Gazette Tracker
Gazette Tracker

Core Purpose

This notification establishes the Shillong Cantonment Building Bye-laws, 2026.

Detailed Summary

This notification establishes the Shillong Cantonment Building Bye-laws, 2026, which apply within the limits of Shillong Cantonment and come into force on the date of their final publication in the Official Gazette by the Central Government. These bye-laws govern building activities including new construction, demolition, and changes in occupancy or use. Key definitions are provided, including "Act" referring to the Cantonments Act, 2006, and "Competent Authority" for building plan sanction under Chapter 10 of the same Act. The "Central Government" for these Bye-laws is specified as the Government of the Union in the Ministry of Defence. Detailed regulations are outlined for basements, cellars, and underground floors, specifying permitted uses such as storage, parking, and housing building services. Importantly, uses for Stilt Parking, Ground Floor, Basement, Lower Ground floor, Cellar, or underground floor listed in 2.17(a) and 2.17(b) (i) to (v) are not reckoned for Floor Space Index (FSI). However, if a basement or lower ground floor is used for living purposes, it is permitted provided requirements for proper lighting, ventilation, and a minimum floor height of 3.0 metres are met, and in such cases, it shall be reckoned for FSI. All such lower floors must have a minimum height of 2.40m, adequate lighting/ventilation (e.g., one exhaust fan per 50 sq.m. for cellars), watertight walls/floors, and proper access/exit. Bathrooms and toilets are permitted in these areas, with their area counted towards FSI. Cellar/underground floor construction requires leaving mandatory setbacks, with the area beyond the covered area exempted from Plot Coverage calculation.

Full Text

EXTRAORDINARY PART II—Section 4 PUBLISHED BY AUTHORITY No. 15] NEW DELHI, FRIDAY , JULY 3, 2026/ASHADHA 12, 1948 CG-DL-E-11072026-274412 1.00 0.00 0.45 1.20 0.45 0.60 1.80 0.60 0.75 2.40 0.75 1.00 3.00 0.75 1.20 4.50 0.90 1.50 5 1.50 0.75 1.00 10 2.00 0.90 1.00 15 2.00 0.90 1.30 20 2.30 1.10 1.30 50 4.00 1.40 1.30 100 8.00 2.60 1.00 150 10.60 2.70 1.00 200 12.40 3.10 1.00 300 14.60 3.90 1.00 50 5.00 1.60 1.30 100 5.70 2.10 1.40 150 7.70 2.40 1.40 200 8.90 2.70 1.40 300 10.70 3.30 1.40 1993. 1993. (ii) CMAR (ii) CMAR (ii) CER (ii) CMAR (ii) CER (iii) CER (क) (ि) (ग) 1 2 3 4 5 6 7 8 योग्य ) 1.75 50% 4 - 14 - वाहन ) 1.50 50% - 3 - 11 1 2 3 4 5 6 भवन 0.50 50% 3 11 1 2 3 4 5 6 7 8 1.80 3.00 3.00 4.60 4.50 1.80 1.00/1.00 3.00 3.00 4.50 4.50 1.80 1.20/1.20 3.00 3.00 3.00 6.00 9.00 2.10 1.80/1.80 3.00 3.00 3.00 6.00 9.00 2.40 2.10/1.80 3.00 4.00 4.00 6.00 9.00 3.00 3.00/2.40 3.00 4.50 5.0 0 6.00 9.00 3.00 4.50/3.00 तक 3.00 6.00 6.00 6.00 9.00 6.00 5.00/5.00 6.00 6.00 6.00 9.00 6.00 6.00/6.00 1) 2 2001 से 12000 1. मैं / हम ………………………… .................................................................. पुत्र / पत्नी ............................................................. आयु ........................ दनवासी - (धनष्पादक ) (1) ___________________ (आवेदक) (2) ___________ ________ (1) _________________ (2) _________________ पता: _____________________________ _____________________________ पता: _____________________________ _____________________________ _____________________________ _______________________________ _______________________________ ______________________________ पता: _____________________________ _____________________________ _____________________________ आवेिक का पता: _____________________________ _____________________________ _____________________________ नाम: ___________________________________ पता: ____________________________________ ____________________________________ नाम: ____________________________________ पता: ____________________________________ नाम: ____________________________________ पता: ____________________________________ ____________________________ ____________________________ ____________________________ ____________________________ _______________________________________ ___________________________________________________ ( पता) पर खस्थत भवन, 1. _________________________________________________________________ 2. _________________________________________________________________ 3. _________________________________________________________________ 4. _________________________________________________________________ 5. _________________________________________________________________ 6. _________________________________________________ ________________ 7. _________________________________________________________________ 8. _________________________________________________________________ 9. _________________________________________________________________ 10. ____________________________ _____________________________________ 11. _________________________________________________________________ 12. _________________________________________________________________ MINISTRY OF DEFENCE NOTIFICATION New Delhi, the 3rd July, 2026 S.R.O . 15(E).—The following draft of the Shillong Can tonment Building bye -laws, 2026, which the Cantonment Board proposes to issue in exercise of the powers conferred by section 251 of the Cantonments Act, 2006 and in supersession of notification number 6005 - AP dated 20th July, 1932, except as respects things done or omitted to be done before such supersession, is hereby published for the information of the public likely to be affected thereby; and notice is hereby given that the said draft Bye -laws shall be take n into consideration on or after the expiry of a period of thirty days from the date on which copies of the Gazette of India containing the Bye -laws are made available to the Public; and the said draft Bye -Laws is also available at the office of the Canton ment Board, Shillong and on the website shillong.cantt.gov.in Any person interested in making any objections or suggestions on the proposals contained in the draft Bye -laws may forward the same in writing, fo r consideration of the Cantonment Board within the period so specified to the Cantonment Board, Shillong or at e-mail address : ceoshil [email protected] The Draft of the Shillong Cantonment Building Bye -laws, 2026 CHAPTER I GENERAL 1. SHORT TITLE, EXTENT AND COMMENCEMENT - (1) Short title - These byelaws shall be called the Shillong Cantonment Building Bye -laws, 2026 (2) Extent - These bye -laws shall apply within the limits of Shillong Cantonment. (3) Commencement - These shall come into force on the date of their final publication in the Official Gazette by the Central Government. (4) Applicability - They shall apply to the building activity or land as given in 5 to 7 below: (5) When a building is newly erected, the bye -laws shall apply to the designs and construction of the building. (6) Where the whole or any part of the building is dismantled/demolished. (7) Where the occupancy or use of the building is changed. 2. DEFINITIONS - In these Bye -laws, unless the context otherwise requires: (1) “Act” means the Cantonments Act, 2006 as amended from time to time; (2) “Access” means a clear approach to a plot or a building; (3) “Air-Conditioning ” means the process of treating air so as to control simultaneously its temperature, humidity, cleanliness and distribution to meet the requirements of conditioned space; (4) “Application ” means an application made in such a form as may be specified by the authority from time to time; (5) “Applicant ” means a person who has legally valid occupancy rights on leased or old grant or private land and intends to erect/ re -erect a building or to make any addition/alteration in the building; (6) “Approved ” means approval granted by the Competent Authority as prescribed under the Act; (7) “Appendix” means an appendix to these Bye -Laws; (8) “Architect ” means any person who holds a valid registration with the Council of Architecture, India as per the provisions of the Architects Act, 1972; (9) “Architectural Projection” means a chajja, cornice etc. which is a protrusion from the building facade or line of the building only for aesthetic purpose and not used for any habitable purpose; (10) “Atrium ” - means a sky lighted and naturally/mechanically ventilated area in a building with no intermediate floors and used as circulation space or entrance foyer; (11) “Addition to a building ” means addition to the cubic contents of a building; (12) “Alteration of a building” means, - (a) The sub -division of any room in such building so as to convert the same into two or more separate rooms, or (b) The change in two or more rooms in such building which increases or diminishes the cubic contents of any room or rooms; (c) The conversion of any passage or space in such building into a room or rooms (13) “Apartment” means whether called block, chamber, dwelling unit, flat, office, showroom, shop, godown, premises, suit, tenement, unit or by any other name, separate and self -contained part of any immovable property, including one or more rooms or enclosed spaces, located on one or m ore floors or any part thereof, in a building or on a plot of land, used or intended to be used for any residential or commercial use such as residence, office, shop, showroom or godown or for carrying on any business, occupation, profession or trade, or for any other type of use ancillary to purpose specified; (14) “Amenity Space” for the purpose of these regulations, amenity space means a statutory space kept in any layout to be used for any of the amenity such as open spaces, parks recreational grounds, pla ygrounds, sports complex, gardens convenience shopping, parking lots, primary and secondary schools, nursery, health club, dispensary, Nursing home, hospital, sub post -office, police station, electric substation, ATM of banks, electronic cyber library, ope n market, garbage bin, assisted living and hospice together, senior citizen housing and orphanage together, project affected person' housing, auditorium, conventional Centre, water supply, electricity supply and includes other utilities, services and conve niences; (15) "Balcony” means a horizontal projection including a handrail, balustrade or parapet to serve as a passage or sitting out place with at least one side open, except for the railing or parapet wall for safety; (16) “Barrier free” means a barrier free en vironment which enables people with disabilities to move safely and freely and to use the facilities within the built environment; (17) “Basement(s) Cellar(s) or Underground floor(s)” (a) ‘Basement(s)’ - means the lower storey / floor(s) of a building, partly below the ground level. It shall be applicable only in flat terrain. (b) ‘Cellar(s) or Underground floor(s)’ - Means a room or floor which may be wholly underground. Lower ground floor(s) - Means the floor(s) of a building below the ground floor which may be closed on at least one side. The basement / lower ground floor / cellar / underground floor can be put to any of the following uses: (i) Storage of house -hold or other goods of non - flammable materials; (ii) Dark room; (iii) Strong -rooms, bank cellars, serv ice floors etc. (iv) Air-conditioning equipment and other machines used for services, other infrastructure and utilities of the building, e.g. Air conditioning Plant and Equipment, Water storage, Electric Sub -Station, HT and LT panel rooms, Transformer Compartment, Control Room, Pump House, Generator Room, mechanical services, installation of electrical and firefighting equipment’s and other services like kitchen store, housekeeping store, laundry, serving & store pantries and other essential services required for the maintenance / functioning of the building, etc. (v) Parking places and garages; Note: Uses of Stilt Parking/Ground Floor/Basement / Lower Ground floor / Cellar / under ground floor as listed in 2.17(a) and 2.17(b) (i) to (v ) shall n ot be reckoned for the purpose of FSI. (vi) The cellar / underground floor shall not be used for living purposes. The use of Basement / Lower Ground floor for living purpose or functional use will be permitted provided the requirement of proper lighting, ventil ation are complied and minimum floor height is 3.0 metres. In such cases the basement shall be reckoned for the purpose of FSI; (vii) Every basement / lower ground floor / cellar / underground floor shall have a minimum height of at least 2.40m from the floor to the underside of the roof slab or ceiling; (viii) Adequate lighting / ventilation shall be provided for the basement / lower ground floor / cellar / underground floor. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fan (one exhaust fan for 50 sq.m. of cellar / under ground floor area), air - conditioning system etc. (ix) Adequate arrangement shall be made such that surface drainage does not enter the basement / lower ground floor / cellar / underground floor; (x) The walls and floors of the basement / lower gr ound floor / cellar / underground floor shall be water -tight and be so designed that the effect of the surrounding soil and moisture, if any, are taken into account in design and adequate damp proofing treatment is given; (xi) There shall be access to the bas ement / lower ground floor / cellar / underground floor providing access and exit. Ramps shall be permitted if they are proposed for construction; (xii) Bathroom and toilet shall be permitted in the basement / lower ground floor / cellar / underground floor wit h proper system for disposal of waste; (xiii) The area of bathroom and toilet so permitted in the basement / lower ground floor / cellar / underground floor shall be counted towards FSI calculations; (xiv) Where cellar / under ground floor is proposed to be constructe d, it shall be allowed after leaving the mandatory setbacks and the area beyond the covered area shall be exempted from calculation of Plot Coverage. (18) “Board” shall mean a Cantonment Board constituted under the Cantonments Act, 2006; (19) “Building” means a house, outhouse, stable, latrine, shed, hut or other roofed structure whether of masonry, brick, wood, mud, metal or other material, and any part thereof, and includes a well and a wall other than a boundary wall but does not in clude a tent or other portable and temporary shelter; (20) “Building Line” means the line up to which the plinth of a building adjoining on a street or on an extension of a street or on a future street may lawfully extend and includes the line prescribed, if any, in any scheme; (21) “Building Envelope” means the horizontal spatial limits up to which a building may be permitted to be constructed on a plot which shall not exceed the clear setbacks as prescribed in the Bye -Laws; (22) “Built up Area” means the area covered by a building on all floors including cantilevered portion, mezzanine floors, if any, but excluding the areas specifically exempted from computation of Floor Space Index (F.S.I) under these Regulations; (23) “Bungalow Area” means area outside notified civil area with old grant/leasehold bungalows excluding privately held properties; (24) “Canopy ” means an overhead roof or else a structure over which a fabric or metal covering is attached, able to provide shade or shelter from weather conditions such as sun, hail, snow and rain. A canopy can also be a tent, generally without a floor; (25) “Chajja” means a projection or horizontal structure overhang usually provided over opening of external walls to provide protection from sun and rain or for architectural conside ration; (26) “Chimney” means an upright shaft containing and encasing one or more flues; (27) “Civil area” means an area declared to be a civil area by the Central Government under sub -section (1) of section 46; (28) “Compliance” means verification of the properties of construction materials based on test data and verification of the strength and structural adequacy of various components of buildings and structures; (29) “Competent Authority” means the authority to sanction the building plan as prescribed under Chapter 10 of the Cantonments Act, 2006; (30) “Commercial Building” means a building used or constructed or adapted to be use d the whole or a substantial part of building for commercial purposes. (31) “Ceiling Height” means vertical distance betwe en the finished floor and the ceiling; (32) “Central Government” for the purpose of these Bye -laws means the Government of the Union in the Ministry of Defence; (33) “Civil Engineer” means any person who is a graduate of civil engineering from a recognized Indian or foreign university duly approved by Govt of India or is a member of Civil Engineering Division of the Institution of Engineers (India) and is competent to carry out supervision of building works as per approved drawings and designs; (34) “Corner plot or Sit e” means a plot or site at the junction of and fronting on two or more intersecting streets; (35) “Combustible material” means any material if it burns or adds heat to a fire when tested for combustibility in accordance with good practice; (36) “Courtyard” means a space open to the sky enclosed or partially enclosed, by walls or by railing and shall be at ground floor level; (37) “Cupboard” means a space used for storage of household goods/dress having shelves/partitions not more than 60 cm apart; (38) “Covered Area” - Means the ground area covered by the building immediately above plinth level, but does not include the space covered by the following : (a) Compound wall, gate, slide/swing door, open ramp, canopy, porch, pergolas, verandahs, balconies which ar e open on at least 2 sides and areas covered by chajja or similar projections and secondary / emergency / fire exit staircases which are uncovered and open at least on three sides. (b) Drainage culvert, conduit, catch -pit, gully -pit, chamber, gutter and the li ke. (c) Garden, rockery, well and well structures, plant nursery, water pool, swimming pool (if uncovered), platform round a tree, tank, fountain, bench, platform with open top and/or unenclosed on sides by walls and the like. (d) Sentry sheds, transformer / sub - stations sheds. (e) Access to the basement / lower ground floor / underground floor, if uncovered. Note: secondary / emergency / fire exit staircases: If more than 1(one) such staircases are provided, then 1 (one) staircase with the highest area will be considered for the purpose of covered area. (39) “Clinic” means a diagnostic centre where patients are examined and investigated for diagnosis and relevant advices are given for management but the patients are not admitted as indoor patients as in a hospital or nursing home; (40) “Polyclinic” means an institution com prising a group of doctors from various medical specialties who provide examination, diagnosis, and consultation to patients; (41) “Damp Proof Course” A course consisting of appropriate water proofing material provided to prevent penetration of dampness or moisture from any part of the ground to the structure or from one part of the structure to any other part of it; (42) “Drain” means a line of pipes including all fittings and equipment such as manholes, inspection chambers, traps, gully traps and f loor traps, used for the drainage of a building, or a number of buildings, or yards appurtenant to buildings, within the same cartilage. Drain shall also include open channels used for conveying surface water; (43) “Drainage” means the removal of any liquid by a system constructed for this purpose; (44) “Dwelling Unit/ Tenement” An independent housing unit with separate facilities for living, cooking and sanitation needs; (45) “Demolished” means total dismantling of an existing building; (46) “Equivalent Car Space (ECS)” means the space occupied by the vehicle as well as the minimum space needed to move it into and out of the space and one equivalent car space is as defined in National Building Code, as amended time to time; (47) “Existing Building or Use” means a building, str ucture or its use as sanctioned or deemed to have been sanctioned by the Competent Authority, existing before the commencement of the Bye -Laws; (48) “Exit” means a passage, or means of egress from any buildings, storey or floor area to a street or any other op en space or safety; (a) Vertical exit - It is a means of exit used for ascending or descending between two or more levels including stairways, ramps and fire escapes. (b) Horizontal exit - It is a protected opening through or around a fire -resistant wall or bridge connecting two buildings. (c) Outside exit - It is an exit from the building to a public way, or to an open area leading to a public way, or an enclosed fire -resistant passage leading to a public way; (49) “Enclosed Staircase” means a staircase separated by fire resistant walls and doors from the rest of the buildings; (50) “External Wall” means an outer wall of a building not being a partition wall, even though adjoining to a wall of another building and also means, a wall abutti ng on an interior open space of any building; (51) “Floor” means the lower surface in a storey on which one normally walks in a building. The general term, floor, unless otherwise specifically mentioned, shall not refer to a mezzanine floor. Sequential numbering of floors shall be determined by their relation to the determining entrance level. For floors at or wholly above ground level the lowest floor in the building with direct entrance from the road/street to be termed as ground floor. Othe r floors above ground floor shall be numbered in sequence as Floor 1, Floor 2, with numbers increasing upwards; (52) “Floor Space Index or FSI” means the quotient obtained by dividing the multiple of the total of the covered area on all floors by the area of the plot i.e. FSI = Total covered area of all floors Plot Area (53) “Floor Area Ratio or FAR” – Floor Area Ratio or FAR means the quotient obtained by dividing the multiple of the total of the covered area on all floors and hundred by the area of the plot i.e. FAR= Total covered area of all floor x 100 Plot Area (54) “Flue” means a confined space provided for the conveyance to the outer air of any product of combustion resulting from the operation of any heat producing appliance or equipment employing solid, liquid or gaseous fuel; (55) "Footing" means a foundation unit constructed in brick work, masonry or concrete, steel or any other material permissible as per IS Code under the base of a wall or column for the purpose of distributing the load over a large area; (56) “Foundation” means that part of the structure which is below the lower most floor and which provides support for the super structure and which transmits loads of the super - structure to the ground; (57) "Frontage" means the measurement of the side of any site abutting the road; (58) “Front Open Space / Margin / Setback” means the distance between the boundary line of plot abutting the means of access/road/street and the building line. In case of plots facing two or more mean s of access, roads / streets, the plot shall be deemed to front on all such means of accesses/roads/streets; (59) “Gallery” means an intermediate floor or platform projecting from a wall of an auditorium or hall providing extra floor, additional seating accomm odation etc; (60) “Garage Private” means a building designed or used for the parking of a motor car or other vehicles; (61) “Ground Floor” Means the floor from where the main entrance to the building is taken with reference to the primary road / footpath adjacent to the plot. The Floor(s) beneath the ground floor shall be termed as ‘basement(s) / lower ground floor(s) / cellar(s) / underground floor(s)’ etc., as the case may be; (62) “Ground Coverage/Plot Coverage” Means the quotient obtained in terms of percentage, by dividing the area of a floor having maximum covered area by plot area, i.e. Plot Coverage (PC) = Area of a floor having maximum covered area x100 Plot area (63) “Ground Level” Means the surface(s) after formation cutting of the site from where the plinth of the building starts. In case of sloping site there may be 2 (two) or more such levels; (64) “Group Housing” means housing of more than one dwelling unit, where land is owned jointly as in the case of cooperative societies or public agencies such as Local Authorities or Housing Boards or property developers etc. and the construction is undertaken by one agency but shall not include properties which are co -owned by family members and may comprise all or any of the following: (a) a dwelling unit, (b) open spaces intended for recreation and ventilation, (c) roads, paths, sewers, drains, water supply and ancillary installations, street lighting and other amenities, (d) convenient shopping place, schools, co mmunity hall or other amenities for common use; (65) “Habitable floor/room” Means a floor/room of minimum height 3.0 metres occupied or designed for occupancy by one or more persons either for study, living, sleeping, eating, cooking, working but not including bathrooms, water closet compartments, laundries, serving & store pantries, corridors, cellars, attics, household, storage spaces etc., and space that are not used frequently or during extended period; (66) “Height of floor/room” Means the vertical distance me asured from the finished floor surface to the finished slab surface/Ceiling. Minimum height of floors in a building including Stilt Parking at any point shall be 3.0 Mts. Provided that in case of sloping roofs (pitched, gabled, folded, etc.) the minimum h eight at the lowest part of roof shall not be less than 2.2 metres from the floor surface. Provided that for verandah, Bathroom, W.C., passages, puja room, store room, stair cabin, minimum height shall be 2.20 mts. (67) “Height of Building” Means the vertical distance(s) measured from the plinth(s) of the building to the terrace of the last floor of the building in the case of flat roofs; and in the case of pitched roofs, up to the point where the external surface of the outer wall intersects the finished surface of the sloping roof; and in the case of gables facing the road, the mid -point between the eaves level and the ridge. Architectural features serving no other function except that of decoration or requirement as per architectural design for e.g. roof of churches, steeples / bell - tower / turrets / spires / domes, sloping roofs, etc., shall be excluded for the purpose of measuring heights. However, where an attic is proposed within the roof, the height of the roof sha ll be reckoned for the purpose of building height. Height Exemptions - The following appurtenant structures shall not be included in the height of the building - (a) Roof tanks and their supports (with total height not exceeding 3m); (b) HVAC, lift rooms and simila r service equipment; (c) Stair cover (MUMTY) not exceeding 3 m in height; (d) Chimneys, parapet walls and architectural features not exceeding 1.5 m in height. (e) Roof Top Towers (RTTs)/machineries. (f) Open terrace swimming pools & shower/changing rooms with deep end not more than 1.8m in depth. (g) Residual Floor of height 1.65 m or less. (68) “Internal Wall” means all partition walls in the interior of a building excluding walls which abut exterior or interior open Spaces; internal walls when made of bricks shall be a minimu m of 125 mm brick work in suitable mortar; other non -load bearing partitions shall be of suitable thickness; (69) “Loft” means an intermediate floor in between two main floors but not more than 1.50 metre in height which may be adopted or constructed for storage purpose; (70) “Masonry” means the form of construction composed of brick, stone, tile, concrete blocks, gypsum or other similar building material units or combination of these material units laid up, bonded together and set in mortar; (71) “Mezzanine floor” means an intermediate floor between any two floors above ground floor in all types of buildings, provided the same is counted as part of total permissible floor area ratio and height of the building. Mezzanine floor may be permitted with the maximum height of 2.40m and a maximum area of 1/3rd the floor area of that particular floor; (72) “Marginal Distance / Side and Rear Marginal Open Space” means a minimum distance required to be left open to sky between the boundary of the building plot and the building line on respective sides and laid down in each case by the Authority, beyond nothing can be constructed; (73) “Mumty” means a structure with a covering roof over a staircase and its landing built to enclose only the stairs for the purpose of prov iding protection from weather and not meant for human habitation; (74) “Materials Alteration” means a change of use in building materials used in any existing building; (75) “Natural Hazard” Means the probability of occurrence, within a specific period of time in a given area of a potentially damaging natural phenomenon; (76) “Natural Hazard Prone Areas” Means areas likely to have moderate to high intensity of earthquake or cyclonic storm, or significant flood flow or inundation or landslides/mud flows/avalanches, or one or more of these hazards; (77) “Non -Structural Component” Those components of buildings, which do not contribute to the structural stability such as infill walls in RCC frame buildings, glass panes, claddin gs, parapet walls, chimneys e tc; (78) “Non -Combustible” means a material which does not burn or add heat to a fire when tested for combustibility in accordance with good practice; (79) “Open Space/ Amenity Space” means a statutory space kept in any layout to be used for any of the amenity suc h as open spaces, parks recreational grounds, playgrounds, sports complex, gardens convenience shopping, parking lots, primary and secondary schools, nursery, health club, dispensary, Nursing home, hospital, sub post-office, police station; (80) “Occupancy” means the function or use of the building; (81) “Parking Space” means an area enclosed or unenclosed sufficient in size to park vehicle together with a drive -way connecting the parking space with a street or alley and provided for ingress and egres s of the vehicles; (82) “Partition” means an interior non -load bearing wall, one storey or part storey in height; (83) “Pillar” means a wood, stone, brick, RCC or a metal pillar and includes all columns or upright post or support, stanchions (steel structures) an d an assemblage of columns of stanchions properly riveted or welded or bolted together; (84) “Plinth” Means the portion of a structure between the level of the ground and the floor immediately above the ground; (85) “Porch or Portico” means covered surface supported on pillars or otherwise for the purpose of pedestrian or vehicular approach to a building; (86) “Parapet” Means a low wall or railing built along the edge of a roof or floor not less than 90cm in height; (87) “Public Building” means a building used or intended to be used either ordinarily or occasionally, as a church, temple, mosque or any other place of public worship, dharmshala, college/school, hostel, Hospital, theatre, cinema, public concert room, lecture room, library, orphanage, or rescue home or any other place of public assembly; (88) “Public Garage” means a building or portion thereof designed other than a private garage, operated for gains, designed or used for repairing, servicing, hiring, selling or storing motor driven or other vehicles; (89) “Refu ge Area” Means an area within the building for a temporary use during egress. It generally serves as a staging area which is protected from the effect of fire and smoke; (90) “Residential Building” means a building used or constructed or adapted to be used wholly for human habitation; (91) “Residential cum Commercial Building ” means a building where part of the building is used or constructed or intended to be used for human habitation with remaining part used or constructed or intended to be used for commercial purpose; (92) “Registered Architect / Engineer / Firm etc.” Means a qualified Architect/Engineer/Town Planner/Firm etc. registered with the Cantonment Board in e - Chhawani portal. Note - Presently, the legislation for profession of architecture is app licable in the country in the form of Architects Act 1972. Accordingly, the qualifications of architects, competence and service conditions followed in the profession of architecture are in accordance of the provision of the said Act and the rules made the re under. Whereas, for other professions and professionals like engineers, developers/promoters for taking up any project there is no legislative framework available/applicable in the country. In the absence of any such legislation, the appropriate qualifi cations, service conditions, professional fees and charges in the engineering profession etc., are varying and are not based on any uniform formula. Keeping the above in view, all construction shall be carried out under supervision of the Architect on Reco rd (AR), Construction Engineer on Record (CER) or Construction Management Agency on Record (CMAR) as per the Table 7 of these Bye -Laws. (93) “Repairs” means and includes the following activities, which do not otherwise violate any provisions regarding general building requirements, structural stability and fire safety requirements of these Bye -Laws. (a) A parapet wall or a cornice or chhajja within the boundaries of the permissible setbacks & ground coverage area of the site. Provided that the total height of the parapet wall shall not be more than 90 cm and width of the cornice or chhajja shall not be more than 60 cm; (b) Repairing of staircase; (c) White washing or painting; (d) Re-flooring of the surface of an existing floor; (e) Minor repairs and recasting of an existin g damaged roof without changing the character and dimensions of such roof; (f) Erection of a false ceiling in any floor for air -conditioning, lighting or decorative purposes; (g) Plastering and Patch work (h) Providing or closing an internal door or a window or a ven tilator not opening directly opposite a door or a window of another building (i) Replacing of fallen bricks or stones (j) Repairing or renewing existing plumbing, sanitary and other utility services (k) Repairing of boundary wall (l) Installation of air conditioner/water tank/ solar plants/ solar water heater etc., (m) Re-roofing or renewal of roof including roof of intermediate floor at the same height; (n) Re-roofing or renewal of roof of existing Assam Type Building including replacement of roof truss with wood or steel. (o) Replacing fallen bricks, stones, pillars, wooden post, beams, any wooden members of the existing building etc. (p) Construction or reconstruction of sunshades not more than 0.75 meters in width within one's own land and not overhanging on public street; (q) Re-erection of internal partitions provided the same are within the purview of the Bye -laws. (r) Erection or re -erection of internal partitions provided the same are within the purview of the Bye -Laws. (94) “Residual floor” Means a floor below the ground floor/ lower gr ound floor(s) not exceeding 1.65 metres in height from the floor to the underside of the slab or ceiling arising out of technical compulsions during construction in the case of sloping sites. Residual Floor shall not exceed half of the Plinth Area of the m ain floor above. This floor shall be considered as part of the structure and shall be provided with braces or struts as measure to counter soft storey effect. This floor shall be used for non - habitable purposes etc. and shall not be reckoned for the purpos e of calculation of FSI or building height. Affidavit cum undertaking stating the duties and responsibilities of the applicant, compliance that the residual floor shall not be used for any other purpose except as specified in the byelaws; (95) “Storey” means the portion of a building included between the surface of any floor and the surface of the floor next above it, or if there be no floor above it, then the space between any floor and the ceiling next above it; (96) “Street” includes anyway, road , lane, square , court, alley or passage in a Cantonment, whether a thoroughfare or not and whether built upon or not, over which the public have the right of way and also the road way or foot -way over any bridge or cause way; (97) “Site or Plot” means a parcel / piece of land enclosed by definite boundaries; (98) “Smoke Pipe” means a flue approximately horizontal, made of metal or other material in which smoke or the products of combustion are conducted from a furnace to a chimney; (99) “Store or Shop” shall mean any store or shop in which it is not intended that any person shall reside; (100) “Structural Engineer” means a person who is a graduate of civil engineering from a recognized Indian or Foreign university duly approved by Government of India or is a member of Civil Engineering Division of the Institution of Engineers (India) with experience in structural engineering practice which includes structural design and field work; (101) “Sanctioned Plan” means the set of plans and specifications submitted under section 235 of th e Cantonments Act, 2006 under the Bye -Laws and regulations in connection with a building and duly sanctioned by the authority under section 234/237/238 of the Cantonments Act, 2006; (102) “Sun Shade” means a sloping or horizontal structural overhang usually pro vided over openings on an external wall to provide protection from sun and rain; (103) “To Abut” means to be positioned juxtaposed to a road, lane, open space, building etc; (104) “To erect or Re -erect” means (a) To erect a new building on any site whether previously built upon or not; (b) To re -erect any building of which portion of the existing building have been dismantled/demolished, pulled down, burnt or destroyed, damaged by storm, rains, fire, earthquake or any other natural calamity to the same extent, and similar specifications as existing prior to damage; (c) Conversion from one occupancy to another; (d) To carry out alterations and; (e) To add to a storey/storeys; (105) “Total Floor Area” means the area of all floors of building including habitable, basement a nd mezzanine floor; (106) “Travel Distance” means the distance an occupant has to travel to reach the exit; (107) “Verandah” means a covered area with at least one side open to the outside; (108) “Water Closet” means a privy with arrangements for flushing the pan with water but does not include bathroom; (109) “Window” means an opening to the outside other than a door which provides all or part of the required natural light, ventilation or both to an interior space and not used as a means of ingress/egress; (110) “Workshop” means a room or a group of rooms or building in which goods are manufactured or repaired; (111) “Washing Platform” means an authorized platform for washing and also for servicing of scooters / cars etc; (112) Words and expressions used and not defined in these bye laws but defined in the Act shall have the same meanings as assigned to them in the Act; 3. BUILDING SANCTION REQUIRED - (1) No person shall carry out any erection, re - erection, addition or alteration to any building or cause the same to be done withou t obtaining a sanction for such work from the Competent Authority. 4. PROCEDURE FOR OBTAINING BUILDING PERMISSION - (1) An Applicant who intends to erect or re -erect a building or to make addition or alteration in any building shall register himself/herself in the e -Chhawani portal and apply through online, duly enclosing all the requisite documents and plans, in e -Chhawani portal through Cantonment Board registered Architect/s, Civil Engineer, Structural Engineer, Structural Design Agency, Co nstruction Engineer, Construction Management Agency. Provided that due to any reasons, if it is not feasible for an applicant to apply in the e - Chhawani portal the Board may prescribe a procedure for submission of applications: Provided further that the C entral Government or Director General may issue guidelines from time to time to the Board regarding the manner of submitting applications for the said purpose. (2) Only persons who have legally valid occupancy rights on leased or old grant or private land are eligible for applying for sanction of building plan. In cases wherein breach of lease conditions on leased land or breach of old grant terms in old grant land involved, the board shall have the right to refuse or reject applications for erections, re -erection or addition/alteration till the breach of lease or old grant conditions is regularized or condoned. (3) On scrutiny of the documents and plans submitted, the applicant receives the development charges communication (or the charges levied by the Board by whatever name these are known) for payment to Cantonment Board. (4) On deposition of development charges (or the charges levied by the Board by whatever name these are known), the sanction is conveyed within the prescribed timelines. (5) All Government Depar tments including Central and Semi - Government Departments shall forward copies of their plans duly prepared as per the provisions laid down in these Bye -Laws to the Authority for sanctioning except Defence Department. (6) The application shall also be accompa nied with an Affidavit cum undertaking stating the duties and responsibilities of the applicant, compliance that the parking and circulation spaces shall not be converted or blocked or used for any other activity, etc. (sample attached to the Bye -Laws). 5. INFORMATION ACCOMPANYING APPLICATION FOR BUILDING PERMISSION/DOCUMENTS AT THE TIME OF APPLICATION - (1) The following documents shall be submitted through online on e -Chhawani portal at the time of submitting application for building sanction: (i) Proof of ownership /HOR/ Lessee / Successor / legal rights document (ii) Indemnity Bond as per Form A. (iii) Proof of identity. (iv) The Site plan, the building plan, elevations, sections general specification, Seismic certificate, Structural drawings, any other information/docume nts which may be sought by the Authority etc. (v) Structural Sufficiency Certificate from the registered Engineer for the proposed building/s. (vi) Structural Sufficiency Certificate from the registered Engineer in case of existing buildings. (vii) A certificate from the Applicant and the Structural Engineer regarding Safety from natural Hazards and Structural Stability as per Form B set forth in the Appen dix. (viii) A certificate from the registered architect / Technical Personnel undertaking the supervision by submitting Form C, set forth in the Appendix. (ix) Any other document as approved by the competent authority (Cantonment specific documents). (2) Site Plan - Shall be drawn to a scale not less than 1:200 and shall show (i) Boundaries of the plot with dimensions (ii) Position of the plot in relation to the neighboring streets. (iii) Position of the building proposal in relation to North direction of the site. (iv) Plot area, plot coverage and FSI. (v) Gap between existing buildings. (vi) Surface drains, position and sizes of septic tank and soak pit in cubic dimensions of length, breadth and depth . (vii) Roof with all projections, setback dimensions, surface drain, Soft Cover, Landscape, Parking, Rain Water Harvesting, Sentry -shed, Transformer / substation, etc. (viii) Any other particulars as prescribed by the Authority. (3) Building Plans, Sections and Elevations accompanying the application shall be drawn to a scale not less than 1:100 and shall: (i) Include floor plans of all floors, indicate the use of each floor of the building. Shall indicate height of the building and parapet. (ii) Give dimensions of the p rojected portions. (iii) Include a roof plan indicating drainage and roof slope in case of building proposal having pitch roof(s). (iv) Specify total floor area of the proposed building/s. (v) Specify total floor area of the existing building/s. (4) Colour Scheme - The plans accompanying the applications may have the colour scheme as described by the consultant architect/engineer in the legends of the drawings. (5) Structural Design Basis Report and Seismic Certificate - (a) Seismic Certificate from the registered engineer/agency that the design is relevant to Indian Standard Code of Practice as well as compliant to earthquake resistant design shall accompany the application on the body of the structural drawings. (6) Signing of the Plan - All plans and d rawings shall be duly signed by the applicant, all the recorded lessee/s of the holding/plot/Bungalow and technical personnel having registration with the Authority. The qualified technical personnel or agency/consultant/s shall be registered in e -chhawani portal. 6. SERVICE PLANS, SPECIFICATIONS, STRUCTURAL SUFFICIENCY CERTIFICATE AND SUPERVISION - (1) Service Plans - The services plans shall include all details of building and plumbing services, and also plans, elevations and sections of private water sup ply, sewage disposal system and rainwater harvesti ng system, if any as per NBC 201 6. (2) Specifications - Specifications, both general and detailed, giving type and grade of materials to be used, duly signed by the registered architect/engineer, shall accompan y the plans. (3) Structural Sufficiency Certificate - In case of existing building and wherever applicable, the application shall be accompanied by structural sufficiency certificate signed by the registered engineer / agency and the owner jointly to the effect that the building is safe against various loads, forces and effects including due to natural disasters, such as, earthquake, landslides, cyclones, floods etc., a s per National Building Code 201 6 and other relevant Codes. The registered engineer / ag ency shall also have the details to substantiate his design for buildings having covered area above 500 sqmt. (4) Supervision - The notice shall be further accompanied by a certificate from the registered architect/Technical Personnel undertaking the supervisi on. 7. REPAIRS TO BUILDING IN CANTONMENT AREA - (1) A parapet wall or a cornice or chajja within the boundaries of the permissible setbacks & ground coverage area of the site. Provided that the total height of the parapet wall shall not be more than 90 cm and width of the cornice or chajja shall not be more than 60 cm (2) Repairing of staircase; (3) White washing or painting; (4) Re-flooring of the surface of an existing floor; (5) Minor repairs and recasting of an existing damaged roof without changing the character and dimensions of such roof; (6) Erection of a false ceiling in any floor for air -conditioning, lighting or decorative purposes; (7) Plastering and Patch work (8) Providing or closing an internal door or a window or a ventilator not opening directly opposite a door or a window of another building (9) Replacing of fallen bricks or stones (10) Repairing or renewing existing plumbing, sanitary and other utility services (11) Repairing of boundary wall (12) Installation of air conditioner/water tank/ solar plants/ solar water heater, etc., (13) Re-roofing or renewal of roof including roof of intermediate floor at the same height; (14) Re-roofing or renewal of roof of existing Assam Type Building including replacement of roof truss with wood or steel. (15) Replacing fallen bricks, stones, pillars, wooden post, beams, any wooden members of the existing building etc. (16) Construction or reconstruction of sunshades not more than 0.75 meters in width within one's own land and not overhanging on public street; (17) Erection or re -erection of internal partitions provided the same are within the purview of the Bye -Laws. 8. BUILDING APPLICATION FEES AND APPLICABLE CHARGES - (1) Building Application Fees: The building application fees for residential, commercial, institut ional, apartment, educational, storage, industries, major proposals etc., shall be decided by the Authority from time to time. The building plan application shall be deemed valid only if the applicant has paid the requisite building application fee as dete rmined by the Board and fulfilled the required conditions under section 236 of the Act. (2) Development Charges: The development charges, labour cess and other fees for residential, commercial, institutional, apartment, educational, storage, industries, major proposals etc., as determined by the Board from time to time are to be paid by the applicant through online before issuance of the sanction of the building application by the Competent Authority. (3) Stacking of building material on street or other public land shall not take place without the permission of the Chief Executive Officer on a case -to-case basis and on payment of charges as fixed by the Chief Executive Officer in terms of Section 257 of the Act. (4) The fees for No Objection Certificates shall be as determined by the Board from time to time. (5) The fixation of these fees shall be governed by the following : - (i) For erection of new building shall be as determined by the Board (ii) For re -erection of exis ting building the fees chargeable shall be the same as for erection of new building. (iii) For addition and alteration in the existing building, the fees shall be chargeable on the added portion only. (iv) For modified/ revised plan etc. of an already sanctioned building a processing fee of 10% the fees paid during sanction of building permission shall be paid by the applicant. (v) For change of use and variation of rates, the fees chargeable shall be the difference between the two, subject to the condition s that (a) The revised plan is in conformance with the building bye laws applicable for that particular use and the building plans are compatible for that use. (b) No fees to be refunded in case there is change of use of higher rate to lower rate, e.g. commercial to residential use. (vi) For renewal/revalidation of building permission, ¼th of the building permission fees shall be paid on the remaining portion only. 9. SCRUTINY OF BUILDING PLAN APPLICATIONS - Once the plans have been scrutinized and objections, if any, have been communicated through online, the applicant may modify the plan, comply with the objections raised and resubmit through online, for consideration of the competent authority. 10. SANCTION/REFUSAL OF PLANS - (1) In case of old gra nt land, the proposed building plan shall be in conformity with the old grant terms and the land policies of Ministry of Defence. (2) In case of leased land, the proposed building plan shall be in conformity with the lease hold rights / terms and the land po licies of Ministry of Defence. (3) The Competent Authority shall sanction the plan unless such building would contravene any of the followings, namely: - (i) That the building or the use of the site for the building or any of the particulars comprised in the site plan, ground plan, elevation, section or specification contravenes the provisions of the Act or the Bye -laws made thereunder; (ii) That the notice for sanction does not contain the required particulars or is not prepared in the manner required under the pr ovisions of these Bye -Laws; (iii) That any information or documents required by the Board under these Bye - Laws has or have not been duly furnished; (iv) That the building plan is not in accordance with the Bye -Laws framed by the Board under section 260 or those frame d under clauses (19) and (20) of section 348 of the Act; (v) That the building would be an encroachment on defence land or land vested in the Cantonment Board; (vi) That the site of the building does not abut on a street or projected street and that there is no acc ess to such building from any such street by a passage or path-way appertaining to such site; or (vii) That the erection or re -erection of the building is not in conformity with any general scheme sanctioned under Section 240 of the Act; (viii) When the land on which i t is proposed to erect or re -erect the building is entrusted to the management of the Board by the Government if the erection or re-erection constitutes a breach of terms of the entrustment of management or contravenes any of the instructions issued by the Government regarding the management of the land by the Board; (ix) When the land on which it is proposed to erect or re -erect the building is not held on a lease from the Government, if the right to build on such land is in dispute between the person applying for sanction and the Govt.; (x) That the minimum size of the plot for residential purpose is not less than 50 sqmt.; or (xi) That it is mandatory to provide Rain water Harvesting if the size of the plot exceeds 200 sqmt.; (xii) That it is mandatory to provide Rooftop Solar Installation if the size of the plot exceeds 500 sqmt.; (4) On receiving all the modifications that have been sought for under Bye -Law No. 9 (Scrutiny of Building Plan Applications) , the Authority must intimate the grant/refusal of the buildi ng permission in writing within 30 working days after the receipt of the modified proposal. The Authority shall as far as possible advice on all the objections and modification so as to ensure their compliance . (5) In case all or any modifications have not been complied with, the refusal must be issued in writing and fresh application is to be sought for consideration. (6) For building proposals requiring no modifications the grant of building permission must be intimated by the Authority within 30 working days after receipt of the application or else it will be deemed that the permission has been granted, subject that the proposal complies with all the applicable bye -laws and provisions of Cantonments Act 2006. (7) Notwithstanding anything stated in the abo ve byelaws, it shall be incumbent on every person whose plans have been approved to submit modified/ revised (amended) plans for any architectural/ structural/ alterations/ redevelopment/ deviations/ rectifications etc. proposed to be made during the cours e of construction of the building work and the procedure laid down for approval of plans mentioned here to before shall apply to all such modified/ revised plans. (8) For existing building(s) which exceeds the permissible plot coverage prescribed in the byelaws and a vertical extension is proposed, such proposal shall be considered to the extent that the covered area of the proposal is within the permissible plot coverage, F.S.I. and other provisions of the byelaws. 11. REVOCATION OF SANCTIONED BUILDING P LANS AND LIABILITY OF THE APPLICANT TO CONFORM TO BYELAWS - (1) The Competent Authority may revoke any building sanction issued under the provisions of these byelaws, whenever there has been any false statement, or any misrepresentation of material fact, or concealment of facts in the application on which the building sanction was based, and the whole work executed on the basis of such sanction shall be treated as unauthorized. Further, any or all executed works in cases of deviation from the sanctio ned plan shall be treated as unauthorised construction and would lead to revocation of accorded sanction. (2) In the case of revocation of sanction during course of construction under above Bye - Law, no compensation/ damages shall be payable by the Competent Authority. (3) No such order of revocation shall be passed by the Competent Authority without giving a reasonable opportunity to the applicant of being heard. 12. VALIDITY PERIOD AND REVALIDATION PROCEDURE - (1) VALIDITY PERIOD : The sanction once gr anted shall be valid for a period of 2 years from the date of issue of sanction. The work shall be commenced within the period of 12 Months from the date of sanction and shall complete the same within the validity period of 2 years and if the building so s anctioned is not commenced/completed by the applicant within the period, it shall not thereafter be commenced or if commenced and not completed, shall not be continued unless the competent Authority on application made therefore has allowed an extension of that period as provided under section 243/244 of the Act. (2) REVALIDATION - The building sanction can be revalidated beyond the date of expiry of the original Sanction of Building plans on payment of the required revalidation fees as decided by the Board under provisions of the Act. Application for such revalidation shall be submitted on plain paper along with the following documents: (i) Original sanction plan (ii) Revalidation fees chargeable based on the decision and guidelines issued by Competent Authorit y from time to time. (iii) Documents in support of construction, if any, having been done within valid period of sanction. (iv) Certificate of supervision from Architect/Engineer/Supervising Engineer and the Applicant by submitting Form C, set forth in the Appendix t hat the construction will be carried out under his supervision according to the plans sanctioned by the Competent Authority. 13. NOTICE OF COMMENCEMENT - On issue of building sanction, the applicant and the registered Architect/s, Civil Engineer, Structural Engineer, Structural Design Agency, Construction Engineer, Construction Management Agency on Record before commencement of the work shall give a prior notice of 14 days to the Authority in prescribed Form D , set forth in the Appendix and the Authority will inspect the work following the receipt of the notice to verify the same. 14. DEVIATION DURING BUILDING CONSTRUCTION - (1) For any deviation from the sanctioned plan during any stage of construction, permission of the Authority shall be obtain ed if the construction is not according to the approved plan. (2) The Authority has the power to stop any construction if it is not as per the approved building plans and the permission holder shall have to comply with the directions served by the Authority. If the permission holder fails to comply with the notice served by the authority, the Authority is empowered to cancel the building permission and start proceeding against the permission holder as per provisions of Cantonments Act 2006 and as amended from time to time. (3) Any building or part thereof constructed unauthorizedly, with or without obtaining the sanction of building plan and / or Occupancy Certificate, can be regularized under the provisions of the Cantonments Act, 2006, if the same is within the ambit of the byelaws and payment of the requisite fees and charges. In case the unauthorized development is beyond the permissible/ compoundable limits of these byelaws, the Authority shall take suitable action as prescribed in Bye Laws No. 17 ( Offence and Penalties) below. (4) Neither granting of permission nor approval of the building plans, nor the inspection of the Authority during erection of the building, shall in any way relieve the owner of such building from full responsibility for carrying out the works in accordance with the building byelaws and in case of any violation, the owner shall be liable for action as per prevailing laws. 15. NOTICE OF COMPLETION AND COMPLETION -CUM -OCCUPANCY CERTIFICATE - (1) NOTICE OF COMPLETION - On completion of work, the applicant shall submit a Notice of Completion of the building as per Form E , set forth in the Appendix within a period of thirty days from the date of completion of work. (2) COMPLETION -CUM -OCCUPANCY CERTIFICATE - The Chief Executive Officer on receipt of the notice of completion shall inspect the work and issue a certificate of occupancy within the period stipulated in the Act, as per Form F , set forth in the Appendix, if the building has been constructed in conformity with sanction issued or may issue the same after levying and collecting compounding fee, if any. (3) Occupancy Certificate shall be mandatory for all buildings. No person shall occupy or allow any other person t o occupy any building or part of a building for any purpose unless such building has been granted an Occupancy Certificate by the Authority. (4) The functional / line agencies dealing with electric power, water supply etc. shall not give regular connections t o the building unless such Occupancy Certificate is produced. (5) Partial Occupancy Certificate may be issued upon request by the applicant and the registered architect / technical personnel provided that completed portion(s) of a part of the entire work may be occupied safely without endangering life or safety of the occupants. (6) The Authority issuing Occupancy Certificate before doing so shall ensure that wherever applicable, the following are complied with - (i) A certificate of Competent Authority or Lift Inspector / Lift Company has been procured and submitted by the owner, regarding satisfactory erection of lift. (ii) If any project consists of more than one detached or semi -detached building / buildings in a building unit and any building / buildings thereof is completed as per provisions of Building Bye -Laws (such as Parking, Common Plots, Internal roads, Height of the Building, Infrastructure facilities, lift and fire safety measures), the Authority may issue Occupancy Certificate for such one detached or se mi-detached building / buildings in a building unit. The Occupancy Certificate shall not be issued unless the information is supplied by the applicant and the supervising registered Architect / technical personnel concerned in the schedule as prescribed by the Competent Authority from time to time. 16. COMPOSITION OF UNAUTHORIZED CONSTRUCTION - (1) The Cantonment Board may calculate quantum of penalty / fees for regularization of unauthorized construction as per Schedule – I (2) Such composition of unauthorised construction shall be subject to the provisions of the Cantonments Act, 2006, the rules subsisting there under and other restrictions mentioned in these Bye -Laws including but not limited to FSI, Set -backs, and Ground Coverage . (3) In so for as constructions which are present and existing on the date of notifying of these Bye -Laws wherein such constructions are without sanction or in violation of approved plan including deviation, the applicants may apply to Cantonment Board for compounding, whic h at the discretion of the Cantonment Board or GOC -in-Chief, as applicable, may be allowed subject to payment of compounding fees as determined by Cantonment Board or GOC -in-Chief, as applicable. This exercise shall be undertaken subject to the Bye -laws fr amed hereunder after approval of Central Government. 17. OFFENCES AND PENALTIES - (1) Any person who violates the building permission sanction issued by the Authority or contravenes with the provisions of the bye -laws or who interferes or obstruct any auth orized personnel in the discharge of his duties shall be guilty of an offence. The Authority shall - (i) Take suitable action under the provisions of Cantonments Act 2006. (ii) Take suitable action as may deem fit which may include demolition of un- authorized works, sealing of premises/ building or any part thereof, filling, any mitigating measures such as disconnection of essential services, utilization of space for non -habitable purposes, dismantling of non -structural components of the floor / b uilding etc. or otherwise etc., prosecution and criminal proceeding against the offender in pursuance of relevant laws in force as decided by the Authority. (iii) Take suitable action against registered technical personnel and registration may be withdrawn in case of an offence as decided by the Authority. In case of Architect matter shall be taken up with the Council of Architecture. (iv) The Authority reserves the right to take action and to debar/blacklist the consultant/technical personnel, if found to have deviated from professional conduct or to have made any mis -statement or on the account of misrepresentation of any material fact or default either in authentication of a plan or in the supervision of the construction against the building byelaws a nd the sanctioned building plans. (v) If the Authority finds at any time any violation of the building byelaws or misrepresentation of fact, or construction at variance with the sanction or building byelaws, inclusive of the prescribed documents, the Authority shall be entitled to revoke the sanction and take appropriate action against such professional and such professional shall not be authorized or permitted to submit anymore fresh plans/ building proposals for any other applicant till finalization of the ca se. (vi) Before debarring or blacklisting a professional found to be indulging in professional misconduct or where he/she has misrepresented any material fact as per (iv) and (v) above, the Authority shall give him / her a show cause notice with personal hearin g, if desired and shall pass an order to debar him/her for submission and supervision of the construction with full justification for the same. An appeal against this order shall lie with the Appellate Authority . 18. UNSAFE BUILDING - Any building reported to be unsafe or damaged shall be examined by a Committee to be constituted under the provisions of the Act and shall make a written record of its finding. The Authority shall give notice to the owner or occupier to complete the specified repairs or improve ments or to demolish the building within a stated time. 19. BUILDING TO BE VACATED - (1) The Authority may on prima facie evidence of inspections/findings that structural elements in a building or building construction appears to be unsafe, may declare the building to be vacated until such records and evidences are produced by the applicant and his/her consultant engineer. The Authority shall keep a record of its findings in detail. 20. INSPECTION - (1) All development work for which permission is required s hall be subject to inspection by the Authority at the following stages of building construction - (i) On receipt of notice for commencement of building work, where alignment and setbacks of the building shall be given, confirmed and recorded. Any deviation thereafter shall solely be the responsibility and risk of the owner or authorized representative and the supervising consultant. (ii) On completion of work after receipt of completion certificate. (iii) Any other stages of construction, as desired by the applicant or authorized representative and the supervising consultant requiring the advice of the Authority after receipt of such notice. (iv) When the supervising consultant intimates to the Authority his/her disassociation in the supervision of the building c onstruction where the status of the building construction is recorded. No further construction will be permitted till appointment of a new supervising consultant. (2) It is incumbent and bounded, therefore for the supervising consultant to ensure that the buil ding construction shall be as per the following parameters - (i) All terms and conditions mentioned in the building permission sanction and/or approved building plans; and in particular, (ii) Setbacks for the building and septic tank are maintained as per approved building plans. (iii) Number of floors, closed and open projections and use of building are as per approved building plans. (iv) Parking spaces shall be provided and maintained as per approved building plans. (v) Provision of septic tank & soak pit, emergency ex it(s) are provided as per approved building plans. (vi) All structural members of the building shall be as per approved drawings. (vii) Safe and Sound Civil Engineering practices as per all the relevant I.S. Codes to be adopted. (3) Non-compliance on the part of the applicant and/or the registered architect/technical personnel to comply with the above provisions would result in the Authority declaring the building “Unauthorized Building” and necessary action against the offenders wil l be initiated by the Authority. (4) It is incumbent on the applicant and the registered architect/technical personnel to intimate to the Authority of the association of the consultants involved in the building construction and the substitutions thereof durin g the period of construction till its completion. CHAPTER II GENERAL BUILDING REQUIREMENTS 21. ZONING - (1) The Shillong Cantonment is divided into two broad zone namely :- (a) Zone I -The whole Notified Civil Area of Shillong Cantonment declared by the Central Government under sub -section (1) of section 46 of the Act and all privately held land comprising civilian habitation. This will be generally high density areas. (b) Zone II - All other land not included in Zone 1 but inclusive of all OGBs and leases situated outside civil area. This will be generally low density zone. 22. REQUIREMENT OF SITE - (1) No piece of land shall be used as a site for the construction of a building if the Competent Authority considers that i. The site is insanitary or is no t drained properly or is incapable of being well drained. ii. The site has no proper means of access. iii. The site is prone to land slide. Where the plot is located adjacent to water body (stream or river), the building regulations shall be governed additionally a s per the “Meghalaya Water bodies (Conservation & Protection) Amendment guidelines, 2023. 23. PROJECTIONS - (1) In addition to canopy, porch etc. the following projections in the upper floors of building shall be allowed: i. Closed projections which form part of a room(s). ii. Open projections for balconies which are open on the least two (2) sides. The permissible maximum projections are as per Table - 1 Table 1: Projections in mandatory Setbacks Setbacks (in meters) Closed projections (in meters) Open projections (in meters) 1.00 0.00 0.45 1.20 0.45 0.60 1.80 0.60 0.75 2.40 0.75 1.00 3.00 0.75 1.20 4.50 0.90 1.50 Note: i. Closed projections will be taken into PC & FSI calculations. ii. Open projections will be exempted from PC & FSI calculations. iii. Measurement of the closed & open projections shall be from the building line. iv. Open projections with walling on three sides shall be counted for PC & FSI calculations. v. Where the setbacks provided are more than the minimum prescribed, projections shall be allowed subject to architectural and structural designs. 24. MINIMUM PLOT SIZES - (1) For commercial: The minimum plot size shall be 50 Sq.mtr. (2) For Residential: The minimum plot size shall be 50 sq.mtr. 25. DISTANCE FROM ELECTRICITY LINES - (1) No verandah, balcony or the like shall be allowed to be erected or re -erected or new addition or alteration made to a building within a distance quoted in Table - 2 below in accordance with the current Indian Electricity Rules and its amendments from time to time. Table – 2: Distance from Electricity Lines Vertically Horizontally a) Low and Medium Voltage lines and services lines 2.5 meter 1.2. meter b) High voltage lines upto and including 33,000 V. 3.7 meter 2.0 meter c) Extra high voltage lines beyond 33.00 V 3.7. meter 2.0 meters (plus 0.3 meter for every additional 33KV or part thereof) 26. REQUIREMENT OF PARTS OF BUILDING - (1) Minimum size and width of different component of residential premises Table – 3: Requirement of Parts Of Building Sl. No. Component of Building Minimum requirements 1 Habitable Room Area 7.50 sq.mt. Width 2.10 mt. 2 Kitchen Area 3.30 sq.mt Width 1.50 mt 3 Bathroom Area 1.20 sq.mt Width 1.00 mt 4 W.C. Area 1.00 sq.mt. Width 0.90 mt. 5 Combined Bath & W.C. Area 2.80 sq.mt. Width 1.20 mt Table – 4 : Sizes and area requirement S. No. Type of room Maximum floor area Maximum height 1 Mezzanine floor Max. coverage of 1/3rd the covered area of that floor. 2.40m 2 Parapet 0.90m – 1.20m 3 Staircase a) Max. No. of steps in one single flight is 16, for residential bungalow (Max. ht. of riser = 15 - 17.5cm: Min. length of tread = 25 - 30cm) b). Dimension of riser & tread for all other types of buildings shall be 15cm & 30cm respectively 27. OTHER REQUIREMENT OF PARTS OF BUILDING - (1) Kitchen, Bathroom and Water closet - Every kitchen, bathroom and water closet shall : - i. be so planned that one of its wall shall open to external air by ventilator/exhaust fan etc.; ii. A flue, if found necessary for a kitchen and; iii. Refuse chute shall be constructed with the I.S. 6024 -1973 Code of practice. Provided that no ventilation shaft may be required for fully air -conditioned building, or mechanically ventilated toilet, kitchen, bath and water close t. 28. REQUIREMENTS OF SANITARY FITTINGS - (1) To ensure optimization of water the following measures shall be adopted in case of all new building sanction where plot size is more than 500 square meters on a case -to-case basis as decided by the Competent A uthority: i. Use of low dual flush capacity cisterns in water closets instead of the normal 12.5 liter capacity. ii. Use of waterless urinals in all public buildings. iii. Provision of storage and use of recycled water for toilet flushing where the minimum discharge in the building /complex is 10,000 liters per day or more. The sanitary fittings and installations for different occupancies shall be as per National Building Code amended time to time. 29. MEZZANINE FLOOR - (1) In case of a Mezzanine floor the following conditions shall be provided: - i. It is so constructed so as not to interfere under any circumstances with the ventilation of the space over and below it; ii. Such mezzanine floor is not sub -divided into small compartments in case of residen tial buildings; iii. Such mezzanine floor or any part of it shall not be used as a kitchen. 30. LOFT - (1) The maximum height of a loft shall be 1.5 meters and the loft may be provided over corridors and passageways only. (2) The clear head room under the loft shall not be less than 2.2 meters, (3) Loft when provided in a commercial building, shall be located 2.0 meters away from the entrance; 31. GARAGE - (1) Individual private garage: The size of a private garage in residential building shall be not less than 2.75 meters x 5.0 meters. The garage if located in the side, open space shall not be constructed within 1.5 meters from the main building. (2) Commercial / Public Garage: The size of a public garage shall be calculated based on the number of vehicles to be parked and the minimum parking space is as specified in bye laws. (3) Height: The maximum head room in a garage and parking area shall be 2.4 meters. (4) The plinth of a garage located at ground level shall not be less than 15 centimeters above the surrounding g round level. (5) The garage shall be set back behind the building line for the street/ road on to which plot abuts, and shall not be so located to affect the access ways to the building. 32. ROOF - (1) The roof of a building shall be so constructed or formed as to ensure effectual drainage of the rainwater therefrom by means of sufficient rain water pipes of adequate size, whenever required so arranged, joined and fixed as to ensure that the rain water is carried away from the building wi thout causing damage in any part of the walls or foundation of the said building or those of an adjacent building. (2) Rainwater from roofs and open areas on the plot shall be collected by suitable means to recharge pits and other devices. In this context ref erence may be made to Part 9 Plumbing Services Section 1: Water Supply, Drainage and Sanitation of the National Building Code of India as amended from time to time. (3) Rainwater pipes shall be affixed to the outside of the walls of the building or in recesses or chases out or formed in such walls or in such other manner as may be approved by the Competent Authority. (4) Terrace of buildings shall not be subdivided and it shall have a common access. 33. CHIMNEYS - (1) Chimneys, where provided shall conform to the requirements of I.S 1645 -1960 Indian Standards Code of practice for fire safety of building (General) chimneys, Flues, Flue pipes and Hearths. (2) The chimneys shall be built at least 0.9 meters above the top of the roof provided the top chimney shall not be below the tops of adjacent parapet wall. In the case of sloping roof, the chimney top shall not be less than 0.6 meters above the ridge of the roof in which the chimney penetrates. 34. CORNER SITE - When the site fronts on two streets, the frontage would be as on the street having the larger width. In cases where the two streets are of the same width, then the larger depth of the site will decide the frontage and open spaces. In such cases the location of a garage if provided within the open spaces shall be located diagonally opposite the point of intersections. 35. LIGHTING AND VENTILATION OF THE ROOMS - (1) The whole or part of one side of one or more rooms intended for human habitation and not abutting on either the front, rear or si de open spaces shall abut on an interior open space whose minimum width in all directions shall be 1.5 metres in case of buildings not more than 12.0 metres in height and subject to the provision of increasing the same with increasing height of 0.10 metres per every metre height or part thereof beyond 12.0 metres. However, in case of buildings already constructed with 12.0 metres the open space for new construction on upper floor, the open space on this basis shall be ensured and would remain as mandatory o pen space. (2) Where the lighting and ventilation requirements are not met through daylight and natural ventilation, the same shall be ensured through artificial lighting and mechanical ventilation as per part VIII Building Services Section 1 Lighting and Ventilation of National Building Code of India, 201 6 as amended from time to time published by the Indian Standard Institution. The latest version of the Nati onal Building Code of India, 2016 shall be considered at the time of enforcement of these Bye -Laws . (3) The minimum aggregate area of opening of habitable room excluding doors and fixed glazing but including the frame shall be not less than 1/8th of floor area of the room. (4) The minimum aggregate area of opening of kitchens excluding doors and fixed glazing but including the frame shall be not less than 1/8th of floor area of the kitchen. (5) No portion of a room shall be assumed to be lighted if it is more than 7.5 meters from the opening assumed for lighting of that portion of the room. (6) In lodges and hotels where attached toilets whose walls are not abutting on an external wall are provided, mechanical ventilation system should be installed as per the provisions of the part VIII of Nati onal Building Code of India, 201 6 as amended from time to time pub lished by the Indian Standard Institution. 36. PLINTH - The plinth of any part of a building shall be raised above ground level or road level, provided that adequate drainage of the site is assured, and shall not be at a height of less than 45 cm. 37. PROVISION OF LIFTS - (1) All the floors shall be accessible for 24 hrs by lift. Lift provided in buildings shall not be considered as means of escape in case of emergency. (2) Collapsible gates shall not be permitted for lifts and shall have solid doors with fire resistance of at least 1 hour. (3) The minimum lift dimensions shall be 1500 mm x 1500 mm. The minimum width of the door shall be 900 mm. 38. EXITS AND MEANS OF ACCESS - All exits and means of access shall be as per provisions of National Building Co de 20 16. Minimum width provisions for Stairways - The following minimum clear width provisions shall be made for each stairway/ passageway/corridors: Residential buildings Apartments --1.00 mt. Other buildings --1.25 mt 39. EXIT REQUIREMENTS - (1) General requirements - The following general requirements shall apply to exits - i. An exit may be a doorway, corridor, passageway(s) to an internal staircase, or external staircase, or to a verandah or terrace(s), which have access to the street, or to the roof of a building or a refuge area. An exit may also include a horizontal exit leading to an adjoining building at the same level; ii. Lifts and escalators shall not be considered as exits; iii. Every exit, exit access or exit discharge shall be c ontinuously maintained free of all obstructions or impediments to full use in the case of fire or other emergency; iv. Every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupants in case of fire or other emergency; v. No building shall be altered to reduce the number, width or protection of exits to less than that required; vi. All exits shall provide continuous means of egress to the exterior of a building or to an exterior open space leading to a street and; vii. Exits shall be so arranged that they shall be reached without passing through another occupied unit. (2) Types of Exits : - i. Exits shall be either of horizontal or vertical type. An exit may be doorway, corridor, and passageways to an internal staircase or external staircase, ramps or to a verandah and/or terraces which have access to the street or to roof of a building. ii. An exi t may also include a horizontal exit leading to an adjoining building at the same level. iii. Lifts, escalators and revolving doors shall not be considered as exits. (3) Number and Size of Exits - The requisite number and size of various exits shall be provided, based on the population in each room, area and floor based on the occupant load, capacity of exits, travel distance and height of buildings. i. Arrangement of Exits - Exits shall be so located that the travel distance on the floor shall not exceed 22.5 m. for residential, and 25 m. for mercantile, and other occupancies. Whenever more than one exit is required for a floor of a building, exits shall be placed as remote f rom each other as possible. All the exits shall be accessible from the entire floor area at all floor levels. The travel distance to an exit from the remote point shall not exceed half the distance as stated above except in the case of institutional occupa ncy wherein it shall not exceed 6.0 meters. ii. Occupant Load - The population in rooms and areas of floors shall be calculated based on the occupant load as provided in National Building Code and amended time to time. iii. Capacity of Exits - The capacity of exi ts (doors and stairways) indicating the number of persons that could be safely evacuated through a unit exit width of 0.5 meter shall be as per the National Building Code amended from time to time. (4) Provision for Staircase – All buildings having height more than ground floor shall have provision of staircase except in the case where the floors can be accessed from their respective ground levels through external steps. All buildings shall have staircase for fire escape staircase and shall be on external wall of buildings and shall open directly to the exterior, interior open space or to an open place of safety. Further, in case buildings with apart -mental occupancies, all units shall have access to a fire escape/emergency staircase. (5) DOORWAYS i. Every exit doorway shall open into an enclosed stairway, a horizontal exit, on corridor or passageway providing continuous and protected means of egress: ii. No exit doorway shall be less than 90 cm. in width in case of residential and 100 cm. in width in case of other buildings. Doorways shall be not less than 200 cm. in height. Doorways for bathrooms, water closet, stores etc. shall be not less than 75 cm. wide. iii. Exit doorways shall open outwards, that is, away from the room but shall not obstruct the travel a long any exit. No door, when opened, shall reduce the required width of stairway or landing to less than 0.90 metres. Overhead or sliding doors shall not be installed. iv. Exit door shall not open immediately upon a flight of stairs. A landing equal to at leas t the width of the door shall be provided in the stairway at each doorway. Level of landing shall be the same as that of the floor which it serves. v. Exit doorways shall be open -able from the Side which they serve without the use of a key. vi. Revolving doors sh all not be allowed. (6) STAIRWAYS i. Single staircase may be accepted for educational, commercial or residential building where floor area does not exceed 300 square metre and height of building does not exceed 11 metre to 14 metre and other requirements of occupant load, travel distance and width of staircase shall meet the requirement. The single staircase in such cases shall be on the outer wall of the building. ii. Internal stairs shall be constructed of non -combustible materials throughout; iii. Internal stairs shall be constructed as a self -contained unit. iv. The minimum width of an internal staircase shall be 1 metre subject to provisions of Table 9.0. Columns and other building features shall not reduce the width of the staircase. v. The minimum width of treads without nosing shall be 250 millimeters for an internal staircase for residential buildings. In the case of other buildings, the minimum tread shall be 300 millimeters. The treads shall be constructed and maintained in a manner to prevent slippi ng. vi. The maximum height of riser shall be 190 millimeter in the case of residential buildings and 150 millimeter in the case of other buildings, they shall be limited to 12 per flight. vii. Handrails shall be provided with a minimum height of 100 cm from the cen tre of the tread. Balusters / railing shall be provided such that the width of staircase does not reduce. viii. The minimum head room in a passage under the landing of a staircase shall be 2.2 meters. Beams and other building features shall not reduce the headro om of the staircase. ix. No living space, store or other fire exits shall open directly into the external staircase. x. The external exit door of the staircase enclosure at ground level shall open directly to the open spaces or should be reached without passing t hrough any door other than a door provided to from a draught lobby. xi. The main staircase and fire escape shall be continuous from ground floor to the terrace level. xii. No electrical shafts/AC ducts or gas pipe etc. shall pass through the staircase xiii. Lift shall no t open in staircase landing xiv. No combustible material shall be used for any surface decoration in the staircase. xv. A staircase shall not be arranged/built/constructed round a lift shaft. xvi. In case of single staircase, it shall terminate at ground floor level and access to the basement shall be by a separate staircase. However, second staircase may lead to basement levels provided the same is separate at ground level by either a ventilated lobby with discharge points at two different ends or through enclo sures. (7) Secondary/Emergency/Fire exit staircase(s) or external stairs The above staircase(s), when provided, shall comply the following: i. Fire escapes shall not be considered in calculating the evacuation time of a building. ii. All fire escapes shall be di rectly connected to the ground. iii. Entrance to fire escape shall be separate and remote from the internal staircase. iv. The route to fire escape shall be free of obstructions at all times, except a doorway leading to the fire escape shall have the required fire resistance. v. Fire escape shall be constructed of non -combustible materials. vi. Fire escapes stairs shall have straight flight not less than 1.2 meter wide with 280 millimeter treads and risers not more than 190 millimeters. The number of risers shall be limit ed to 16 per flight. vii. Handrails shall be of a height not less than 1000 mm and not exceeding 1200 mm. There shall be provisions of balusters with maximum gap of 150 mm. (8) Ramps i. Ramps with a slope of not more than 1 in 10 may be substituted for stairways and shall comply with all the applicable requirements regarding enclosure capacity and limiting dimensions. Ramps shall be surfaced with approved non - slipping materials. ii. Handrails shall be provided on both sides of the ramp; iii. Ramps shall lead directly to outside open space at ground level or courtyard or safe place. (9) Corridors and passageways i. The minimum width of a corridor shall not be less than 90 centimeters in the case of two storey row housing residential building. For all other buildings minimum width shall be 1.2 meter. ii. In case of more than one main staircase of the building interconnected by a corridor or other enclosed space there shall be at least one smoke stop door across the corridor or enclosed space between the doors in the enclosing walls of any two staircases. iii. Where stairways discharge through corridors & passageways the height of the corridors & passageways shall not be less than 2.40 mtr; iv. All means of exit including staircases, lifts, lobbies & corridors shall be adeq uately ventilated. (10) Spiral Staircase i. The use of spiral staircase shall be limited to low occupant load and building of 4 (four) storeys. ii. A spiral staircase of 1.20m - 1.50m in diameter and shall be designed to give the adequate headroom. iii. Where there are 2 or more dwelling units per floor, emergency staircase/exit has to be provided. (11) Refuge area i. An alternative to immediate evacuation of a building via staircases and/or lifts is required for the movement of differently -abled persons to areas of safety within a building. If possible, they could remain there until the fire is controlled and extinguished or until rescued by fire fighters. ii. A refuge area may be provided at the fire protected stair landing on each floor that can safely hold on e or two wheelchairs. iii. The area shall have doorways with clear opening width of 900 mm; and iv. The area shall have an alarm switch installed between 900 mm and 1200 mm from the floor level. v. Refuge area is mandatorily to be provided for the plot size of 1000 s q.mt and above. (12) Compound Gate - No compound gate(s) shall open towards the public property i.e. road/ footpath etc. 40. LOCATION AND SIZES OF SEPTIC TANKS / EFFLUENT TREATMENT PLANT - (1) No septic tank / ETP shall be located under a building/ room, unless the floor height is more than 1.20 meters. (2) Location of septic tank/ETP is permitted beneath a parking space and setback area. The minimum setback of a septic tank from the plot boundary is 1.0 m from all sides. However, wherever there is water body adjacent to the plot, the setback of the Septic Tank/ETP/STP shall be governed by the Meghalaya Water Bodies (Conservation & Protection) Amendment Guidelines, 2023 - 24. Table - 5: Sizes of Septic Tank No. of user Length (in M eter) Width (in Meter) Liquid depth (in Meter) 5 1.50 0.75 1.00 10 2.00 0.90 1.00 15 2.00 0.90 1.30 20 2.30 1.10 1.30 50 4.00 1.40 1.30 For Housing Colonies 100 8.00 2.60 1.00 150 10.60 2.70 1.00 200 12.40 3.10 1.00 300 14.60 3.90 1.00 Hostels, Boarding Schools 50 5.00 1.60 1.30 100 5.70 2.10 1.40 150 7.70 2.40 1.40 200 8.90 2.70 1.40 300 10.70 3.30 1.40 CHAPTER III STRUCTURAL SAFETY AND SERVICES 41. STRUCTURAL DESIGN - The structural design of foundation elements made of masonry, timber, plain concrete, reinforced concrete, pre -stressed concrete and structural steel, shall be carried out in accordance with Part -VI Structural Design, Section -1 Loads, S ection 2 - foundation, Section 3. Wood, Section 4 masonry, Section 5 - Concrete, Section 6 - Steel of Nati onal Building Code of India, 201 6 taking into consideration all relevant Indian Standards given below: (1) IS: 1893 (Part 1) -2002 “Criteria for earthquake Resistant design of Structures (Fifth Revision)” (2) IS:13920 -1993 “Ductile Detailing of Reinforced Concrete Structures subject to Seismic Forces - Code of Practice” November 1993 (3) IS: 13828 - 1993 “Improving Earthquake Resistance of Low Strength Masonry Buildings” August 1993. (4) IS:4326 -2013 “Earthquake Resistance Design and Construction of Buildings - Code of Practice (Second Revision)” (5) IS: 13827 -1993 “Improving Earthquake resistance of Earthen Building – Guidelines” October 1993 (6) IS: 13827 -2009 “Seismic Evaluation, Repair and Seismic Strengthening of Buildings - Guidelines” (7) For Protection of Landslide Hazard: i. IS 14458 (Part 1):1998 Guidelines for retaining wall for hill area: Part 1Selection of type of wall. ii. IS 14458 (Part 2): 1997 Guidelines for retaining wall for hill area: part 2 design of retaining/breast walls. iii. IS 14458 (Part 3): 1998 “Guidelines for retaining wall for hill area: Part 3 Construction of dry stone walls. iv. IS 14496 (Part 2): 1998 Guidelines for the preparation of landslide - Hazard zonation maps in mountainous terrains: Part 2 Macro -zonation. (8) Note: Whenever an Indian Standard or the National Building Code of India is referred, the latest provision in the standard should be adhered to. 42. SUPERVISION - (1) All construction shall be carried out under supervision of the Architect on Record (AR), Construction Engineer on Record (CER) or Construction Management Agency on Record (CMAR) as per the Table below - TABLE - 6: Supervision Sl. No. Type of Structures Supervisor 1 All buildings having covered area above 500 square metres. (i) AR & CER or (ii) CMAR 2 All buildings having a covered area of up to 500 square metres (i) AR & CER or (ii) CMAR 3 All buildings having a covered area up to 250 square metres (i) AR & CER or (ii) CER 4 Buildings having total floor area of up to 500 square metres (i) AR & CER or (ii) CER 5 Buildings up to G + 2 Floors having total floor area of upto 400 square metres (i) AR & CER or (ii) CER 6 Buildings up to G + 1 Floors having total floor area of up to 200 square metres (i) AR & CER or (ii) Diploma in Architecture & CER or; (iii) CER 43. MATERIAL AND CONSTRUCTION METHODS - Quality of Materials and Workmanship (1) All materials and workmanship shall be of good quality conforming generally to accepted standards of Meghalaya Public Works Department , Indian standard Specifications and Code as included in Part V Building Materials and Part VII Constructional Practices and Safety of National Building Code of India. (2) All burrow pits dug in the cour se of construction and repair of buildings, roads, embankment and the like shall be deep and connected with each other in the formation of a drain directed towards the lowest level and properly sloped for discharge into a river, stream, channel or drain an d no person shall create any isolated burrow pit which is likely to cause accumulation of water which shall breed mosquitoes 44. NEW MATERIALS AND DESIGN METHODS - (1) The provisions of these Bye -Laws are not intended to prevent the use of any material or method of design or construction not specifically prescribed by Bye - Laws no. 43 provided any such alternative has been approved by BIS or any other statutory body. (2) Such alternatives may be approved provided that it is found that the proposed alternative is satisfactory and conforms to the provisions of relevant parts regarding material, design and construction and that material, method, or work offered is for the purpose intended, at least equivalent to that prescribed, in the Bye -Laws in qual ity, strength, compatibility, effectiveness, fire and water resistance, durability and safety. 45. ELECTRICAL SERVICES - The planning, design and installation of electrical installation, air conditioning installation and installation of lifts and escalator s shall be carried out in accordance with Part VIII Building Services, Section -2 Electrical installations, Section -3 Air-conditioning and Heating, Section -5 Installation of lifts and escalators of the National Building Code of India . 46. LIGHTENING PROTECT ION OF BUILDING -The lightning protection for building shall be provided based on the provisions of Part III of the National Building Code of India. 47. PLUMBING SERVICES - The planning, design, construction and installation of water supply, drainage and sanitation and gas supply systems shall be in accordance with Part IX Plumbing Services, Section - 1 Water Supply, Section 2 Drainage and Sanitation, Section - 3 Gas Supply of the National Building Code of India . 48. FIRE SAFETY DETECTION AND EXTINGUISHIN G SYSTEM - Fire protection and extinguishing system shall conform to accepted standards and shall be installed as recommended in the National Building Code of India and to the satisfaction of Directorate of Fire and Emergency Services. CHAPTER IV MINIM UM SETBACKS, PARKING SPACES & HEIGHT STIPULATION FOR ALL TYPES OF BUILDINGS 49. PARKING SPACE - (1) No off -street parking space shall be less than 2.50 m in width and 5.00m in length, with a minimum head room of 2.4 m measured at the bottom of beam, if parked in a covered area. (2) The minimum width of circulation driveway to be provided for adequate maneuvering of vehicles shall be 3.0m for cars and 5.00 m for trucks exclusive of parking space referred to in (a) above. However, a projection from a height a bove 5.50 m from the ground level may be permitted keeping the mandatory open space open to sky (3) Minimum gradient for a driveway ramp shall be 1:10 or as per N ational Building Code. (4) The parking requirements shall comply as given in these byelaws. The location of parking spaces shall be well ventilated. Parking will be permitted at any / all of the following: i. Basement/Lower Ground Floor. ii. Ground Floor or at any floor (s) (5) For building with different uses, the area of parking space shall be worked out on the basis of respective uses separately and parking space to be provided for the total number of vehicles thus required. (6) In case of a plot containing more than one building, parking requirement for all buildings shall be calculated on the ba sis of consideration of the area of respective uses. (7) The Parking spaces shall be located beyond the mandatory setback spaces (open or covered) as provided in these Bye -Laws and read with bye law 2.17(b )(v) Parking can be at any floor(s) if not met within t he plot area and shall be exempt from FSI calculations. The approved parking and circulation spaces shall not be converted to any other use (habitable or non -habitable), space for generator sets, sentry sheds etc. (8) For horizontal or vertical building exte nsion proposals, in addition to conformity of all the relevant byelaws, the parking requirements of the extension will have to be met. (9) The Minimum Parking Spaces shall be as shown in Table below. Table - 7: Minimum Parking Spaces Sl. No. Occupancy One parking Space for every (a) (b) (c) 1 Residential, Commercial and Residential cum Commercial 100 sq.m. of floor area. 2 Educational 100 sq.m. floor area 3 Public and semi -public, private business buildings etc. 75 sq.m. floor area. 4 Commercial (markets, departmental stores, shops and other commercial users) 75 sq.m. floor area. (10) Parking Space - The area of each ECS shall be as follows: Table - 7A: Parking Space S. No. Parking Category Area in sq mt 1 Open Parking 23.00 2 Stilt Parking 28.00 3 Basement Parking 32.00 50. FLOOR SPACE INDEX AND PLOT COVERAGE - (1) Permissible FSI, Building Height, Number of Floor and Plot Coverage for Zone –I shall be as per Table below: Table - 8: Zone I Sl. No . Type of Occupancy Maxi mum Permi ssible F.S.I. Maxi mum Permi ssible Plot Cover age Maximum No. of Permissible Floors (Inclusive of Stilt parking/ Basement/Lo wer Ground Floor/Underg round Floor/Cellar) Maximum No. of Permissible Floors (Inclusive of Basement/Lo wer Ground Floor/Underg round Floor/Cellar) Maximum Building Height in Metres (Inclusive of Stilt parking/ Basement/Lo wer Ground Floor/Underg round Floor/Cellar/ Mezzanine Floor/Service Floor) Maximum Building Height in Metres (Inclusive of Basemen t/L ower Ground Floor/Under ground Floor/Cellar/ Mezzanine Floor/Servic e Floor) Motorable Plots Non Motorable Plots Motorable Plots Non Motorable Plots 1 2 3 4 5 6 7 8 1 a) Special small Residential Plot [up to 100 Sq.m ] (Motorable) 1.75 50% 4 14 b) Special small Residential Plot [up to 100 Sq.m ] (Non Motorable) 1.5 50% - 3 - 10 2 a) Residential, Commercial and Residential cum Commercial [above 100 Sq.m] (Motorable) 1.75 50% 4 - 14 - b) Residential, Commercial and Residential cum Commercial [above 100 Sq.m] (Non Motorable) 1.50 50% - 3 - 11 3 Institutional 1.50 40% 4 - 14 - 4 Public & Semi Public Building 1.75 50% 4 - 14 - (2) Permissible FSI, Building Height, Number of Floor and Plot Coverage for Zone –II (Bungalow Area) shall be as per Table below: Table - 9: Zone II Sl. No. Type of Occupancy Maxi mum Permi ssible F.S.I. Maximu m Permissi ble Plot Coverage Maximum No. of Permissible Floors (Inclusive of Basement Floor/ Lower Ground Floor/ Underground Floor/ Cellar). Maximum Building Height in Metres (Inclusive of Basement/Lower Ground Floor/Underground Floor/Cellar/Mezzanine Floor/Service Floor) Motora ble Plots and Non Motorable Plots 1 2 3 4 5 6 1 Residential, Commercial , Residential cum Commercial 0.50 50% 3 11 4 Institutional 0.50 40% 3 11 5 Public & Semi -Public Building 0.50 50% 3 11 Note: - (i) Number of Basement Floor in Zone –II (Bungalow Area) shall be restricted to 1 (one) only and shall be used only for parking, storage and housing service. Basements in no case be used for residential purpose. Non-FSI spaces: i. Mumty (Stair cover) over staircase on top floor, ducts / cut -outs, machine room for lift on top floor as required for the lift machine room installation shall not be taken for FSI calculations. ii. Area under emergency / secondary / fire exit staircases shall not be taken for FSI calculations. iii. Only one floor of the area under primary staircases/ escalators / lifts / atrium shall be accounted for calculations of FSI. iv. Area under lift shaft(s)/ escalators shall not be taken for FSI calculations. v. Area used for Sentry sheds and transformer / sub - stations shall not be taken for FSI calculations. vi. Access to the basement / lower ground floor / cellar / underground floor, if uncovered shall not be taken for FSI calculations. vii. Rockery, well and well structures, plant, nursery, water -pool, swimming pool (if uncovered), platform around a tree, water tank, fountain, bench, ramps, compound wall, gate, slide, steps outside building, domestic washing place, swing, overhead water tank on top of buildings, underground suction tank having roof slab 0.50m above ground level, cooling tower of A.C. plant resting above the top roof slab and drainage culvert, conduit, catch -pit, chamber, gutter, culvert on drains shall not be taken for FSI calculations. viii. Open projections such as balconies, chajjas, canopy, porch, verandahs, and architectural features serving no other function except that of decorations shall not be taken for FSI calculations. ix. The use of Stilt (if any)/Ground Floor/Basement / Lower Ground floor / Cellar / underground floor from 2.17(a ) and 2.17( b)(i) to (v ) shall not be reckoned for the purpose of FSI. x. Roof top machineries/towers shall not be taken for FSI calculations. xi. Open to sky swimming pool & shower/changing rooms shall not to be taken for FSI calculations. (a) Parking Spaces. (b) Residual Floor. 51. TENEMENT DENSITY: No independent dwelling unit of less than 75 sq. mtr. can be constructed if the plot size is more than 500 sq. mtr. 52. OPEN SPACES/SET BACKS: (1) The exterior open spaces shall be governed by the following minimum clear open space and setbacks: - i. Front setback (a) Every building abutting a street / footpath shall have a front setback as prescribed in these byelaws. (b) Where a building is abutting a non -motorable footpath/street/lane, but has the feasibility for ro ad widening in future, setback shall be 3.00 metre from such footpath/street/lane. (c) If a building abuts on two or more streets of different widths, the building shall be deemed to face upon the street that has the greater width. (d) No staircase or ramp shall start from the edge to the front setback. ii. Side and Rear setback (a) Every building shall have a minimum clear side and rear setbacks as prescribed in these byelaws. Where the sides/rear setbacks are more than 2.50 m for buildings upto 4 storeys and the sides/rear setbacks are not facing a road/street/motorable footpath, pa rking spaces for vehicles shall be permitted. (b) Where the plot is located adjacent to a water body (stream or river), the building regulations shall be governed additionally as per the Meghalaya Water Bodies (Conservation & Protection) Amendment Guidelines, 2023. The minimum setbacks shall be as per the table below: Table – 10: Minimum Setbacks for Motorable Plots for Zone 1 and Zone 2 Plot size (in Sq m.) Minimum Front Setback (in Mts.) Abutting Road width Minimum Setbacks for other sides (In Mtrs) Non- motorable Footpath Single Lane/ motorable Footpath Double Lane Four Lane Six Lane Rear Side Other sides 1 2 3 4 5 6 7 8 Up to 100 1.80 2.10 NA NA NA 1.00 1.00 Above 100 & up to 200 1.80 3.00 3.00 4.60 4.50 1.80 1.00/1.00 Above 200 & width < 10m 2.40 3.00 3.00 4.50 4.50 1.80 1.20/1.20 Above 200 & up to 500 3.00 3.00 3.00 6.00 9.00 2.10 1.80/1.80 Above 500 & up to 750 3.00 3.00 3.00 6.00 9.00 2.40 2.10/1.80 Above 750 & up to 3.00 4.00 4.00 6.00 9.00 3.00 3.00/2.40 Above 2000 & up to 3.00 4.50 5.0 0 6.00 9.00 3.00 4.50/3.00 Above 3500 & up to 5000 3.00 6.00 6.00 6.00 9.00 6.00 5.00/5.00 Above 5000 6.00 6.00 6.00 6.00 9.00 6.00 6.00/6.00 General Notes : - Note 1: -For plots of land, whether having motorable or non -motorable access, with plot width less than 7m, the maximum number of floors permissible shall be limited to 3 (three) only in Zone I and 2 (two) only in Zone II. Note 2: -Considering specific local site conditions, topography of the land, extent and type of development, building height and number of floors, etc., transfer of setback from one side to another can be permitted by the Authority and the reasons thereof shall be recorded. Note 3: -Considering th e irregular plot shapes and sizes, slope profile, local topography of building sites, etc., on a case to case basis, where reduced setbacks proposal is received from an applicant, such proposal may be considered only when (i) there is neighbours NOC duly signed and witnessed (ii) the Plot coverage and FSI should not exceed the permissible limits and (iii) subject to structural design which shall not affect the structural stability of the proposed structure/building and the neighbouring structure(s)/buildin g(s). (2) Existing And Under Construction Buildings For buildings (existing or under construction) granted permission under the previous Bye-laws, the following conditions shall be mandatorily complied with: i. For the proposed construction: (a) The setbacks, number of floors, building height conditions and exemptions of these bye -laws shall apply; (b) Plot coverage shall be as per provisions of these Bye -laws; (c) FSI shall be limited to as per provisions of these bye -laws; (d) Lift to be provided as per provisi ons of these bye -laws; (e) Emergency/secondary staircase to be provided within the building bye - laws envelop and shall not be allowed in the mandatory setbacks as per provisions of theses bye -laws; (f) Parking space requirements as per provisions of these bye -laws; ii. For alteration, change of use, etc. the provisions mentioned at (i) above shall not be applicable. 53. FIRE & LIFE SAFETY - (1) Reasonable safety measures and provisions for fire and life safe ty as per Part IV of the NBC 201 6 and as per recommendation of the Fire & Emergency Services Department, Government of Meghalaya shall apply to the following: - i. Mixed occupancies, where any of these buildings have covered area more than 500 sq.m; ii. educational/institutional/public & semi -public buildin gs having 9 metre height or more with covered area more than 500 sq. m; iii. buildings with basements/lower ground floor/ Cellar/underground floor with covered area more than 500 sq.m. CHAPTER V FACILITIES IN THE PUBLIC BUILDING FOR THE DIFFERENTLY -ABLED PERSONS: 54. APPLICABILITY - (1) These provisions are applicable to all buildings, recreation areas and facilities used by public. It does not apply to private domestic residences. i. Site planning - Level of the roads, access paths and park ing areas shall be described in the plan along with specification of materials. Every building should have at least one access to main entrance/exit to the differently abled which shall be indicated by proper signage. This entrance shall be approached through a ramp together with stepped entry. The ramp should have a landing after every 9.0 meter run and in front of the doorway. Minimum size of landing shall be 1.0 meter x 2.0 meter. ii. Access path/walk way - Access path from plot entry and surface parking to building entrance shall be minimum of 1.8 meter -wide having even surface without any step. Slope, if any shall not have gradient greater than 5 %. Selection of floor material shall be made suitably to attract or to guide visually impaired persons (limited to floor material) whose color texture is conspicuously different from that of the surrounding floor material or the material that emit different sound to guide visually impaired persons. Finishes shall have a non -slip surface with texture traversable by a wheel chair. Curbs wherever provided should blend to common level. 55. PARKING – (1) For parking of vehicles, the following provisions shall be made: i. Surface parking for two car spaces shall be provided near entrance for the persons with disabilities with maximum travel distance of 30m from building entrance. ii. The width of parking shall be a minimum of 3.60m. iii. The information stating that the space is reserved for wheel chair users shall be conspicuously displayed. iv. Guiding floor materials shall be provided for a device, which guides visually impaired persons with audible signals, or other devices, which served the same purpose, shall be provided. 56. BUILDING REQUIREMENTS – (1) The specified facilities for the building for persons with disabilities shall be as follows : - i. Approach to plinth level. ii. Corridor connecting the entrance/exit for the handicapped. iii. Stairways. iv. Lift. v. Toilet. vi. Drinking water. vii. Braille signage shall be provided at the above specified facilities. 57. APPROA CHES TO PLINTH LEVEL - (1) Ramp shall be provided with non -slip material to enter the building, minimum clear width of ramp shall be 1.8 meter with maximum gradient 1:12, between top and bottom of the ramp. Length of ramp shall not exceed 9.0 meters having 0.7 meter -high handrail on both sides extending 300 millimeters beyond the ramp. Minimum gap from the adjacent wall to the handrail shall be 50 millimeters. (2) Minimum clear opening for the entrance door shall be 0.5 meter. Threshold shall not be raised more than 12 millimeters. (3) For stepped approach, size of tread shall not be less that 300 millimeter and maximum riser shall be 150 millimeters. Provision of 0.8 meter -high handrails on both sides of the stepped approach similar to the ramped ap proach shall be made. 58. CORRIDOR CONNECTING THE ENTRANCE/EXIT FOR THE DIFFERENTLY - ABLED – (1) The corridor connecting the entrance/exit for differently -abled leading directly outdoors to a place where information concerning the overall use of the specified building can be provided to visually impaired person either by a person or by signs, shall be provided as follows: i. Guiding floor materials shall be provided or devices that emit sound to guide visually impaired persons. ii. The minimum width shall be 900 mm. iii. In case there is a difference in level, slope ways shall be provided with a slope of 1:10. iv. Handrails shall be provided for ramps/slope ways. 59. LIFTS – (1) Wherever lift is necessary, provisions of at least one lift shall be made for the wheel chair user with the following car dimensions of lift recommended for passenger lift for 13 persons’ capacity by Bureau of Indian Standards. i. Clear internal width minimum of 1.90 metre. ii. A Handrail not less than 0.60 metre -long at 0.90 – 1.00 metre a bove floor level shall be fixed adjacent to the control panel. iii. The lift lobby shall be of an insi de measurement of 1.50 metre X 1.50 metre or more iv. The Braille signage will be posted outside the lifts. v. Operational details of lifts shall conform to the National Building Code of India and will be the responsibility of designer as well as manufacturer. 60. ACCESS TO TOILET FACILITY :- (1) Unisex Accessible Toilets (multi -use) - Unisex accessible toilet allows Persons with Disabilities to be assisted by ca rers of the same or opposite gender. In all public buildings, one unisex accessible toilet should be provided in each toilet block. Apart from this all toilet blocks must have one cubicle suitable for use by persons with ambulatory disabilities. The unisex toilet should have :- i. The layout of the fixtures in the toilet should be such that there is a clear maneuvering space of 1800 mm x 1800 mm in front of the water closet and wash basin in the accessible toilet unit (Figure 1); ii. Minimum internal dimensions of 2200 mm x 2000 mm minimum (Figure 2); iii. All fixtures and utilities should provide a clear space of 900 mm x 1200 mm for wheelchair users to access them; iv. Have clear space of not less than 900 mm wide next to the water closet; Figure 1: Wheelc hair manoeuvring space in toilet Figure 2: Suggested Plan WC Compartment for the Ambulant Disabled 61. TOILET CUBICLE FOR WHEELCHAIR USERS - (1) Where a toilet cubicle for the wheelchair user is provided, it should conform to the dimensions as given in figure 1. (2) Toilet cubicle for Ambulatory Disabled. (3) In a set of toilets (for ladies or for gents), there shall be one WC for the use of the ambulant disabled persons as per Figure 3 -1 and 3 -2. (4) Toilet Doors: The toilet door should be either an outward opening door or two -way opening door or a sliding type and should provide a clear opening width of at least 900mm. Figure 3 -1: WC Compartment for the Ambulant Disabled Figure 3 -2: WC Compartment for the Ambulant Disabled 62. WATER CLOSET - (1) Be located between 460mm to 480mm from the centerline of the water closet to the adjacent wall; (2) It should have a clear dimension of 750 mm from the front edge of the water closet to the rear wal l to facilitate side transfer; (3) The top of the water closet seat should be 450 to 480mm from the floor as shown in the figure 2; when the water closet does not have the required height, the necessary height may be obtained by providing a circular base under the water closet. The base so provided must not protrude beyond the circumference of the base of the water closet; (4) There should be an adequate clear floor space of at least 1350mm depth and 900mm width, both in front and on the transfer side, adjac ent to the water closet; (5) Have a suitable back support to reduce the chance of imbalance or injury caused by leaning against exposed valves or pipes; (6) Where more than one accessible toilet is provided, a left -hand and right -hand transfer option should be made available. (7) Water Closet Grab Bars i. Water closets should be provided with grab bars, be mounted at a height between 200mm and 250mm from the water closet seat; ii. One L -shape grab bar: 600mm long horizontal and 700mm long vertical should be mounted on the side wall closest to the water closet (Figure 4); iii. A hinged type horizontal grab bar should be installed adjacent to the water closet; at a distance of 320mm from the centre -line of the WC, between heights of 200mm - 250mm from the top of the water closet seat and extending 100mm to 150mm beyond the front of the water closet. iv. An emergency alarm cum call switch should be provided within easy reach on the wall near water closet at two levels: at 300mm and 900mm from the floor level to allow user to call for help in case of an emergency. Figure 4: Grab bars specifications 63. WASHROOM ACCESSORIES - (1) Washroom accessories should comprise the following: i. A mirror installed in a way to have the bottom edge at a height of not more than 1000mm from the floor and mirror should be tilted at an angle of 300 for better visibility of wheelchair user ii. Accessories should be placed in close proximity to the basin, to avoid a person with wet hands wheeling a chair. (2) Additional Considerations i. There should be adequate colour and tonal contrast between the fixtures, walls and the flooring. This is to enable easy recognition by persons with visual impairments. ii. There should be a visual emergency alarm in the toilet. 64. URINALS - (1) At least one of the urinals in the Gents toilets on each floor should have grab bars; installed on each side and in the front of the urinal to support ambulant Persons with Disabilities (for example, crutch users). (2) The front bar is to provide chest support; the sidebars are for the user to hold on to while standing. (3) Urinals shall be stall -type or wall -hung, with an elongated rim at a maximum of 430 mm above the finish floor. (4) Urinal with chest support grab bar (5) A clear floor space 760m m by 1220mm should be provided in front of urinals to allow forward approach. Urinal shields (that do not extend beyond the front edge of the urinal rim) may be provided with 735mm clearance between them (6) Flush controls should: be located not more than 120 0mm from the floor. (7) Where urinals for the ambulatory disabled are provided, they should comply with the following as illustrated in the figure E6 -6. CHAPTER VI GREEN BUILDINGS & SUSTAINABILITY PROVISIONS 65. ENERGY CONSERVATION MEASURES: (1) Use of Compact Florescent Lamps and Electric Chokes: i. The use of incandescent lamps and conventional chokes in all new buildings, institutions constructed in Government sector, Government Aided sector, Boards and Corporations and Autonomous bodies is banned. ii. It will be ma ndatory that in these existing buildings the defective incandescent lamps and chokes when replaced would be replaced by only compact fluorescent lamps (CFL), LED and electronic chokes. iii. The Competent Authority will effect necessary modification in the local demand to promote the use of Compact Fluorescent Lamps, LED and electronic chokes instead of conventional bulbs and chokes while releasing/sanctioning new connections/loads in such buildings. (2) All new cases may consider the following provisions of solar water heating systems for energy conservation: i. An open space in the roof which receives direct sunshine; the roof shall have a load bearing capacity of at least 1000 kg. Per square meter. ii. The building must have a provision for continuous water supply to the solar water heating system. iii. The building design should provide for an insulated pipeline from the heating system to all distribution points where hot water is required. iv. The recommended minimum capacity of installation shall not be less than 2 00 litres per day for each bathroom and kitchen subject to the maximum of 15% of the total roof area is utilized by the system. v. Installation of Solar Assisted Water Heating Systems shall confirm to BIS specification IS 12933. The solar collectors used in t he system shall have the BIS certification mark. (3) Whenever hot water requirement is continuous, auxiliary arrangement either with electrical elements or oil -based systems of adequate capacity may be provided. (4) No new building in the following categories shall be sanctioned unless this installation has solar assisted water heating system: i. Industries which use hot water for processing; ii. All hospitals and nursing homes; iii. All hostels, hotels, motels, guest houses and banquet halls; iv. Large canteens i.e . which serve more than 50 persons in a day. v. Office building on a plot area of 200 square metre or above. vi. Residential buildings on a plot area of 500 square metre or above. vii. Residential schools and colleges; (5) Off Grid Roof Top Solar Power Plant at New Buildings - All buildings on plot size 500 square meter or more, which are proposed to be constructed afresh, shall install Rooftop Solar Power installation, adequate capacity, as per norms and parameters fixed by Ministry of New and Renewable Energy or it s subordinate organizations, time to time. 66. LANDSCAPING - (1) Institutional, Industrial, Commercial and Group Housing Complexes shall be required to plant a minimum number of trees as per Table below: - Table - 11· Number of trees to be planted Sl. No Plot Area (in Square metre) No of trees required 1 Up to 2000 One tree per 80 square metre of open space out of which minimum 50% trees to be in the category of evergreen trees having height of 6.0 metres or more. 2 From 2001 to 12000 One tree per 80 square meter of open space out of which minimum 50% trees to be i n the category of evergreen trees, having height of 9.0 metres or more. 3 More than 12000 One tree per 80 square metres of open space, out of which a minimum of 50% shall be evergreen trees having a height of 12.0 metres or more. (2) A detailed landscaping plan will have to be got approved from the Competent Authority with specifications. (3) Norms for planting in all plots for residential, residential cum commercial shall be as follows: (a) Minimum of three trees in every plot for plot size above 200 square meter. (b) Selected trees should be more than 3 meter in height and be suitable for local climate. 67. REQUIREMENTS OF WATER SUPPLY IN BUILDING - (1) The total requirements of water supply shall be calculated based on the Building Occupancy as follows and as per national building code amended time to time. i. Residential Building: Five persons per tenement. ii. Other buildings: No. of persons based on occupant block and floor area. (2) Storage of Water: Minimum provision should be made for storage of water to meet the daily requirements of the individuals using the building as follows: Table - 12: Minimum Domestic storages activities S. No. No. of Floors Storage Capacity For premises occupied as tenements with common convenience 1 Floor 1 Nil, provided no down take fittings are attached 2 Floor 2 and above 500 litres per tenement For premises occupied as flats or blocks 3 Floor 1 Nil, provided no down take fittings are attached 4 Floor 2 and above 500 litres per tenement Note: 1. If the premises are situated at a place higher than road level in front of the premises, storage at ground level shall be provided as on upper floors 2. The above storage may be sanctioned to be installed provided that the total domestic stora ge calculated on the above basis is not less than the storage calculated on the number of down -take fitting according to the scale given below Down -take taps: 70 liter each Showers: 135 liter each Bathtubs: 100 liter each 68. RAIN WATER HARVESTING AND GROUND WATER REGULATIONS - (1) Water harvesting through storage of water runoff including rain water in all building on plots of 200.00 square metre and above will be mandatory. (2) Adoption of rooftop rain water harvesting system is mandatory for all residential/ educational/ institutional/ hotel building/ industrial and commercial establishments, which have plot size more than 500 Square meter and more. (3) The plans submitted shall in dicate the system of storm water drainage along with points of collection of rainwater in surface reservoirs or in recharge wells. These provisions will be applicable as per the Public Notice (s) of Central Ground Water Authority issued from time to time. (4) Undertaking of any operations connected with drilling, cleaning, construction or rehabilitation of ground water abstraction structures and related works including installation of pumps cannot be taken up without prior permission of the Cantonment Board. (5) Drilling contractors or Agencies/Plot occupiers and required to take prior permission for works connected with drilling, cleaning, boring and installation of pumps. (6) The authority shall ensure that no drilling activity is undertaken wit hout prior approval and is authorized to take action against offenders by seizing of drilling rig, sealing of tube well and disconnection of electric supply to the energized tube well. Note: Digging and use of Bore well shall be governed as per the Shillong Cantonment Board (Digging and use of Bore wells) Regulations 2024, published in the Gazette of India, Extra Ordinary Dt. 09 August, 2024. 69. INCENTIVES FOR OWNERS LEAVING MORE SETBACKS/R AIN WATER HARVESTING/RECYCLING OF WASTE WATER - The following incentives in terms of rebate in building permission fees will be given by the Authority for owners or their successors -in-interest who: (1) Construct the building /blocks by leaving more setbacks t han the minimal stipulated in these bye -laws: Leaving 1.5 times or more the minimum setbacks in all sides - 10 % rebate on building permission fees will be allowed provided the setbacks has to be on all sides to qualify for the rebate. Leaving more on one side and the minimum on other sides would not qualify for such rebate. (2) Undertake both recycling of waste water and rain water harvesting structures: 10 % rebate of building permission fees. (3) Incentive in development charges if Rooftop Solar Installati on and Rain Water Harvesting is proposed and implemented: For construction of residential or commercial or any building less than 500 sqmt., if the applicant opts for Rooftop Solar Installation and / or Rain Water Harvesting, he/she shall be eligible for r efunding of development charges after the completion of said Rooftop solar installation and / or Rain Water Harvesting facility and submission of photographs to this effect. The quantum of incentive for different categories of buildings shall be decided by the Board by resolution. (4) HOR/ Lessee / Successor of the Property holder(s) will be allowed additional FSI over and above the maximum permissible limit on parting a portion of land (duly reclassified the parted land under the provisions of CLAR 2021) for the purpose of road widening free of cost and subject to structural safety & sufficiency of the building. The additional FSI shall be proportionate to the land parted with. (5) Where HOR/ Lessee / Successor of the Property holder(s) provide at least 25% additional parking space over and above the minimum they would be allowed for a rebate of 10 % in building permission fees. (6) Energy Conservation Building: Building or building complexes having a connected load of 100 KW or more will be regulated as per the Energy Conservation Code 2017 for commercial buildings. CHAPTER VII MISCELLANEOUS PROVISIONS 70. PENALTIES TO BE LEVIED F OR VIOLATIONS OF PROVISIONS OF BYE -LAWS.: (1) All the provisions of these Bye -laws except those given below shall not be compounded / regularized and shall have to be rectified by alteration/demolition at the risk and cost of owner/HOR. Compoundable Items: (i) Coverage - Maximum of 5%. For Projects of the Government, additional relaxation shall be given up to a limit as approved by the competent authority. (ii) FSI - Maximum of 10% (iii) Unauthorized construction, if the same is within the norms of Building Bye -laws subject to satisfaction of the Authority. Non-compoundable Items: (i) Parking norms (ii) Projection/ encroachment of public land. (2) Compoundable Items If a building or any part thereof has been constructed unauthorisedly i.e. without obtaining the required building permission from the Authority as required by Building Bye-laws the same shall be compounded at the following rates provided the construction conforms to the provisions of Building Bye -laws. For th is, applicant shall have to submit the request for permission in the prescribed procedure as per bye -laws. (3) Rates for compounding shall be as given in the Schedule -I Note: The Authority may however refuse regularisation of construction even with penalties a s specified in the above provisions if in the opinion of the Authority this may infringe public safety and general environment of adjoining area. SCHEDULE – I Sl. No. Type of compoundable Item Rate of Compounding 1 Coverage The rate for every unit area under compoundable coverage & FAR shall be (i) 5(Five) times the plinth area rate of Meghalaya PWD Schedule of Rates prevailing at the time of compounding in the case of commercial buildings. (ii) 2.5 (Two point five) times the plinth area rate of Meg halaya PWD Schedule of Rates prevailing at the time of compounding in the case of other buildings. 2 FSI 3 Unauthorized construction, if it is within the norms of Building Bye-laws subject to satisfaction of the Authority. The rate for every unit area under compoundable unauthorized construction shall be 5(five) times the rate of building permission fees as applicable. 71. APPLICABILITY OF THE BYE LAWS TO THE EXISTING BUILDING - (1) The provisions of these bye -laws shall not apply to the existing buildings. However, in case of any addition, alteration, erection or re -erection in the existing building, the provisions of these bye laws shall also apply. (2) Relaxation - Due to the slope profile, topography and irregular plot shapes and sizes prevalent in the Shillong Cantonment, the Authority is at liberty to exercise discretion in the side and rear setbacks without affecting the P.C & FSI. Such order shall be given in writing with justifications. 72. PROVISION WITH RESPECT TO NATIONAL BUILDING CODE (NBC) - (1) Any aspect not covered in these bye -laws; the NBC shall be the reference document regarding the various aspects as required. 73. SAVINGS – The existing buildings approved by the Board shall remain valid and the buildings erected as per the building plans approved by the Board before the date of entry into force of this Bye -laws shall also be valid. 74. INTERPRETATION TO BE IN CONSONANCE WITH CANTONMENTS ACT, APPLICABLE RULES AND POLICIES - Notwithstanding anything contained hereunder, the provisions of this Building Bye -Laws shall at all times be in consonance and within the provisions of the Act and other statutory rules under the Act. Whenever any discrepancy or ambiguity arises, the Ac t shall apply and shall prevail. The provisions of the Act , 2006 are in built into these Bye -Laws and shall be read as part of the Bye -Laws for understanding and applying the Bye -Laws. Similarly, the terms of lease, terms of old grant and such other terms as per the existing policies or any policy issued in this regard from time to time shall prevail and the Building Bye -Laws now promulgated shall be within the meaning of these policies and shall not be in any way contrary to the said policy terms. To the s aid extent, the terms of these Building Bye - Laws are conditional. [F. No. SHG/7/BLDG BYE -LAW/2025] SOUVIK, IDES Chief Executive Officer AFFIDAVIT (For Parking Space a s per Bye Law No. 4(6)/ Resi dual Floor as per Bye Law No. 2. (93)) AFFIDAVIT CUM UNDERTAKING BY OWNER OF BUILDING 1. That I / We ………………………….................................................................. S/o / W/o ............................................................. Age ........................ R/o .............................. .............. do hereby solemnly affirm and declare as under: - 2. That the deponent(s) is/ are competent / authorized to submit this Affidavit. 3. That the deponent has submitted the building plan application for sanction of building plan of the plot at …………………………………. 4. That Parking provision/ re sidual floor is proposed for the building as per the submitted building plans and accepts any modification made there to by the Authority. 5. That the residual floor / parking space sanctioned shall not be used for any other purpose except as specified in the bye -laws. 6. The approved parking and circulation spaces shall not be converted to any other use (habitable or non -habitable), space for generator sets, sentry sheds etc. The parking and circulation spaces shall not be converted or blocked or used for any other activity. 7. That the Authority will be free to take any action if the parking spaces / residual floor are being occupied by the deponent(s) in case of violation of this undertaking. This stipulation shall also be applicable on such person to who m it is sold / transferred. DEPONENT Verification: Verified at .................... on this ............................day of .......................... that the contents of the above affidavit are true and correct to the best of my knowledge and belie f and nothing has been concealed therefrom. DEPONENT FORM A INDEMNITY BOND FOR BASE MENT (As Per Bye Law No. 5 (1)(ii )) (To be submitted by applicant through e -Chhawani portal) TO BE SUBMITTED ON NON -JUDICIAL STAMP PAPER OF RS. 20/ - DULY ATTESTED BY THE OATH COMMISSIONER/MAGISTRATE FIRST CLASS Indemnity bond is executed by Shri/Smt.___________________ S/o, D/o Shri _______________ R/o ________________ hereby called Applicant of Plot No./Holding No./Bungalow No. ___________ in Block No./War d No. _____________________ situated at road / street ____________________ survey / GLR Sy No. ___________________ Cantonment in favour of the Competent Authority. Whereas the Applicant has submitted the plan of basement and whereas the Applicant has represented to the Competent Authority that if sanction is granted for the construction of the said basement the Applicant shall indemnify the Competent Authority of any loss at time of digging of foundation of the said basement or in the cou rse of construction of the basement or even thereafter. And whereas the said Applicant has further agreed to indemnify the Competent Authority for any claims put up against the Authority either by way of damage, compensation or in any other way in case the Authority is required to pay any such amount to any person or the Applicant or Applicants of the adjoining properties. The Applicant hereby agrees/free and undertake to indemnify the Authority to pay the full extent of the amount of the Authority may requ ire to pay the extent hereinabove mentioned. The Applicants further undertakes/undertake and agree to indemnify the Authority for any such amount the Competent Authority may require to pay / free either by way of compensation or damage or any other amount and further undertake to indemnify the authority of all cost and expenses that the Authority may require to defend such action in any court of law. The Applicant undertakes/undertake that no excavation shall be carried out beyond permissible boundaries of plot. Any damage occurring during or due to excavation made at site to public sewer, water drains shall be made good by the Applicant. In consideration of the above matter, undertaking and indemnity given by the said Applicant, the Authority hereunder in t his behalf grant the sanction to construct the basement to the said Applicants. In witness hereof, the Applicant above mentioned puts/put their hands and seal to the said indemnity bond on this ____________ day of ____________ (Executants) (1) ___________ ________ (Applicant) (2) ___________________ Witness: (1) _________________ (2) _________________ FORM B CERTIFICATE REGARDING SAFETY FROM NATURAL HAZARDS AND STRUCTURAL SAFETY(AS PER BYE LAW NO. 5(1)(vii )) (To be submitted by structural engineer and ap plicant through e -Chhawani portal) To, Chief Executive Officer Shillong Cantonment Board Shillong Cantt Sir/ Madam, I hereby certify that the erection/ re -erection or addition/ alteration in building No.__________________ on / in plot no. /Holding No./ Bungalow No._____________________ in block no./Ward No.________________________ situated at road / street _____________ survey / GLR Sy No. ______________________ of _____________________________ Cantonment has been undertaken by me. I certify that the bui lding plans submitted for approval adhere to the safety requirements of Bye-laws. It is certified that the structural design including safety from natural hazards based on soil conditions has been duly incorporated in the design of the building and these p rovisions shall be adhered to during the construction. I, being a structural engineer, certify that the erection/ re -erection or addition/ alteration satisfy the requirements of structural stability and all such alterations, repairs involving walls, column s, beams, roof, footings, foundations etc., are covered under the provisions of building bye-laws requiring compliance. Signature of Engineer _____________________________ Name in block letters _____________________________ Address _____________________________ __________________________ _____________________________ Signature of Applicant _____________________________ Name in block letters _____________________________ Address _____________________________ ____________ _________________ _____________________________ Dated ____________ FORM C CERTIFICATE FOR SUPERV ISION (AS PER BYE LAW NO. 5(1)(viii )) (To be submitted by Architect / Civil Engineer / Structural engineer and applicant through e - Chhawani portal) To, Chief Executive Officer Shillong Cantonment Board Shillong Cantt Sir/ Madam, I hereby certify that the erection/ re -erection o r addition/ in building No. _________________________ on / in Plot No./Holding No./Bungalow No.___________________________ in Block No./Ward No. _____________________ situated at road / street ____________________ survey / GLR Sy No. ___________________ sh all be carried out under my supervision and I certify that all materials (type and grade) and the Workmanship of the work shall be generally in accordance with the general specification submitted along with the building application and that the work shall be carried out according to the sanctioned plan. I shall be responsible for the execution of the work in all respects. Signature of Architect / Civil Engineer / Structural Engineer _______________________________ Name of Architect / Civil Engineer / Struct ural Engineer _______________________________ License no. Of Architect / Civil Engineer / Structural Engineer _______________________________ Signature of Architect / Civil Engineer / Structural Engineer _______________________________ Signature of Applica nt _____________________________ Name in block letters _____________________________ Address _____________________________ _____________________________ _____________________________ Dated ____________ _________________ FORM D NOTICE FOR COMMENCEMENT OF WORK (Bye Law No. 13) To, Chief Executive Officer Shillong Cantonment Board Shillong Cantt Sir/madam, I hereby state that the erection/ re -erection or addition/ in building No._________________________ on / in Plot No./Holding No./Bunga low No.___________________________ in Block No./Ward No. _____________________ situated at road / street ____________________ survey / GLR Sy No. ___________________ Cantonment will be commenced on ________________ as per your permission granted vide offic e letter no. ___________________________ dated_____________________ under the supervision of____________________________________ Architect / Civil Engineer /Structural Engineer / in accordance with sanctioned plans. Signature of Applicant ________________ _____________ Name of Applicant _____________________________ (IN BLOCK LETTERS) Address of Applicant _____________________________ _____________________________ _____________________________ Dated ____________ FORM E NOTICE ON COMPLETION OF BUILDING (Bye Law No.15 (1)) (Section 242 of the Act) To, Chief Executive Officer Shillong Cantonment Board Shillong Cantt Sir/madam, 1. We hereby certify the erection/ re -erection or addition/ in building No. _________________________ on / in Plot No./Holding No./Bungalow No.___________________________ in Block No./Ward No. _____________________ situated at road / street ____________________ survey / GLR Sy No. ___________________ has been supervised by the undersigned and is strictly in accordance with the plan sanctioned vide letter No.__________ ____________ dated _____________. No provisions of the building bye -laws have been transgressed. The work has been completed to our satisfaction and the Workmanship and materials used strictly a dhere to the general and detailed specifications. Drainage/ sanitation/ water supply works have been executed as per building bye -laws and sanctioned plan. No provision of the building bye -laws and conditions prescribed or orders issued thereunder have bee n transgressed in the course of the work. The building is fit for use for which it has been erected / re -erected or altered/ constructed and enlarged. 2. Certificates: 2.1 Certified that the building/s has/ have been constructed according to the Sanctione d Plan and structural design which incorporate the provisions of structural safety as specified in relevant prevailing IS Codes / Standards/ Guidelines. 2.2 Certified that water harvesting as well as waste water re -cycling systems have been provided as per the sanctioned building plan. 2.3 It is also certified that construction has been done under our supervision and guidance and adheres to the drawings submitted and the records of supervision maintained by us. 3. Permission to occupy or use the building m ay be granted. 4. Any subsequent change from completion drawings will be the responsibility of the Applicant (s) Signature of Applicant ____________________________________ Name ___________________________________ Address ____________ ________________________ Signature of Supervisory Architect ____________________________________ License No. ____________________________________ Name ____________________________________ Address ____________________________________ Signature of Structural Engineer ____________________________________ License No. ____________________________________ Name ____________________________________ Address ____________________________________ FORM F CERTIFICATE FOR COMPLETION -CUM -OCCUPANCY OF BUILDING (Bye Law No. 15(2)) To, ____________________________ ____________________________ ____________________________ ____________________________ Sir/ madam, With reference to your notice of completion dated ______________________________ I hereby certify that building, as per description below at _______________________________________ ___________________________________________________ (address) whose plans were sanctioned vide san ction no _______________________ dated _________________ has been inspected to ascertain if the same conforms to building bye -laws in respect of the structural safety, hygienic and sanitary conditions inside and in the surrounding. It is declared fit for o ccupation. The details of the construction work completed are as follows: Brief description of each block with area: 1. _________________________________________________________________ 2. _________________________________________________________________ 3. _________________________________________________________________ 4. _________________________________________________________________ 5. _________________________________________________ ________________ 6. _________________________________________________________________ 7. _________________________________________________________________ 8. _________________________________________________________________ 9. _____________________________ ____________________________________ 10. ________________________________________________________________ 11. ________________________________________________________________ 12. ________________________________________________________________ Letter No._ _____________ Office Stamp Date__________________ Chief Executive Officer Shillong Cantonment Board Shillong Cantt Uploaded by Dte . of Printing at Government of India Press, Ring Road, Mayapuri, New Delhi -110064 and Published by the Controller of Publications, Delhi -110054 .

Never miss important gazettes

Create a free account to save gazettes, add notes, and get email alerts for keywords you care about.

Sign Up Free