres, and the minimum width of a side
shall be 1.2 metres. The minimum size of a water closet shall be 1.1 square metres and the
minimum width of a side shall be 0.9 metres. The minimum size of a combined bathroom and water
closet shall be 2.8 square metres and the minimum width of a side shall be 1.2 metres.
(2) Height: The height of a bathroom or water closet measured from the surface of the floor to the
lowest point in the ceiling i.e. bottom of slab shall not be less than 2.2 metres and not more than 5.0
metres.
(3) Other Requirements: A bathroom or water closet shall:-
(a) be so situated that at least one of its walls shall open to external air and shall have a minimum
opening in the form of a ventilator or window of 1.0 square metres;
(b) not be directly under or above any room other than another water closet, bathroom, washing area
or terrace unless it has a water tight floor;
(c) have the platform and/or seat made of water tight non-absorbent material;
(d) be enclosed by walls/ partitions whose surface is finished with a smooth impervious material to a
minimum height of 1.5 metre above the floor level;
(e) be provided with an impervious floor finish, with floor surface sloping towards the drain with a
suitable grade and not towards any other habitable room;
(4) No room containing water closets shall be used for any purpose except as a lavatory and no such
room shall open directly into a kitchen or cooking space by a door, window or other opening. Every
room containing water closets shall have a door completely closing the entrance to it.
23. KITCHEN:- (1) Size: The minimum area of the kitchen shall be 4.5 square metres and the minimum
width of a side shall be 1.5 metres. The minimum area of the kitchen which is also intended to be
used as dining room shall be 9.5 square metres and the minimum width of a side shall be 2.4 metres.
(2) Height: The height of a kitchen measured from the surface of the floor to the lowest point in the
ceiling i.e. bottom of slab shall not be less than 2.75 metre and not more than 5.0 metre, except for the
(c) a window the size of which shall be subject to Byelaw No. 31(4) opening directly to an interior or
exterior open space, but not into a shaft;
(d) unless separately provided for in a pantry, means for the washing up of kitchen utensils which shall
lead directly or through a sink to a grated and trapped connection to the waste pipe;
(e) be enclosed by walls/ partitions whose surface is finished with a smooth impervious material to a
minimum height of 1.5 metre above the floor level;
(f) be provided with an impervious floor finish, with floor surface sloping towards the drain with a suitable
grade and not towards any other habitable room;
(g) fly-proof gauze covering for all doors and windows except where a cooking place is provided in a
verandah of single living room tenement;
24. PANTRIES: -Pantries shall have:-
(1) a floor area of not less than 3 square metres and a minimum width of a side shall be 1.4 metres;
(2) a sink for cleansing of kitchen's utensils which shall drain through a grated and trapped
connection to the waste pipe;
(3) been enclosed by walls/ partitions whose surface is finished with a smooth impervious material
to a minimum height of 2.0 metre above the floor level.
(4) been provided with an impervious floor finish, with floor surface sloping towards the drain with a
suitable grade and not towards any other habitable room.
25. LOFT:- (1) The maximum height of a loft shall be 1.5 metres and the loft may be provided over
corridors and passageways only.
(2) The clear head room under the loft shall not be less than 2.2 metres,
(3) Loft when provided in a commercial building and industrial building shall be located 2 metres away
from the entrance.
26. MEZZANINE FLOOR:- (1) Size: Mezzanines shall not be sanctioned in residential buildings. When
provided in commercial and factory buildings the aggregate area of the mezzanine floor shall not
exceed 33-1/ 3 percent of the built up area of that floor.
(2) Height: The minimum height of a mezzanine floor shall be 2.2 metres. The head room under
mezzanine floor shall not be less than 2.2 metres.
(3) Other Requirements: A mezzanine floor may be sanctioned over a room or a compartment
provided that:
(a) Mezzanine area shall be counted towards the FAR.
(b) In case the size of mezzanine floor is 9.5 square metres or more, it should conform to the
standard of living room insofar as lighting and ventilation is concerned.
(c) It is so constructed as not to interfere under any circumstances with the ventilation of the space
over and under it;
(d) Such mezzanine floor or any part of it shall not be used as a Kitchen.
(e) In no case shall a mezzanine floor be closed so as to make it liable to be converted into
unventilated compartments.
27. GARAGE:– (1) Individual Private garage: The size of a private garage in the residential building
shall be not less than 2.5 metres x 5 metres. The garage if located in the side, open space shall
not be constructed within 1.5 metres from the main building.
(2) Commercial Public Garage: The size of a pubic garage shall be calculated based on the
number of vehicles to be parked and the minimum parking spaces for each vehicle as specified in
Bye law 17(4).
(3) Height: The maximum head room in a garage and parking area shall be 4.0metres.
(4) The plinth of a garage located at ground level shall not be less than 0.15 metres above the
surrounding ground level.
(5) The garage shall be set back behind the building line for the street/road on to which plot abuts, and
shall not be so located to affect the access ways to the building.
(6) Corner site: When the site fronts on two streets, the frontage would be as on the street having the
larger width. In cases where the two streets are of the same width, then the larger depth of the site will
decide the frontage and open spaces. In such cases the location of a garage if provided within the open
spaces shall be located diagonally opposite the point of intersections.
28. ROOF:- (1) The roof of a building shall be so constructed or formed as to ensure effectual
drainage of the rainwater there from by means of sufficient rain water pipes of adequate size,
whenever required so arranged, joined and fixed as to ensure that the rain water is carried away
from the building without causing damage in any part of the walls or foundation of the said building
or those of an adjacent building.
(2) Rainwater from roofs and open areas on the plot shall be collected by suitable means to
recharge pits and other devices. In this context reference may be made to Part 9 “Plumbing
Services Section 1: Water Supply, Drainage and Sanitation of the National Building Code of India
as amendedfrom time to time.
(3) Rainwater pipes shall be affixed to the outside of the walls of the building or in recesses or
chases out or formed in such walls or in such other manner as may be approved by the Competent
Authority.
(4) Terrace of buildings shall not be subdivided and it shall have a common access.
29. BASEMENTS:– (1) Basements may be erected within the prescribed setbacks andprescribed
building lines and subject to maximum coverage on ground floor.
(2) Basements shall not be used for residential purposes and used only for:
(a) storage of household or other goods except inflammable materials;
(b) strong room, bank cellars etc.;
(c) air-conditioning equipment and other machines used for services and
utilities of the building;
(d) parking on obtaining a no objection certificate from the Competent
Authority.
(3) Basements shall have the following requirements, namely;-
(a) Every basement shall be in every part at least 2.4 metres in height from the floor to the
underside of the slab or ceiling.
(b) Adequate ventilation shall be provided for the basement. The standards of ventilation shall be
the same as required by the particular occupancy according to byelaws. Any deficiency may be
met by providing adequate mechanical ventilation in the form of blowers or exhaust fans at the
rate of one exhaust fan for 50 sq.m floor area.
(c) The minimum height of the ceiling of any basement shall be 0.9 metres and the maximum 1.2
metres above the average surrounding ground level.
(d) Adequate arrangement shall be made so that surface drainage or drainage water does not enter
the basement.
(e) The basement shall not be partitioned. In cases where partitions are allowed by Competent
Authority and the ventilation standards as laid-down in (b) above are met, the partitioning of
basement may be sanctioned, subject to the condition that no space shall be less than 50
square metres.
(f) Adequate protection against the fire shall be provided. The roofs separating basement and floors
above shall be constructed of a material like R.C.C. or of such material which will provide
resistance against fire for at least two hours.
(g) Where a basement is sanctioned in apartment houses (residential flats) and hotels, the
applicant/ occupier shall display the basement plan at the entrance. Thimbles shall be provided
in the roof of the basement and their positions clearly indicated on the plan. One fire extinguisher
for every 30 square metres of basement area or part thereof shall be provided.
(h) The walls and floors of the basement shall be water-tight and so designed that the effect of
surrounding soil moisture, if any, are taken into consideration and adequate damp proofing
treatment is given.
(i) In the event of atmospheric water percolating into basement necessary arrangement to drain out
the same shall be provided.
(j) Kitchen, bath and water closet shall not be sanctioned in the basement unless the sewer levels
allow the same and there is no chance of backflow and flooding of sewage. If sanctioned they
shall be placed against the external walls of the basement (which shall also be the external walls
of the building) and shall be adequately lighted and ventilated. The area of such kitchens, baths
and water closets shall be counted in the FAR.
(k) A kitchen when sanctioned in the basement shall be equipped with electric ovens, stoves, gas
only. No coke or fire wood will be used.
(l) The access to the basement shall be from separate from the main and alternate staircase
providing access and exit from higher floors. Where the staircase is continuous the same shall
be enclosed type serving as a fire separation from the basement floor and higher floors. Open
ramps shall be sanctioned if they are constructed within the building line subject to suitable
drainage provision.
(m) In case of basements of office and commercial occupancy sufficient number of exit ways and
access ways shall be provided as per norms stated in the National Building Code of India.
30.CHIMNEYS:– (1) Chimneys, where provided shall conform to the requirements of I.S 1645-1960
Indian standards code of practice for fire safety of building (General) chimneys, Flues, Flue pipes and
Hearths.
(2) The chimneys shall be built at least 0.9 metres above the top of the roof provided the top chimney
shall not be below the tops of adjacent parapet wall. In the case of sloping roof, the chimney top shall not
be less than 0.6 metres above the ridge of the roof in which the chimney penetrates.
31. LIGHTING AND VENTILATION OF THE ROOMS:–
(1) The whole or part of one side of one or more rooms intended for human habitation and not
abutting on either the front, rear or side open spaces shall abut on an interior open space
whose minimum width in all directions shall be 3.0 metres in case of buildings not more than
12.5metres in height and subject to the provision of increasing the same with
increasing height @ of 0.3 metres per every meter height or part thereof beyond 12.50
metres. However, in case of buildings already constructed with 3.0 metres the open space
for new construction on upper floor, the open space on this basis shall be ensured and would
remain as mandatory open space.
(2) Where the lighting and ventilation requirements are not met through daylight and natural
ventilation, the same shall be ensured through artificial lighting and mechanical ventilation as
per part VIII Building Services Section 1 Lighting and Natural Ventilation of National Building
Code of India as amended from time to time published by the Indian Standard Institution.
The latest version of the National Building Code of India shall be taken into account at the
time of enforcement of these Bye-laws.
(3) The minimum aggregate area of opening of habitable room excluding doors and fixed glazing
but including the frame shall be not less than 1/8th of floor area of the room.
(4) The minimum aggregate area of opening of and kitchens excluding doors and fixed glazing
but including the frame shall be not less than 1/6th of floor area of the kitchen.
(5) No portion of a room shall be assumed to be lighted if it is more than 7.5 metres from the
opening assumed for lighting of that portion of the room.
(6) In lodgesand hotels where attached toilets whose walls are not abutting on an external wall
are provided, mechanical ventilation system should be installed as per the provisions of the
National Building Code of India.
(7) 35% of setback to left as Green Area.
(8) Balconies shall not be less than 1.0 meter.
32. PARAPETS:-Parapet walls and hand rails provided on the edges of roof terrace, balcony, etc.
shall not be less than 1.0 meters and not more than 1.50 meters in height. The specified height
shall not apply when roof terrace is not accessible by a staircase.
33. BOUNDARY WALL :- (1) Except with the special permission of the Competent Authority, the
maximum height of the boundary wall shall be 2.5 m(Cantonments Act 2006) above the centre line
of the street.
(2) However, the provision of Bye-law No. 33(1) is not applicable to boundary walls of industrial
buildings, electric substations, transformer stations, institutional buildings like workshops, factories and
educational building like schools, colleges, including the hostels.
34. EXIT REQUIREMENTS:-(1)General requirements:
(a) Every building meant for human occupancy shall be provided with exits sufficient to
provide for safe escape occupants in case of fire or other emergency.
(b) In every building, exits shall comply with the minimum requirement ofthis part, except
those not accessible for general public use.
(c) All exitsshall be free of obstructions.
(d) No building shall be altered so as to reduce the number, width or protection of exits to
less than that required.
(e) Exits shall be clearly visible and the routes to reach the exit shall be clearly marked and
sign posted to guide the population of floor concerned.
(f) All exit ways shall be properly illuminated.
(g) Firefighting equipment where provided along exits shall be suitably located and clearly
marked but must not obstruct the exit way and yet there should be clear indication about
its location from either side of the exit way.
(h) Alarm devices shall be installed to ensure prompt evacuation of the population
concerned though the exits, wherever required.
(i) All exits shall provide continuous means of egress to the exterior of a building or to an
exterior open space leading to a street.
(j) Exits shall be so arranged that they may be reached without passing through another
occupied unit, except in the case of residential buildings.
(2) Types of Exits :- (a)Exits shall be either of horizontal or vertical type. An exit may be
doorway, corridor, passageways, ramp, internal staircase or external staircase, to an internal
or external open area, verandah and/or terraces which have access to the street or to roof of a
building.
(b) An exit may also include a horizontal exit leading to an adjoining building at the same level; and
(c) Lifts, escalators and revolving doors shall not be considered as exits.
(3) Number and Size of Exits:- The requisite number and size of various exits shall be pro
vided, based on the population in each room, area and floor based on the occupant load,
capacity of exits, travel distance and height of buildings.
(a) Arrangement of Exits: Exits shall be so located so the travel distance on the floor shall
not exceed 22.5 metres for residential, educational, institutional and hazardous
occupancies and 30 metres for assembly, business, mercantile, industrial and storage
occupancies. Whenever more than one exit is required for a floor of a building, exits shall
be placed as remote from each other as possible. All the exits shall be accessible from the
entire floor area at all floor levels.
The travel distance to an exit from the remote point shall not exceed half the distance as
stated above except in the case of institutional occupancy wherein it shall not exceed 6
metres.
(b)Occupant Load: The population in rooms, areas of floors shall be calculated based on the
occupant load given in Table 10.0.
Table 10.0: Occupant Load for various Occupancy Types
+-----+-------------------------------------------------------+-----------------------------------+
| S. | Group of Occupancy | Occupant Load Gross Area* in square metre / person|
| No. | | |
+=====+=======================================================+===================================+
| 1.0 | Residential | 12.5 |
+-----+-------------------------------------------------------+-----------------------------------+
| 2.0 | Educational | 4.0 |
+-----+-------------------------------------------------------+-----------------------------------+
| 3.0 | Institutional | 15+ |
+-----+-------------------------------------------------------+-----------------------------------+
| 4.0 | Assembly | |
+-----+-------------------------------------------------------+-----------------------------------+
| 4.1 | with fixed or loose seating and dance floors | 6++ |
+-----+-------------------------------------------------------+-----------------------------------+
| 4.2 | without seating facilities and dining rooms | 1.5++ |
+-----+-------------------------------------------------------+-----------------------------------+
| 5.0 | Mercantile | |
+-----+-------------------------------------------------------+-----------------------------------+
| 5.1 | street floor and sales basement | 3.0 |
+-----+-------------------------------------------------------+-----------------------------------+
| 5.2 | upper sale floors | 6.0 |
+-----+-------------------------------------------------------+-----------------------------------+
| 6.0 | Business and Industrial | 10.0 |
+-----+-------------------------------------------------------+-----------------------------------+
| 7.0 | Storage | 30.0 |
+-----+-------------------------------------------------------+-----------------------------------+
| 8.0 | Hazardous | 10.0 |
+-----+-------------------------------------------------------+-----------------------------------+
| | *The gross area shall mean plinth or covered area. | |
+-----+-------------------------------------------------------+-----------------------------------+
| | + Occupant load in dormitory portions of homes for the aged, orphanages, insane |
| | asylums, etc. where sleeping accommodation is provided, shall be calculated at not|
| | less than 7.5 square metre gross area per person. | |
+-----+-------------------------------------------------------+-----------------------------------+
| | ++The area shall include, in addition to the main assembly room or space, any |
| | occupied open connection or space in the same storey or in the storeys above or |
| | below, where entrance is common to such rooms and spaces and they are available |
+-----+-------------------------------------------------------+-----------------------------------+
for use by the occupants of the assembly place. No deductions shall be made in the
gross area for corridors, closets or other subdivisions; one area shall include all
space serving the particular assembly occupancy
(c) Capacity of Exits: The capacity of exits (doors and stairways) indicating the number of
persons of that could be safely evacuated through a unit exit width of 0.5 metre shall be as
given in Table 11.0
Table 11.0: Number of Occupants per Unit Exit Width
+-----+---------------------+------------+-------+--------+
| S. No.| Group of Occupancy | Number of Occupants |
| | | Stairways | Ramps | Doors |
+=====+=====================+============+=======+========+
| 1.0 | Residential | 25 | 50 | 75 |
+-----+---------------------+------------+-------+--------+
| 2.0 | Educational | 25 | 50 | 75 |
+-----+---------------------+------------+-------+--------+
| 3.0 | Institutional | 25 | 50 | 75 |
+-----+---------------------+------------+-------+--------+
| 4.0 | Assembly | 40 | 50 | 60 |
+-----+---------------------+------------+-------+--------+
| 5.0 | Business | 50 | 60 | 75 |
+-----+---------------------+------------+-------+--------+
| 6.0 | Mercantile | 50 | 60 | 75 |
+-----+---------------------+------------+-------+--------+
| 7.0 | Industrial | 50 | 60 | 75 |
+-----+---------------------+------------+-------+--------+
| 8.0 | Storage | 50 | 60 | 75 |
+-----+---------------------+------------+-------+--------+
| 9.0 | Hazardous | 25 | 30 | 40 |
+-----+---------------------+------------+-------+--------+
(d) Notwithstanding the detailed provision for exits as per Bye-law No. 34(3) (c) the minimum
width provision for each stairway shall be as per Table 12.0
Table 12.0: Minimum Staircase Width
+-----+------------------------------------------+----------------+
| S. No.| Group of Occupancy | Width in metres|
+=====+==========================================+================+
| 1.0 | Residential Building upto 3 storey height| 0.9 |
+-----+------------------------------------------+----------------+
| 2.0 | Other residential buildings, hostels and | 1.2 |
| | guest houses | |
+-----+------------------------------------------+----------------+
| 3.0 | Auditoriums, theatres and cinema | 1.5 |
+-----+------------------------------------------+----------------+
| 4.0 | All other buildings | 1.25 |
+-----+------------------------------------------+----------------+
| 5.0 | Hospitals | 2.0 |
+-----+------------------------------------------+----------------+
| 6.0 | Schools and colleges | 1.5 |
+-----+------------------------------------------+----------------+
(e) Notwithstanding the detailed provision for exits as per Bye-Laws the minimum width
provision for passageways shall be as per Table 13.0.
Table 13.0: Minimum Passageway Width
+-----+------------------------------------------+----------------+
| S. No.| Group of Occupancy | Width in metres|
+=====+==========================================+================+
| 1.0 | Residential Building upto 3 storey height| 0.9 |
+-----+------------------------------------------+----------------+
| 2.0 | Other residential buildings, hostels and | 1.25 |
| | guest houses | |
+-----+------------------------------------------+----------------+
| 3.0 | Auditoriums, theatres and cinema | 1.5 |
+-----+------------------------------------------+----------------+
| 4.0 | All other buildings | 1.2 |
+-----+------------------------------------------+----------------+
4. Doorways:- (a)Every exit doorway shall open into an enclosed stairway, a horizontal exit,
on corridor or passageway providing continuous and protected means of egress:
(b) No exit doorway shall be less than 1.0metres in width. Doorways shall be not less than 2.0
metres in height. Doorways for bathrooms, water closet stores etc. shall not be less than
0.75 metres wide.
(c) Exit doorways shall open outwards, that is, away from the room but shall not obstruct the
travel along any exit. No door, when opened, shall reduce the required width of stairway or
landing to less than 0.90 metres. Overhead or sliding doors shall not be installed.
(d) Exit door shall not open immediately upon a flight of stairs. A landing equal to at least the
width of the door shall be provided in the stair way at each doorway. Level of landing
shall be the same as that of the floor which it serves.
(e) Exit doorways shall be open-able from the side which they serve without the use of a key.
(f) Revolving doors shall not be allowed.
5. Stairway :- (a) For assembly, business, educational, hazardous, industrial, mercantile,
multi-storey and public buildings there shall be a minimum of two staircases and one of
them shall be an enclosed stairway and the other shall be on the external wall of the
building and shall open directly to the exterior, interior open space or to any open space for
safety. Single staircase may be accepted for educational, business or residential building
where floor area does not exceed 300 square metre and height of building does not exceed
24 metre and other requirements of occupant load, travel distance and width of staircase
shall meet the requirement. The single staircase in such cases shall be on the outer wall of
the building.
(b) Internal stairs shall be constructed of non-combustible materials throughout;
(c) Internal stairs shall be constructed as a self contained unit with at least one sideadjacent to an
external wall and shall be completely enclosed;
(d)The minimum width of an internal staircase shall be 1 metre subject to provisions of Table 9.0.
Columns and other building features shall not reduce the width of the staircase.
(e) The minimum width of treads without nosing shall 250 millimeter for an internal staircase for
residential buildings. In the case of other buildings the minimum tread shall be 300millimeter. The
treads shall be constructed and maintained in a manner to prevent slipping.
(f)The maximum height of riser shall be 190millimeter in the case of residential buildings and
150millimeter in the case of other buildings. They shall be limited to 12 per flight.
(g)Handrails shall be provided with a minimum height of 0.9metres from the centre of the tread;
(h) The minimum head room in a passage under the landing of a staircase and under the staircase
shall be 2.2 metres. Beams and other building features shall not reduce the head room of the
staircase.
(i) No living space, store or other fire exits shall open directly into the stairwell of the staircase.
(j)The external exit door of the staircase enclosure at ground level shall open directly to the open
spaces or should be reached without passing through any door other than a door provided to from
a draught lobby.
(k)The main staircase and fire escape shall be continuous from ground floor to the terrace level.
(l) No electrical shafts/AC ducts or gas pipe etc. shall pass through the staircase.
(m)Lift shall not open in staircase landing.
(n) No combustible material shall be used for any surface decoration in the staircase.
(o) A staircase shall not be arranged round a lift shaft.
(p) The exit sign with arrow indicating the way to the escape route shall be provided at a suitable
height from the floor level on the wall and shall be illuminated by electric light connected to corridor
circuits. All exit way marking signs of suitable size should be flushed with the wall and so designed
that no mechanical damage shall occur to them due to moving of furniture or other heavy
equipments. Further all landings of floor shall have floor indication boards indicating the number of
floor as per bye-law. The floor signage indicator shall be placed on the wall immediately facing the
flight of stairsand nearest to the landing. It shall be of size not less than 0.2 metre X0.5 metre.
(q) In case of single staircase it shall terminate at the ground floor level and the access to the
basement shall be by a separate staircase. However, the second staircase may lead to basement
levels provided the same is separate at ground level by either a ventilated lobby with discharge
points at two different ends or through enclosures.
6. Fire Escapes or External Stairs:-(a) Fire escapes shall not be considered in calculating
the evacuation time of a building.
(b) All fire escapes shall be directly connected to the ground.
(c)Entrance to fire escape shall be separate and remote from the internal staircase.
(d) The route to fire escape shall be free of obstructions at all times, except a doorway leading to
the fire escape which shall have the required fire resistance.
(e) Fire escape shall be constructed of non-combustible materials.
(f) Fire escapes stairs shall have straight flight not less than 0.75 metre wide with 250 millimeter
treads and risers not more than 190millimeter. The number of risers shall be limited to 16 per flight.
(g) Handrails shall be of a height not less than 0.90 metre.
7. Ramps:-(a)Ramps with a slope of not more than 1:10 may be substituted for and shall
comply with all the applicable requirements of required stairways as to enclosure capacity
and limiting dimensions. Ramps shall be surfaced with approved non-slipping materials.
(b)The minimum width of the ramps in hospitals shall be 2.25 metres;
(c) Handrails shall be provided on both sides of the ramp;
(d) Ramps shall lead directly to outside open space at ground level or courtyard or safe place.
8. Corridors:-(a) The minimum width of a corridor shall not be less than 75 centimetres in the
case of 2 storey row housing residential building. For all other buildings minimum width
shall be calculated based on the provision of Table 9.0.
(b) In case of more than one main staircase of the building interconnected by a corridor or other
enclosed space there shall be at least one smoke stop door across the corridor or enclosed space
between the doors in the enclosing walls of any two stair cases.
35. NON-FSI SPACES:-The following shall not be included in FSI calculation:
(a) In the Terrace above the top most storey, areas covered by stair-case room and lift rooms
and passages thereto, architectural features, elevated tanks(provided its height below
the tank from the floor does not exceed 3 meter and W.C (with floor area not exceed
1.20sqmts).
(b) Staircase and lift rooms and passage thereto in the stilt parking floor or upper floors used
for parking.
(c) Staircase and lift rooms and passage thereto in the basement floor or floors used for
parking.
(d) Area of the basement floor or floors used for parking.
(f) Area of the stilt parking floor provided it is open on sides, and used for parking.
(g) Servants or drivers bath room and water closet for each block in case of Non-High-Rise
buildings at ground floor or stilt parking floor.
(h) Watchman booth.
(i) Caretaker booth or room in ground floor or stilt parking floor.
(j) One toilet in each floor not exceeding of 4.2 sqm.
CHAPTER V
INCLUSIVE DESIGN
36. FACILITIES IN THE PUBLIC BUILDING FOR THE DIFFERENTLY-ABLED PERSONS:-These
provisions are applicable to all buildings, recreation areas and facilities used by public. It does
not apply to private domestic residences.
(1) Site planning:-Level of the roads, access paths and parking areas shall be described in
the plan along with specification of materials. Every building should have at least one
access to main entrance/exit to the differently-abled which shall be indicated by proper
signage. This entrance shall be approached through a ramp together with stepped entry.
The ramp should have a landing after every 9 metre run and in front of the doorway.
Minimum size of landing shall be 1.0 x 2.0 metre.
(2) Access path/walk way:- Access path from plot entry and surface parking to building
entrance shall be a minimum of 1.8 metre wide having even surface without any step.
Slope, if any shall not have gradient greater than 5%. Selection of floor material shall be
made suitably to attract or to guide visually impaired persons (limited to floor material)
whose colour texture is conspicuously different from that of the surrounding floor material or
the material that emit different sound to guide visually impaired persons. Finishes shall
have a non-slip surface with texture traversable by a wheelchair. Curbs wherever provided
should blend to common level.
(3) Parking :- For parking of vehicles of differently-abled people the following provisions shall
be made:
(a) Surface parking for two Equivalent Car Spaces (ECS) shall be provided near entrance
for the differently-abled persons with maximum travel distance of 30 metre from building
entrance.
(b) The width of parking bay shall be minimum 3.6 metre.
(c) The information stating that the space is reserved for wheel chair users shall be
conspicuously displayed.
(d) Guiding floor materials shall be provided or a device which guides visually impaired
persons with audible signals or other devices which serves the same purpose shall be
provided.
(4) Building Requirements:-The specified facilities for the buildings for disabled persons shall
be as follows:
(a) Approach toplinth level.
(b) Corridor connecting the entrance exits for the differently-abled.
(c) Stair-ways.
(d) Lift.
(e) Toilet.
(f) Drinking water.
(g) Braille signage shall be provided at the above specified facilities.
(5) Approaches to Plinth Level - (a) Ramp shall be provided with non-slip material to enter
the building minimum clear width of ramp shall be 1.8 metre with maximum gradient 1:12,
between top and bottom of the ramp. Length of ramp shall not exceed 9.00 metres having
0.8-metre-high handrail on both sides extending 300 millimetres beyond the ramp.
Minimum gap from the adjacent wall to the handrail shall be 50 millimetres.
(b) Minimum clear opening for the entrance door shall be 1.0 metre. Threshold shall not be
raised more than 12 millimetres.
(c) For stepped approach, size of tread shall not be less than 300 millimetre and maximum
riser shall be 150 millimetres. Provision of 0.8-metre-high handrails on both sides of the
stepped approach similar to the ramped approach shall be made.
(6) Corridors connecting the entrance/exit for the differently-abled - The corridor
connecting the entrance/exit for differently-abled leading directly outdoors to a place where
information concerning the overall use of the specified building can be provided to visually
impaired person either by a person or by signs, shall be provided as follows:
(a) Guiding floor materials shall be provided or devices that emit sound to guide visually
impaired persons.
(b) The minimum width shall be 1.5 metre.
(c) In case there is a difference of level, slope ways shall be provided with a slope of
1:12.
(d) Handrails shall be provided for ramps/slope ways.
(7) Stairways - Stairways with open riser and provision of nosing shall not be sanctioned.
(8) Lifts - Whenever lift is required as per bye-laws, provisions of at least one lift shall be made
for the wheelchair user with the following car dimensions of lift recommended for passenger
lift for 13 person's capacity by Bureau of Indian Standard.
(a) Clear internal depth minimum of 1.1 metre.
(b) Clear internal width minimum of 2.0 metre. Entrance door width shall be 0.91metre.
(c) A handrail not less than 0.6 metre long at 0.9 metre above floor level shall be fixed
adjacent to the control panel.
(d) The lift lobby shall be of an inside measurement of 1.8 m x 2.0 m or more.
(e) The Braille signage will be posted outside the lifts.
(f) Operational details of lifts shall confirm to the National Building Code of India as
amended from time to time and will be the responsibility of designer as well as
manufacturer.
(9) Toilets - One special water closet in a set of to let shall be provided for the use of
differently-abled with essential provision of washbasin near the entrance for the differently
abled.
(a) The minimum size shall be 1.5 metre x 1.75 metre.
(b) Minimum clear opening of the door shall be 0.9 metre and the door shall swing or
sliding type.
(c) Suitable arrangement for vertical/horizontal hand rails with 50millimetre clearance
from wall shall be made in the toilet.
(d) The water closet seat shall be 0.5 metre from the floor.
(e) One toilet-cum-bathroom unit in each floor may be constructed which will not be
counted in FAR for buildings having plot area less than 100 sq.m.
(10) Refuge - An alternative to immediate evacuation of a building via staircases and/or lifts is
the movement of differently-abled persons to areas of safety within a building. If possible,
they could remain there until the fire is controlled and extinguished or until rescued by fire
fighters.
(a) A refuge area may be provided at the fire protected stair landing on each floor that
can safety hold one or two wheelchairs.
(b) The area shall have doorways with clear opening width of 900 m and
(c) The area shall have an alarm switch installed between 900mm and 1200mm from
the floor level.
(d) Refuge area is mandatorily to be provided for the plot size of 50 Sq. mt and above.
CHAPTER VI
PROVISIONS OF STRUCTURAL SAFETY, ELECTRICAL AND PLUMBING SERVICES, WATER
SUPPLY, ETC.
37. LANDSCAPING:-(1) Institutional, Industrial, Commercial and Group Housing complexes shall be
required to plant a minimum number of trees as per Table 14.0.
Table 14.0
Number of trees to be planted.
+-----+-----------------------------------+-------------------------------------------------------+-----------------------------------+
| S. | Plot area (in square metre) | No of trees required | Minimum open space for soft landscaping|
| No. | | | |
+=====+===================================+=======================================================+===================================+
| 1 | Upto 2000 | One tree per 80 square metre of open space out of | 25% of open area. In case of |
| | | which minimum 50% trees to be in the category of | industrial plots no soft |
| | | evergreen trees having height of 6.0 metres or more | landscaping is required. |
+-----+-----------------------------------+-------------------------------------------------------+-----------------------------------+
| 2 | From 2001 to 12000 | One tree per 80 square metre of open space out of | 25% of the open area. |
| | | which minimum 50% trees to be in the category of | |
| | | evergreen trees, having height of 9.0metres or more | |
+-----+-----------------------------------+-------------------------------------------------------+-----------------------------------+
| 3 | More than12000 | One tree per 80 square metre of open space out of | 25% of the open area. |
| | | which minimum 50% trees to be in the category of | |
| | | evergreen trees having height of 12.0metres or more | |
+-----+-----------------------------------+-------------------------------------------------------+-----------------------------------+
(2) A detailed landscaping plan will have to be got approved from the Competent Authority
with specifications.
(3) Norms for planting in residential plots belonging to individual shall be as follows:
a. Minimum of one tree in every plot for plot size up to 100 square metre.
b. Minimum of two trees in every plot for plot size 100 to 500 square metre.
c. Minimum of three trees in every plot for plot size above 500 square metre.
d. All selected trees should not be less than 3.6 m in height and should be suitable for
local climate.
38. STRUCTURAL DESIGN AND SAFETY FEATURES:-The structural design of foundation elements
made of masonry, timber, plain concrete, reinforced concrete, pre-stressed concrete and structural
steel, shall be carried out in accordance with Part-VI Structural Design, Section-1 Loads, Section 2
- Foundation, Section 3. Wood, Section 4Masonry, Section 5- Concrete, Section 6 - Steel of
National Building Code of India, 2005 taking into consideration all relevant Indian Standards given
below:
(1) IS:1893(Part 1)2002 "Criteria for Earthquake Resistant Design of Structures (Fifth
Revision)"
(2) IS:13920-1993 "Ductile detailing of Reinforced Concrete Structures subject to Seismic
Forces - Code of Practice" November 1993.
(3) IS:13828-1993 "Improving Earthquake Resistance of Low Strength Masonry Buildings"
August 1993.
(4) IS:4326-2013 “Earthquake Resistant Design and Construction of Buildings - Code of
Practice (Second Revision)".
(5) IS:13827-1993 "Improving Earthquake Resistance of Earthen Building Guidelines" October
1993.
(6) IS:13935-2009 "Seismic Evaluation, Repair and Seismic Strengthening of Buildings -
Guidelines"
(7) For Protection of Landslide Hazard:
(a) IS 14458 (Part 1):1998 Guidelines for retaining wall for hill area: Part 1 Selection of
type of wall.
(b) IS 14458 (Part 2):1997 Guidelines for retaining wall for hill area: Part 2 Design of
retaining/breast walls.
(c) IS 14458 (Part 3):1998 Guidelines for retaining wall for hill area: Part 3
Construction of dry stone walls.
(d) 15 14496 (Part 2):1998 Guidelines for the preparation of landslide - Hazard zonation
maps in mountainous terrains: Part 2 Macro-zonation.
(8) Whenever an Indian Standard or the National Building Code of India is referred, the latest
provision in the standard should be adhered to.
39. MATERIAL AND CONSTRUCTION METHODS:-(1) Quality of Materials and
Workmanship(a)All materials and workmanship shall be of good quality conforming
generally to accepted standards of Public Works Department of West Bengal, Indian
Standard Specifications and Code as included in Part V Building Materials and Part VII
Constructional Practices and Safety of National Building Code of India.
(b)All burrow pits dug in the course of construction and repair of buildings, roads,
embankment and the like shall be deep and connected with each other in the formation of a
drain directed towards the lowest level and properly sloped for discharge into a river,
stream, channel or drain and no person shall create any isolated burrow pit which is likely
to cause accumulation of water which shall breed mosquitoes.
(2) New Materials and Design Methods
(a)The provisions of these Bye-Laws are not intended to prevent the use of any material or
method of design or construction not specifically prescribed by 39.1 above, provided any
such alternative has been approved by BIS or any other statutory body.
(b)Such alternatives may be approved provided that it is found that the proposed
alternative is satisfactory and confirms to the provisions of relevant parts regarding
material, design and construction and that material, method, or work offered is for the
purpose intended, at least equivalent to that prescribed, in the Bye-Laws in quality,
strength, compatibility, effectiveness, fire and water resistance, durability and safety.
40. ELECTRICAL SERVICES:- The planning, design and installation of electrical installation, air
conditioning installation and installation of lifts and escalators shall be carried out in accordance
with Part VIII Building Services, Section - 2 Electrical installations, Section - 3 Air- conditioning and
Heating, Section – 5 Installation of Lifts and Escalators of the National Building Code of India.
41. ENERGY CONSERVATION MEASURES :-
(1) Use of LED Lights-
(a)The use of incandescent lamps and conventional chokes in all new buildings,
institutions constructed in Government sector, Government Aided sector, Boards and
Corporations and Autonomous bodies is banned with immediate effect.
(b)It will be mandatory that in these existing buildings the defective incandescent lamps
and chokes when replaced would be replaced by only equivalent LED lighting system.
(c)The Competent Authority will effect necessary modification in the local demandnotices
within two months time from the issue of this notification to promote theuse of LED lights
instead of conventional bulbs and chokes while releasing/sanctioning new
connections/loads in such buildings.
(2) All new cases shall be sanctioned only if they have the following provisions for solar
water heating systems:-
(a) An open space in the roof which receives direct sunshine; the roof shall have a
load bearing capacity of at least 50 kg per square meter.
(b) The building must have a provision for continuous water supply to the solar water
heating system.
(c) The building design should provide for an insulated pipeline from the heating system
to all distribution points where hot water is required.
(d) The recommended minimum capacity of installation shall not be less than 25 litres per
day for each bathroom and kitchen subject to the maximum of 50% of the total roof
area is utilized by the system.
(e) Installation of Solar Assisted Water Heating Systems shall confirm to BIS
specification IS 12933. The solar collectors used in the system shall have the BIS
certification mark.
(3) Whenever hot water requirement is continuous auxiliary arrangement either with electrical
elements or oil based systems of adequate capacity may be provided.
(4) No new building in the following categories in which there is a system of hot water supply
shall be sanctioned unless this installation has solar assisted solar assisted water heating
system;
(a) Industries which use hot water for processing;
(b) All hospitals and nursing homes;
(c) All hostels, hotels, motels, guest houses and banquet halls;
(d) Large canteens i.e. which serve more than 100 persons in a day;
(e) Office building on a plot area of 500 square metre or above;
(f) Residential buildings on a plot area of 500 square metre or above;
(g) Residential schools and colleges;
(5) Provision of Solar Energy :-Provision for use of solar energy by using of solar
photovoltaic cells for generation of green energy be included in the building plan in case of
new building and in addition/alteration of the building.
42. LIGHTENING PROTECTION OF BUILDING:-The lightening protection for building shall be
provided based on the: provisions of Part III of the National Building Code of India.
43. PLUMBING SERVICE:-The planning, design, construction and installation of water supply,
drainage and sanitation and gas supply systems shall be in accordance with Part IX Plumbing
Services, Section -1Water Supply, Section- 2Drainage and Sanitation, Section – 3 Gas Supply of
the National Building Code of India.
44. REQUIREMENTS OF WATER SUPPLY IN BUILDING:-(1) The total requirements of water supply
shall be calculated based on the Building Occupancy as follows and as per Table 15.0. Wherever
not clearly specified, Occupancy load shall be calculated as per Table 10.0.
(a)Residential Building: Five persons per tenement
(b)Other Buildings: No. of persons based on occupant block and floor area
Table 15.0
Per capita water requirements for various occupancies/uses
+-----+-------------------------------------------------------+------------------------------+
| S. | Type of Occupancy | Consumption/head/day (litres)|
| No. | | |
+=====+=======================================================+==============================+
| 1 | Residential | |
| | In dwelling units | 135 |
| | Hostels with lodging (per bed) | 100 |
+-----+-------------------------------------------------------+------------------------------+
| 2 | Educational | |
| | Day school | 045 |
| | Boarding school | 135 |
+-----+-------------------------------------------------------+------------------------------+
| 3 | Hospital | |
| | Less than 100 beds | 340 |
| | More than 100 beds | 450 |
| | Medical quarters and hostels | 135 |
+-----+-------------------------------------------------------+------------------------------+
| 4 | Assembly Buildings like Cinemas theatres, auditoriums | 015 |
| | etc. (per seat accommodation) | |
+-----+-------------------------------------------------------+------------------------------+
| 5 | Government or semi-public business | 045 |
+-----+-------------------------------------------------------+------------------------------+
| 6 | Commercial | |
| | Restaurants – per seat | 070 |
| | Other business buildings | 045 |
+-----+-------------------------------------------------------+------------------------------+
| 7 | Industrial | |
| | Factories with bathrooms | 045 |
| | Factories without bathrooms | 030 |
+-----+-------------------------------------------------------+------------------------------+
| 8 | Storage (including warehouses) | 030 |
+-----+-------------------------------------------------------+------------------------------+
| 9 | Hazardous | 030 |
+-----+-------------------------------------------------------+------------------------------+
(2) Storage of Water-Minimum provision should be made for storage of water to meet the daily
requirements of the individuals using the building as per Tables 16.0 and 17.0.
Table 16.0
Minimum Flushing storage capacities
+-----+-------------------------------------------------------+-----------------------------------+
| S. | Type of Occupancy | Storage capacity (litres/per day) |
| No. | | |
+=====+=======================================================+===================================+
| 1 | For tenements having common conveniences | 180 per water closet seat |
+-----+-------------------------------------------------------+-----------------------------------+
| 2 | For residential premises other than tenements having | 270 per first water closet seat and|
| | common conveniences | 180 for each additional seat |
+-----+-------------------------------------------------------+-----------------------------------+
| 3 | For factories and workshops | 900 per water closet seat and 180 |
| | | per urinal |
+-----+-------------------------------------------------------+-----------------------------------+
| 4 | For cinemas, public assembly halls | 900 per water closet seat and 180 |
| | | per urinal |
+-----+-------------------------------------------------------+-----------------------------------+
Table 17.0
Minimum Domestic storage capacities
+-----+---------------+-------------------------------------------------------+
| S. | No. of floors | Storage capacity |
| No. | | |
+=====+===============+=======================================================+
| | For premises occupied as tenements with common convenience |
+-----+---------------+-------------------------------------------------------+
| 1 | Floor 1 | Nil provided no down take fittings are attached |
+-----+---------------+-------------------------------------------------------+
| 2 | Floor 2 and | 500 litres per tenement |
| | above | |
+-----+---------------+-------------------------------------------------------+
| | For premises occupied as flats or blocks |
+-----+---------------+-------------------------------------------------------+
| 3 | Floor 1 | Nil provided no down take fittings are attached |
+-----+---------------+-------------------------------------------------------+
| 4 | Floor 2 and | 500 litres per tenement |
| | above | |
+-----+---------------+-------------------------------------------------------+
Note:
1. If the premises are situated at a place higher than the road level in front of the
premises, storage at ground level shall be provided on the same lines as on
upper floors
2. The above storage may be Sanctioned to be installed provided that the total
domestic storage calculated on the above basis is not less than the storage
calculated on the number of down-take fittings according to the scale given
below
- Down-take taps: 70 litres each
- Showes:135 litres each
- Bathtubs: 200 litres each
45. RAIN WATER HARVESTING AND GROUND WATER REGULATIONS:–(1)Water harvesting
through storage of water runoff including rain water in all building on plots of 500 square metre and
above will be mandatory.
(2) Adoption of roof top rain water harvesting system is mandatory for all residential/
educational/institutional/hotel building/ industrial and commercial establishments.
(3) The plans submitted to the Board shall indicate the system of storm water drainage along
with points of collection of rainwater in surface reservoirs or in recharge wells. These
provisions will be applicable as per the Public Notice(s) of Central Ground Water Authority
issued from time to time.
(4) Undertaking of any operations connected with drilling, cleaning, construction or rehabilitation
of ground water abstraction structures and related works including installation of pumps
cannot be taken up without prior permission of the Cantonment Board.
(5) Drilling contractors or Agencies/Plot occupiers are required take prior permission for works
connected with drilling, cleaning, boring and installation of pumps.
(6) The Authority shall ensure that no drilling activity is undertaken without prior approval and is
authorized to take action against offenders by seizing of drilling rig, sealing of tube well and
disconnection of electric supply to the energized tube well.
(7) Waste water recycling system shall be incorporated in all buildings including group housing
having a minimum discharge of 40,000 litres and above per day for flushing of toilets /
Gardening / car washing, etc.
46. REQUIREMENTS OF SANITARY FITTINGS :- (1)To ensure optimization of water the following
measures shall be adopted in case of all new building sanction where plot size is more than 1000
square meters on a case to case basis as decided by the Competent Authority:
(a) Use of low duel flush capacity cisterns in water closets instead of the normal 12.5 litre
capacity.
(b) Use ofwaterless urinals in all public buildings.
(c) Provision of storage and use of recycled water for toilet flushing where the minimum
discharge in the building/complex is 10000 litres or more.
(2) The sanitary fittings and installations for different occupancies shall be as givenin Table
18.0 to 21.0.
Table 18.0
Sanitation requirements for Educational Occupancy
+-----+----------------+-----------------------+-----------------------------------+-----------------------------------+-----------------------------------+
| S. | fitments | Nursery School | Boarding institutions | Other institutions |
| No. | | | For males | For females | For males | For females |
+=====+================+=======================+=================+===================+=================+===================+
| 1 | Water closet | 1 for 15 pupils or | | | | |
| | | part thereof | N A | | | |
+-----+----------------+-----------------------+-----------------------------------+-----------------------------------+-----------------------------------+
| 2 | Ablution tap | One in each water closet | | | |
+-----+----------------+-----------------------+-----------------------------------+-----------------------------------+-----------------------------------+
| 3 | One water tap with drainage arrangement shall be provided for every 50 persons or part thereof in the vicinity of closets and urinals|
+-----+----------------+-----------------------+-----------------------------------+-----------------------------------+-----------------------------------+
| 4 | Urinal | _ | 1 for 20 persons| _ | 1 for 20 persons| _ |
| | | | or part thereof | | or part thereof | |
+-----+----------------+-----------------------+-----------------+-------------------+-----------------+-------------------+
| 5 | Wash basin | 1 for 15 pupils or | 1 for 8 pupils | 1 for 6 pupils | 1 for 60 pupils | 1 for 40 pupils |
| | | part thereof | or part thereof | or part thereof | or part thereof | or part thereof |
+-----+----------------+-----------------------+-----------------+-------------------+-----------------+-------------------+
| 6 | Bath | 1 for 40 pupils or | 1 for 8 pupils | 1 for 6 pupils | _ | _ |
| | | part thereof | or part thereof | or part thereof | | |
+-----+----------------+-----------------------+-----------------+-------------------+-----------------+-------------------+
| 7 | Drinking water | 1 for 50 pupils or | 1 for 50 pupils | 1 for 50 pupils | 1 for 50 pupils | 1 for 50 pupils |
| | taps | part thereof | or part thereof | or part thereof | or part thereof | or part thereof |
+-----+----------------+-----------------------+-----------------+-------------------+-----------------+-------------------+
| 8 | Cleaner sink | One per floor minimum | | | |
+-----+----------------+-----------------------+-----------------------------------+-----------------------------------+-----------------------------------+
Table 19.0
Sanitation requirements for Hotels
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| S. | fitments | residential public and staff | For public rooms | For non-residential staff |
| No. | | | For males | For females | For males | For females |
+=====+================+=======================================================+=======================================+=======================================+=======================================+=======================================+
| 1 | Water closet | 1 per 8 persons; omit roomwith occupants of both | 1 per 100 persons up to 400; add @ of one per 250 or | 2 per 100 persons up to 200; add @ of one per 100 or | 1 for 1-15 persons, 2 for 16-35 persons, 3 for 36-65 | 1 for 1-12 persons, 2 for 13-25 persons, 3 for 26-40 |
| | | sexes having attached toilet | part thereof | part thereof for | persons, 4 | persons, 4 |
| | | | for over 400; | over 200; | for 66-100 persons | for 41-57 persons |
+-----+----------------+-------------------------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| 2 | Ablution tap | One in each water closet | | | |
+-----+----------------+-----------------------------------------------------------------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| 3 | One water tap with drainage arrangement shall be provided for every 50 persons or part thereof in the vicinity of closets and urinals|
+-----+----------------+---------------------------------------------------------------------------------------------------------------------------------------+
| 4 | Urinal | _ | 1 for 50 persons or part thereof | _ | Nil upto 6 persons, 1 for 7-20, 2 for 21-45, 3 for 46-70, 4 for 71-100| _ |
+-----+----------------+-------------------------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| 5 | Wash basin | 1 per 100 persons omitting the wash basin installed in bath suites| 1 per water closet and urinal provided| 1 per water closet and urinal provided| 1 for 1-15 persons, 2 for 16-35 persons, 3 for 36-65 persons, 4 for 66-100 persons| 1 for 1-12 persons, 2 for 13-25 persons, 3 for 26-40 persons, 4 for 41-57 persons|
+-----+----------------+-------------------------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| 6 | Bath | 1 per 10 persons; omit occupants of the room with bath suites| _ | _ | _ | _ |
+-----+----------------+-------------------------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| 7 | Slope sink | 1 per 30 bedroom (I per floor minimum) | _ | _ | _ | _ |
+-----+----------------+-------------------------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| 8 | sink | One in each kitchen | | | |
+-----+----------------+-------------------------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
Notes
1. One water tap with drainage arrangements shall be provided for 50persons or part
thereof in the vicinity of water closets and urinals.
2. It may be assumed that two thirds of the building occupants are males and one third
female.
Table 20.0
Sanitation requirements for Hospital with Indoor Patient Ward
+-----+----------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| S. | fitments | Patient toilets | Office Toilets |
| No. | | For males | For females | For males | For females |
+=====+================+===========================+===============================+===============================+===============================+
| 1 | Toilet Suite* | For up to 4 patients | For individual doctor’s /officer’s rooms|
+-----+----------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| | For general wards, hospital staff and visitors | | |
+-----+----------------+---------------------------+-------------------------------+-------------------------------+-------------------------------+
| 2 | Water closet | 1 for 8 beds | 1 for 8 beds | 1 for 1-15 persons, 1 | 1 for 1-12 persons, 1 |
| | | हेतु 1 | हेतु 2 | | |
+-----+----------------+---------------------------+-------------------------------+-------------------------------+-------------------------------+
| 3 | Ablution tap | One in each water closet | |
+-----+----------------+-----------------------------------------------------------------------------------------------+-------------------------------+-------------------------------+
| 4 | Urinal | 1 per every 30 beds | _ | Nil up to 6 persons, 1 for 7-20, 2 for 21-45| _ |
+-----+----------------+---------------------------+-------------------------------+-------------------------------+-------------------------------+
| 5 | Wash basin | 2 up to 30 beds; 1 for | 1 for 1-15 persons, 2 for 16-35 persons| 1 for 1-12 persons, 2 for 13-25 persons|
| | | every additional 30 beds | | | |
| | | or part thereof | | | |
+-----+----------------+---------------------------+-------------------------------+-------------------------------+-------------------------------+
| 6 | Drinking water | 1 per ward | 1 per 100 persons or part thereof| | |
| | fountain | | | | |
+-----+----------------+---------------------------+-------------------------------+-------------------------------+-------------------------------+
| 7 | Bed pan | 1 per ward | _ | | |
| | washing sink | | | | |
+-----+----------------+---------------------------+-------------------------------+-------------------------------+-------------------------------+
| 8 | Cleaner sink | 1 per ward | _ | | |
+-----+----------------+---------------------------+-------------------------------+-------------------------------+-------------------------------+
| 9 | Kitchen sink | 1 per ward | _ | | |
| | & dish wash | | | | |
+-----+----------------+---------------------------+-------------------------------+-------------------------------+-------------------------------+
| | * A toilet suite comprises of one water closet, 1 wash basin and shower stall.| | |
+-----+---------------------------------------------------------------------------------------------------------------------------------------+---------------------------------------+---------------------------------------+
Table 21.0
Sanitation requirements for Medical Occupancy: Staff Quarters and Hostel
+-----+---------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| S. | fitments | Doctor’s Dormitories | Nurse Hostel: male & female |
| No. | | For males | For females | |
+=====+=====================+===========================+===============================+=======================================+
| 1 | Water closet | 1 per 4 persons or part | 1 per 4 persons or part | 1 per 4 persons or part thereof |
| | (Water Closet) | thereof | thereof | |
+-----+---------------------+---------------------------+-------------------------------+---------------------------------------+
| 2 | Ablution tap | One in each water closet |
+-----+---------------------+-----------------------------------------------------------------------------------------------+
| 3 | Wash basin | 1 per 8 persons or part | 1 per 8 persons or part | 1 per 8 persons or part thereof |
| | (Wash Basin) | thereof | thereof | |
+-----+---------------------+---------------------------+-------------------------------+---------------------------------------+
| 4 | Bath | 1 per 4 persons or part | 1 per 4 persons or part | 1 per 4 persons or part thereof |
| | | thereof | thereof | |
+-----+---------------------+---------------------------+-------------------------------+---------------------------------------+
| 5 | Cleaner sink | One per floor minimum | 1 per floor minimum |
+-----+---------------------+-------------------------------------------------------+---------------------------------------+
| 6 | Drinking water | One per 100 persons or part thereof with a minimum of one on each floor|
| | fountain | | |
+-----+---------------------+-----------------------------------------------------------------------------------------------+
Table 22.0
Sanitation requirements for Restaurants
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| S. | fitments | For public | For staff |
| No. | | For males | For females | For males | For females |
+=====+================+=======================================================+=======================================================+=======================================================+=======================================================+
| 1 | Water closet | 1 per 50 persons up to 200; add @ of one per 100 or | 3 per 100 persons up to 200; Over 200 add @ of 2 per | 1 for 1-15 persons, 2 for 16-35 persons, 3 for 36-65 | 1 for 1-12 persons, 2 for 13-25 persons, 3 for 26-40 |
| | (Water Closet) | part thereof for over 200; | 100 or part thereof; | persons, 4 | persons, 4 |
| | | | | for 66-100 persons | for 41-57 persons |
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| 2 | Ablution tap | One in each water closet | | |
+-----+----------------+-----------------------------------------------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| 3 | Urinal | One for 50 persons or part thereof | - | Nil upto 6 persons, 1 for 7-20, 2 for 21-45, 3 for | - |
| | | | | 46-70, 4 for 71-100 | |
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| 4 | One water tap with drainage arrangement shall be provided for every 50 persons or part thereof in the vicinity of closets and urinals|
+-----+----------------+-----------------------------------------------------------------------------------------------------------------------------------------------------------------------+
| 5 | Wash basin | One per floor for 100 persons or part thereof | One per floor for 100 persons or part thereof | One per floor for 100 persons or part thereof | One per floor for 100 persons or part thereof |
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| 6 | Slope sink | One in each restaurant | - | - | - |
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| 7 | Kitchen sink | One in each kitchen | - | - | - |
| | (Kitchen Sink) | | | | |
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
Notes
1. In every toilet at least one Indian style water closet shall be provided.
2. It may be assumed that two thirds of the building occupants are males and one third
female.
Table 23.0
Sanitation requirements for Government and Public Business
Occupancies and Offices
+-----+--------------------------+---------------------------------------+---------------------------------------+
| S. | fitments | For male personnel | For female personnel |
| No. | | | |
+=====+==========================+=======================================+=======================================+
| 1 | Water closet | 1 per every 25 persons or part thereof| 1 per every 15 persons or part thereof|
+-----+--------------------------+---------------------------------------+---------------------------------------+
| 2 | Ablution tap | One in each water closet |
+-----+--------------------------+-------------------------------------------------------------------------------+
| 3 | One water tap with draining arrangement shall be provided for every 50 persons or part thereof in the vicinity of closets and urinals|
+-----+--------------------------+-----------------------------------------------------------------------------------------------------------------------+
| 4 | Urinal | Nil upto 6 persons, 1 for 7-20, 2 for 21-45, 3 for 46-70, 4 for 71-100 | _ |
+-----+--------------------------+---------------------------------------+---------------------------------------+
| 5 | Wash basin | 1 for every 25 persons or part thereof| 1 for every 25 persons or part thereof|
+-----+--------------------------+---------------------------------------+---------------------------------------+
| 6 | Drinking water fountain | 1 per 100 persons or part thereof with a minimum of one on each floor| 1 per 100 persons or part thereof with a minimum of one on each floor|
+-----+--------------------------+---------------------------------------+---------------------------------------+
| 7 | Bath | Preferably one on each floor | Preferably one on each floor |
+-----+--------------------------+---------------------------------------+---------------------------------------+
| 8 | Cleaner sink | One per floor minimum preferably adjacent to sanitary rooms| One per floor minimum preferably adjacent to sanitary rooms|
+-----+--------------------------+---------------------------------------+---------------------------------------+
Notes:-
1. In every toilet at least one Indian style water closet shall be provided.
2. It may be assumed that two thirds of the building occupants are males and one third
female.
Table 24.0
Sanitation requirements for Factories
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+
| S. | fitments | For males | For females |
| No. | | | |
+=====+================+=======================================================+=======================================================+
| 1 | Water closet | 1 for 1-15 persons, 2 for 16-35 persons, 3 for 36-65 | 1 for 1-12 persons, 2 for 13-25 persons, 3 for 26-40 |
| | | persons, 4 for 66-100 persons; For 101 – 200 persons | persons, 4 for 41-57 persons 5 for 58 – 77 persons, 6 |
| | | add @ 3%; From over 200 persons add @ 2.5% | for 78 – 100 persons; For 101 – 200 persons add @ 5%; |
| | | | From over 200 persons add @ 4% |
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+
| 2 | Ablution tap | One in each water closet |
+-----+----------------+-----------------------------------------------------------------------------------------------+
| 3 | One water tap with drainage arrangement shall be provided for every 25 persons or part thereof in the vicinity of closets and urinals|
+-----+----------------+-----------------------------------------------------------------------------------------------------------------------+
| 4 | Urinal | Nil upto 6 persons, 1 for 7-20, 2 for 21-45, 3 for | - |
| | | 46-70, 4 for 71-100 For 101 – 200 persons add @ 3% | |
| | | From over 200 persons add @ 2.5% | |
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+
| 5 | Drinking Water | One for every 100 persons with a minimum of 1 at each floor| One for every 100 persons with a minimum of 1 at each floor|
| | fountain | | |
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+
| 6 | Baths | As required for particular trade or occupancy | As required for particular trade or occupancy |
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+
Table 25.0
Sanitation requirements for Hospitals with Outdoor Patient
+-----+----------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| S. | fitments | Patient toilets | Office Toilets |
| No. | | For males | For females | For males | For females |
+=====+================+===========================+===============================+===============================+===============================+
| 1 | Toilet Suite* | For up to 4 patients | For individual doctor’s /officer’s rooms|
+-----+----------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| 2 | Water closet | 1 for every 100 persons or part thereof| 2 for every 100 persons or part thereof| 1 for 1-15 persons, 2 for 16-35 persons| 1 for 1-12 persons, 2 for 13-25 persons|
+-----+----------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| 3 | Ablution tap | One in each water closet | |
+-----+----------------+-----------------------------------------------------------------------------------------------+-------------------------------+-------------------------------+
| 4 | Urinal | 1 per every 50 persons or part thereof| _ | Nil up to 6 persons, 1 for 7-20, 2 for 21-45| _ |
+-----+----------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| 5 | Wash basin | 1 for every 100 persons or part thereof| 2 for every 100 persons or part thereof| 1 for 1-15 persons, 2 for 16-35 persons| 1 for 1-12 persons, 2 for 13-25 persons|
+-----+----------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| 6 | Drinking water | 1 per 500 persons or part thereof | 1 per 500 persons or part thereof | _ | _ |
| | fountain | | | | |
+-----+----------------+---------------------------------------+---------------------------------------+---------------------------------------+---------------------------------------+
| | * A toilet suite comprises of one water closet, 1 wash basin and shower stall.| | |
+-----+---------------------------------------------------------------------------------------------------------------------------------------+---------------------------------------+---------------------------------------+
Table 26.0
Sanitation requirements for Assembly buildings like Cinema, Auditoriums and
Exhibition/Multipurpose Halls
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| S. | fitments | For public | For staff |
| No. | | For males | For females | For males | For females |
+=====+================+=======================================================+=======================================================+=======================================================+=======================================================+
| 1 | Water closet | 1 per 100 persons up to 400; Over 400 add @ of one per 250 or part thereof;| 3 per 100 persons up to 200; Over 200 add @ of 2 per 100 or part thereof;| 1 for 1-15 persons, 2 for 16-35 persons, 3 for 36-65 persons;| 1 for 1-12 persons, 2 for 13-25 persons, 3 for 26-40 persons;|
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| 2 | Ablution tap | One in each water closet | | |
+-----+----------------+-----------------------------------------------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| 3 | Urinal | One for 25 persons or part thereof | - | Nil upto 6 persons, 1 for 7-20, 2 for 21-45, 3 for | - |
| | | | | 46-70, 4 for 71-100 | |
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| 4 | One water tap with drainage arrangement shall be provided for every 50 persons or part thereof in the vicinity of closets and urinals|
+-----+-----------------------------------------------------------------------------------------------------------------------------------------------------------------------+
| 5 | Wash basin | One per floor for 100 persons or part thereof | One per floor for 100 persons or part thereof | One per floor for 100 persons or part thereof | One per floor for 100 persons or part thereof |
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| 6 | Slope sink | One in each restaurant | - | - | - |
+-----+----------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+-------------------------------------------------------+
| | Notes | 1. In every toilet at least one Indian style water closet shall be provided. |
| | | 2. It may be assumed that two thirds of the building occupants are males and one third female. |
+-----+----------------+-----------------------------------------------------------------------------------------------------------------------------------------------------------------------+
CHAPTER VII
SAVINGS, PENALTIES, REPEALS AND INTERPRETATION
47. SAVINGS CLAUSE :-The existing buildings approved by the Board shall remain valid and the
buildings erected as per the building plans approved by the Board before the date of entry into
force of this Bye-Laws shall also be valid.
48. PENALTIES :-Any person who contravenes any of the provisions of these byelaws shall be
punishable as per the provisions of the Act.
49. INTERPRETATION TO BE CONSONANCE WITH THE CANTONMENTS ACT, APPLICABLE
RULES AND POLICIES:-Notwithstanding anything contained hereunder, the provisions of this
Building Bye-Laws shall at all times be in consonance and within the provisions of the Act and
other statutory rules under the Act. Whenever any discrepancy or ambiguity arises, the Act shall
apply and shall prevail. The provisions of the Act are in built into these Bye-Laws and shall be read
as part of the Bye-Laws for understanding and applying the Bye-Laws. Similarly, the terms of
lease, terms of old grant and such other terms as per the existing policies or any policy issued in
this regard from time to time shall prevail and the Building Bye-Laws now promulgated shall be
within the meaning of these policies and shall not be in any way contrary to the said policy terms.
To the said extent, the terms of these Building Bye-Laws are conditional.
FORM A: CERTIFICATE REGARDING SAFETY FROM NATURAL HAZARDS AND STRUCTURAL SAFETY
(To be submitted by structural engineer and applicant through e-Chhawani portal)
To,
The Chief Executive Officer
Barrackpore Cantonment Board
Sir/Madam,
I hereby certify that the erection/ re-erection or addition/ alteration in building No. __
_______________ on / in plot no.__________________________________ in ward
no.________________________ situated at road / street _______________ survey / GLRS No.
______________ of Barrackpore Cantonment has been undertaken by me.
I certify that the building plans submitted for approval adhere to the safety requirement of the
Byelaws.
It is certified that the structural design including safety from natural hazards based on soil
conditions has been duly incorporated in the design of the building and this provisions shall be
adhered to during the constructions.
I being a structural engineer, certified that the addition/alterations satisfy the requirements of
structure stability and all such alterations, repairs involving walls, columns, beams, roof, footings
foundations etc., are covered under the provisions of building byelaws requiring compliance.
Signature of Engineer _____________________________
Name in block letters _____________________________
Address _____________________________
_____________________________
_____________________________
Signature of Applicant _____________________________
Name in block letters _____________________________
Address _____________________________
_____________________________
_____________________________
Dated________________
FORM B: CERTIFICATE FOR SUPERVISION
(To be submitted by Architect/ Civil Engineer/ Structural Engineer and applicant through
e-Chhawani portal)
To,
The Chief Executive Officer
Barrackpore Cantonment Board
Sir/Madam,
I hereby certify that the erection/ re-erection or addition/ alteration in building No. ___
_______________ on / in plot no.__________________________________ in block
no.________________________ situated at road / street _______________ survey / Cantonment
No. ______________ shall be carried out under my supervision and I certify that all materials (type
and grade) and the workmanship of the work shall be generally in accordance with the general
specification submitted along with the building application and that the work shall be carried out
according to the sanction plan. I shall be responsible for the execution of the work in all respects.
Signature of
Architect /Civil Engineer / Structural Engineer ______________________________
Name of
Architect /Civil Engineer / Structural Engineer_______________________________
License no. of
Architect /Civil Engineer / Structural Engineer ______________________________
Signature of
Architect /Civil Engineer / Structural Engineer ______________________________
______________________________
Signature of Applicant _____________________________
Name in block letters _____________________________
Address _____________________________
_____________________________
_____________________________
Dated _____________________
Name of Cantonment _____________________
FORM C: INDEMNITY BOND FOR BASEMENT
(To be submitted by applicant through e-Chhawani portal)
TO BE SUBMITTED ON NON-JUDICIAL E-STAMP PAPER OF RS. 20/- DULY ATTESTED BY
THE OATH COMMISSIONER/MAGISTRATE FIRST CLASS
Indemnity bond is executed by Shri _________________ s/o Shri_______________ R/o
________________ hereby called Applicant of plot no. _________ in ___________
______________ of Barrackpore Cantonment in favour of the Competent Authority.
Whereas the Applicants have submitted the plan of basement and whereas the Applicants have
represented to the Competent Authority and if sanction is granted for the construction of the said
basement the Applicants shall indemnify the Competent Authority of any loss at time of digging of
foundation of the said basement or in the course of construction of the basement or even
thereafter.
And whereas the said Applicants have further agreed to indemnify the Competent Authority for any
claims put up against the Authority either by way of damage, compensation or in any other way in
case the Authority is required to pay any such amount to any person or the Applicant or Applicants
of the adjoining properties. The Applicants hereby agree and undertake to indemnify the Authority
to pay the full extent of the amount the Authority may require to pay to the extent here in above
mentioned.
The Applicant further undertake and agree to indemnify the Authority for any such amount the
Competent Authority may require to pay either by way of compensation or damage or any other
amount and further undertake to indemnify the authority of all cost and expenses that the Authority
may require to defend such action in any court of law. The Applicants undertake that no excavation
shall be carried out beyond permissible boundaries of plot. Any damage occurring during or due to
excavation made at site to pubic sewer, water drains shall be made good by the Applicants.
In consideration of the above matter, undertaking and indemnity given by the said Applicants the
Authority hereunder in this behalf grant the sanction to construct the basement to the said
Applicant.
In witness hereof the Applicants above mentioned put their hands and seal to the said indemnity
bond on this _______ day of ___________
(Executants) (1) _____________________
(Applicant) (2) _____________________
Witness:
(1) _____________________
(2) _____________________
FORM D: NOTICE FOR COMMENCEMENT OF WORK
To,
The Chief Executive Officer
Barrackpore Cantonment Board
Sir/Madam,
I hereby state that the erection / re-erection or addition/alteration in/o building no.
________________ on / in Survey No. _______________________ Mohalla /Road
_____________ Barrackpore Cantonment will be commenced on ____________ as per your
permission vide office letter no. __________ dated ______________ under the supervision of
________________________________________Architect / Civil Engineer / Structural Engineer /
in accordance with sanctioned plans.
Signature of Applicant ________________________
Name of Applicant ___________________________
(IN BLOCK LETTERS)
Address of Applicant _________________________
_____________________________
_____________________________
_____________________________
Dated________________
FORM E: NOTICE ON COMPLETION OF BUILDING
(Section 242 of the Act)
To,
The Chief Executive Officer,
Barrackpore Cantonment Board
Sir/Madam,
1. We hereby certify that the erection/re-erection of building or addition/alteration in building on
_________ __________ (address) has been Supervised by the undersigned and is strictly in
accordance to sanctioned plan vide letter ______________ dated ___________. No provisions of
the building byelaws have been transgressed. The work has been competed to our satisfaction
and the workmanship and materials used strictly in accordance with general and detailed
specifications. Drainage/sanitation/water supply works have been executed as per building
byelaws and sanctioned plan. No provision of the Building Byelaws and conditions prescribed or
orders issued there under have been transgressed in the course of the work. The building is fit for
use for which it has been erected/re-erected or altered/constructed and enlarged.
2. Certificates:
2.1 Certified that the building/s has been constructed according to the Sanctioned Plan and
structural design which incorporate the provisions of structural safety as specified in relevant
prevailing IS Codes/Standards/Guidelines.
2.2 Certified that water harvesting as well as waste water re-cycling systems have been provided
as per the sanctioned building plan.
2.3 It is also certified that construction has been done under our supervision and guidance and
adheres to the drawings submitted and the records of supervision maintained by us.
3. Permission to occupy or use the building may be granted.
4. Any subsequent change from completion drawings will be the responsibility of the Applicant(s)
Signature of Applicant _______________________________
Name _______________________________
Address _______________________________
Signature of Supervisory Architect _______________________________
License No. _______________________________
Name _______________________________
Address _______________________________
Signature of Structural Engineer _______________________________
License No. _______________________________
Name _______________________________
Address _______________________________
Dated _________________
FORM F: CERTIFICATE FOR COMPLETION-CUM-OCCUPANCY OF BUILDING
(Section 246 of the Act)
To,
____________________________
____________________________
____________________________
____________________________
Sir,
With reference to your notice of completion dated _____________________ I hereby certify that
building, as per description below certified plan at _____________
_______________________________________________________ address whose plans were
sanctioned vide sanction no ________________dated ______________ has been inspected with
reference to Building Bye-Laws in respect of the structural safety, hygienic and sanitary conditions
inside and in the surrounding. It is declared fit for occupation. The detail of the construction
work completed is as follows:
Brief description of each block with area:
1. ______________________________________________________________
2. ______________________________________________________________
3. ______________________________________________________________
4. ______________________________________________________________
5. ______________________________________________________________
6. ______________________________________________________________
7. ______________________________________________________________
8. ______________________________________________________________
9. ______________________________________________________________
10. ______________________________________________________________
11. ______________________________________________________________
12. ______________________________________________________________